10-344-013FOOTINGS AND COLUMNS SCHEDULE ALL SUMS- SHALL BE A MINIMUM OF 4"THICK (3000 PSI AT 28 DAYS MINIMUM) WITH 6" X 6" - 10/10 W.W.M. ON WELL COMPACTED FILL AND WITH A 6 MIL VAPOR BARRIER BETWEEN SLAB AND FILL EXISTING CONC.TIE BEAM GENERAL STRUCTURAL NOTES 2. SOIL STATEMENT: INSPECTION OF THE SITE INDICATES UNDISTURBED SAND AND LOOSE ROCK WITH A BEARING PRESSURE CAPACITY OF 2,000 PSF. IF ANY OTHER CONDITION ARE ENCOUNTERED ARCHITECT SHALL BE NOTIFIED BEFORE CONTINUING WITH WORK. 2. TIE MEAM: A. ALL CAST -IN -PUCE CONCRETE TIE MEAM IN THIS JOM SHALL ME REINFORCED WITH 4 # 3 TIES AT 12" O.C. AT THE CORNERS AND AT EACH SIDE OF TIE COL. AND AT 415" O.C. ELSEWHERE B. CONTINUITY OF THE REINFORCING SHALL ME PROVIDED AT CORNERS BY BENDING TWO 2 BARS FROM EACH DIRECTIONS AROUND THE CORNER 30 INCHES OR MY ADDING TWO 2 # 5 BARS WHICH EXTEND 30 INCHES EACH END FROM THE CORNERS. 3. CONCRETE: A. ALL CAST -IN -PUCE CONCRETE IN THIS JOB SHALL ATTAIN A D( MINIMUM COMPRESSIVE STRENGTH (F'C) AT 28 DAYS OF 4000 P.S.I. M. CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF ACI 301-89 "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS." C. CONCRETE BLOCK WORK SHALL CONFORM TO ALL REQUIREMENTS AND SHALL BE REINFORCED WITH 1 # 9 UDDER TYPE HORIZ. REINFORCEMENT SPACED EVERY OTHER COURSE. Ld D. ALL MASONRY WALLS ARE DESIGNED AS HEARING WALLS, AND SHALL BE IN PUCE BEFORE SLAMS, MEAMS AND COLUMNS ARE POURED. ALL co HEARING MLOCK UNITS SHALL CONFORM TO ASTM C 90, "STANDARD SPECIFICATIONS FOR HOLLOW LOAD BEARING CONCRETE MASONRY UNITS," MORTAR SHALL CONFORM TO ASTM C270, TYPE "M". D-2. GROUT FOR THE CELLS TO BE 3000 PSI MINIMUM "PEA-GRAVEL"CONCRETE a" TO 11" SLUMP. D-3. MASONRY WALLS SHALL CURE AT LEAST THREE DAYS TO GAIN STRENGTH BEFORE POURING GROUT. D-4. WHEN GROUTING IS STOPPED FOR ONE HOUR OR LONGER,THE GROUT SHALL BE STOPPED EXISTING CONC. FOOTING 1-1/2" BELOW THE UPPERMOST UNIT. D-5. GROUT SHALL WE POURED IN LIFTS NOT TO EXCEED 4' MAXIMUM. " DRILL 3/4"X6 1/2" HOLES TO RECEIVE # 5 BARS. FILL HOLES WITH SIKADUR-31 HI -MOD DXY GRPUT OR EQUAL MRF INSTRUCTIONS MIN 6" EMBED )P & BOTTOM) 2#5 IN CONC. FILLED CELL XISTING CBS AAS. WALL 2#5 VERT. DOWELL E. PROVIDE 1-9 HORIZONTAL JOINT REINFORCEMENT UDDER TYPE @ 16 O.C. NEWnFC1 O N EXIST. WALL DETAIL THE CONTRACTOR SHALL ENSURE THE VERTICAL CONTINUITY OF ALL CELLS TO BE FILLED AND SHALL MAINTAIN THOSE CELLS FREE AND CLEAR OF ANY AND ALL DEBRIS TO PROVIDE A CONTINUOUS AND UNOBSTRUCTED WALL CAVITY FOR MAXIMUM HEIGHT OF 12 FEET. ALL VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT THE TOP AND BOTTOM OF THE CELL TO ME GROUTED.MINIMUM LENGTH 8"X12" CONC.TIE BEAM OF UP SPICES =48 MAR DIAMETERS TYPE "M" MORTAR 2,500 PSI SHALL BE USED 2 5 CONT. TO PUCE ALL UNITS . CONTRACTOR SHALL PROVIDE CLEAN OUT OPENING AT THE ELEV.- SEE PUN - BOTTOM OF ALL CELLS TO ME GROUTED AND AT ALL REINFORCING SPLICES LOCATION FOR PROPER VISUAL INSPECTION OF CONTINUOUS CONCRETE FLOW.REINFORCED UNITS MASONRY SHALL ME IN ACCORDANCE WITH THE STANDARD SPECIFICATION FOR THE DESIGN AND CONSTRUCTION OF LOAD HEARING CONCRETE MASONRY OF THE NATIONAL CONCRETE MASONRY ASSOCIATION AND THE PROVISIONS OF ACI 531, "MUILDING CODE REQUIREMENTS FOR CONCRETE MASONRY ".--F---ADD 2 4. WOOD: WHEN T.B DEPTH EXC WOOD FRAMING MEMMERS OTHER THAN TRUSSES SHALL ME #2 SOUTHERN 36" ADD #4 "1" BARS �-� PINE WITH A FIBER BENDING STRESS OF 1200 PSI, SIZES SHOWN ARE EA FACE "SPACED AT A NOMINAL. DISTANCE= d6 5. REINFORCING STEEL: :E: I A. REINFORCING STEEL SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH ACI 31 a-a9. B. REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO I ADD 7 BOT. F T.B ASTM A 615, GRADE 60. C. ALL WELDED WIRE FABRIC SHALL CONFORM TO ASTM A 185. STD. H K TYP. D. REINFORCING TO BE HELD SECURELY IN POSITION WITH STANDARD ACCESSORIES DURING PLACING OF CONCRETE. " WINDOW OPEN G S' E. ALL TOP REINFORCING SHALL TERMINATE WITH STANDARD HOOKS (HEARING END) (BEARING END) AT DISCONTINUOUS EDGES. F. ALL MOTTOM MARS SHALL HEAR 6" MINIMUM OVER SUPPORTS, u.o.N. TIRRUP SPACING AT 12" MAX BEAM DROP DETAI 6. MINIMUM CONCRETE OVER REINFORCING; MINIMUM CLEAR COVER, IN. A. CONCRETE AGAINST AND PERMANENTLY EXPOSED TO EARTH (UNFORMED FACES) 3 ....................... 8"X12" CONC. CAP W/4#5 BARS M. CONCRETE EXPOSED TO EARTH OR WEATHER is #3 TIE 0 36"0/ (FORMED FACES): A. #6 BARS AND LARGER ..........................2 B. #5 BARS AND SMALLER .........................1 1/2 C. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: a"X16" CONC. BLOCK A. SUBS AND WALLS.............................3/4 W/ i�g WIRE REINF. TRUSS TYP. M. MEAMS AND COLUMNS ...........................1 1/2 ( ) 7. STRUCTURAL STEEL: A. STRUCTURAL STEEL SHALL COMPLY WITH RISC "SPECIFICATIONS FOR DESIGN, FAMRICATION AND ERECTION FOR STRUCTURAL STEEL EVERY OTHER COURSE MUILDINGS," LATEST EDITION. B. STRUCTURAL STEEL SHAPES AND PLATES SHALL CONFORM TO ASTM A 36. C. ANCHOR BOLTS SHALL CONFORM TO ASTM A 307. D. BOLTS SHALL CONFORM TO ASTM A 307. E. STRUCTURAL STEEL TUBE COLUMNS SHALL CONFORM TO ASTM A 590, GRADE M, FY= 46 KSI. a. WELDING: A. WELDING SHALL BE DONE WITH E-70 ELECTRODES. CD I 9. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS OF EXISTING STRUCTURES AFFECTING NEW CONSTRUCTION PRIOR TO COMMENCING ANY WORK. ANY VARIATIONS IN ACTUAL FIELD CONDITIONS/DIMENSIONS FROM THOSE SHOWN ON THE CONTRACT DRAWINGS SHALL BE REPORTED TO THE ARCHITECT/ENGINEER FOR DETERMINING THE NEED OF REDESIGN 1#6 IN CONC. FILLED CELL PRIOR TO CONTRACTOR'S SUMMITTAL OF SHOP OR WORKING DRAWINGS @ 40" O.0 FOR REVIEW. `'-- 10. SUBMITTALS TO STRUCTURAL ENGINEER: A. REINFORCING STEEL SHOP DRAWINGS. M. TRUSSES SHOP DRAWINGS AND DESIGN DATA. 3/4" TEXTURE STUCCO C. STRUCTURAL STEEL SHOP DRAWINGS. 11. ALL CONSTRUCTION SHALL BE DONE IN ACCORDANCE WITH ALL 4" C NC B 0 yyE ��CC MW��TEpp� FALL APPLICAMLE FEDERAL, STATE, AND LOCAL ORDINANCES, INCLUDING THE W/ 6 x -'WU4 x1.4 .1r� (T1T. v. 0 N.) SOUTH FLORIDA BUILDING CODE, LATEST EDITION. 12. DIMENSIONS AND CONDITIONS: ALL DIMENSIONS AND CONDITIONS SHALL BE VERIFIED MY THE CONTRACTOR IN THE FIELD PRIOR TO CONSTRUCTION. ANY DISCREPANCIES SHALL ME MROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALE. SCALE IS FOR GUIDELINE PURPOSES ONLY. IF DIMENSIONS ARE UNCLEAR, DO NOT SCALE, REQUEST CLARIFICATION FROM THE ARCHITECT OR ENGINEER. 13. METHODS & SAFETY: THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL METHODS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION. III CONSTRUCTION SITE SAFETY, INCLUDING ALL ADEQUATE TEMPORARY MRACING AND SHORING, IS THE SOLE RESPONSIMILITY OF THE CONTRACTOR. THE CONTRACTOR SHALL COORDINATE THE STRUCTURAL WORK WITH THE WORK OF ALL OTHER TRADES. 14. PROTECTION OF EXISTING CONSTRUCTION: III EXISTING CONSTRUCTION WHICH IS TO REMAIN SHALL NOT BE DAMAGED. CONTRACTOR SHALL LOCATE AND PROTECT -I CONCEALED PIPES AND CONDUITS PRIOR TO DEMOLITION AND EXCAVATION AND TAKE APPROPRIATE ACTION TO PROTECT I I I I: THEM AND TO PROVIDE FOR SAFETY. 15. CONSTRUCTION LOADS: IT IS THE RESPONSIMILITY OF THE CONTRACTOR TO EMPLOY THE NECESSARY PROFESSIONAL SERVICES TO DETERMINE THE NECESSARY METHODS AND SUPPORTS REGARDING FORMING AND CONSTRUCTION LOADS. 16. CONFLICTS IN DOCUMENTS: IF CONFLICTS OCCUR IN OR BETWEEN ARCHITECTURAL AND ENGINEERING DOCUMENTS, BETWEEN DOCUMENTS AND FIELD CONDITIONS OR OTHERWISE, THE CONTRACTOR SHALL IMMEDIATELY CONTACT THE ENGINEER FOR CLARIFICATION AND �-- DIRECTION BFFORE PROCEEDING. THE CONTRACTOR SHALL COORDINATE ALL DIMENSIONS BETWEEN ARCHITECTURAL AND STRUCTURAL DRAWINGS PRIOR TO PROCEEDING WITH THE WORK. WF 36 SECTION 6 N.T.S EXISTING CONC.TIE BEAM DRILL 3/4"X6 1/2" HOLES TO RECEIVE # 5 BARS. FILL HOLES WITH SIKADUR-31 HI -MOD DXY GRPUT OR EQUAL MRF INSTRUCTIONS MIN 6" EMBED )P & BOTTOM) 1#5 IN CONC. FILLED CELL XISTING CBS VIAS. WALL 3"Xi" WINDOW SILL1 #5 W/2#5 1#5 VERT. DOWELL EXISTING CONC. FOOTING NEW LC)ON EXIST. WALL DETAIL 5/8" "CDX" PLYWOOD NAILED TO EVERY SUPPORT W/ Ad RING SHANK NAILS 0 6" k W/ 10d NAILS 0 4" 0 FDGF 70NF (4' CRICKET 2X8 WOOD JOIST 0 1 EL. +9'-0" (FIELD VERIFY) 2X4 TO BE CONNECTED TO EA. MEMBER W/14ga GALV. STEEL STRAP W/(4) 16d NAILS INTO MEMBER AND INTO 2X4. TYP. REMOVE EXIST WOOD BEAM ONLY AFTER AJUST. PORT SHORE TO SUPPORT EXISTING ROOF PRIOR TO THE START OF WORK IN THIS AREA THE CONTRACTOR SHOULD COORD. FIRST W/ ARCHITECT/ENGINEER. 2X4 WOOD MEMBER (EXIST. WOOD ROOF CONNECTOR RB-2 SECTION 4 SCALE 3/4" = l'-O" 5/9" "CDX" PLYWOOD NAILED TO EVERY SUPPORT W/ Ad RING SHANK NAILS @ 6" & W/ 10d NAILS 0 4" 0 EDGE ZONE (4'-t CRICKET 2X8 WOOD JOIST 0 1 EL. +9'-0." I / (FIELD VERIFY) 2X4 TO BE CONNECTED TO EA. MEMBER W/14ga GAL W/(4) 16d NAILS INTO MEMBER AND INTO 2X4. TYP. 5/8" "CDX" PLYWOOD NAILED TO EVERY SUPPORT W/ Ad RING SHANK NAILS 0 V k W/ 10d NAILS 0 4" 0 EDGE ZONE (4'-B" r' EL. 12'-5" 2X8 WOOD JOIST 0 16" O/C BEYOND _-- e (2) 5/8" DIAM. A- 325 (3)4"Xa" WOOD BEAM - `� TRHU BOLTS NAILED TOGETH R W/lOd NAILS 0 ED 4-1/2" 0 A-307 ANCHOR 1 /4 "U" SADDLE11 (��BLE TIES NG CLOSED TIES 71 3/ 6„ VERT. REINF. DOWELS SAME SIZE & NO. AS VERT. BAR EL, SEE PLANK GROUND FLOORY x-x-x-x-x- '` x _ _ _ r I I -I I I-_ I I I -I I I-- " CD -III -III I I I-1-1 Ln I /2" EXP. JOINT WELDED WIRE FABRIC x --- x x- x- x- x- x 1 1/2- `6 MIL VISQUEEN V) Y � �- FOOTING (SEE SCHEDULE) III- 3" CL. 44 UNDISTURBED LIMEROCK STD. HOOK TYPICAL COLUMN( -FOOTING DETAIL- N. T. S. GRADE I- co Z CONC. COL. BEYOND 2X4 WOOD MEMBER (.EXIST. WOOD ROOF CONNECTOR 2Q EXIST. TO SECTION 1 SCALE 3/4" = 1'-O" EL. 12'-5" EXIST. a" CMU HEARING WALL 5/8" "CDX" PLYWOOD NAILED TO EVERY SUPPORT W/ ad RING SHANK NAILS @ 6" k W/ 10d NAILS 0 4" @ EDGE ZONE (4' EL. +9'-0" OlL (FIELD VERIFY) REMOVE EXIST WOOD BEAM ONLY AFTER AJUST. PORT SHORE ' TO SUPPORT EXISTING ROOF PRIOR TO THE START OF WORK IN THIS AREA THE CONTRACTOR SHOULD COORD. FIRST W/ ARCHITECT/ENGINEER. EL. 1 l'-V 5/8" "CDX" PLYWOOD NAILED TO EVERY SUPPORT W/ ad RING SHANK NAILS 0 6" Ac W/ 10d NAILS 0 4" 0 EDGE ZONE (4'- NVRT-20 CONNECTED TO EA MEMBER W/(7) lid NAILS INTO EA MEMBER 2X8 WOOD JOIST 0 16" O/C ((3)4"Xi",WOOD BEAM / NAILED TOGETHER W/1 Q� NAILS 0 6" STAGERED SECTION 2 f� SCALE 3/4" = 1'-O" 1 1/2" CIRCULAR HOOK. CL. 1 4 L1 -6 IN. r'E" BARS \ a" 2X8 W OD JOIST 0 16" O.0 - CONNECTOR Q3 CONC. COL. BEYOND MIST. WOOD ROOF CONNECTOR 1Q RI-1 SECTION 5 SCALE 3/4" = l'-O" CONC. COL. BEYOND PREFAB WOOD TRUSS SEE PUN FQR CONNECTOR CD 12" 12" STANDARD HOOK �TB a" CMU WALL, SECTION 3 3/4" "C" BARS (TOP OVER EACH SUPPORT) WHERE BARS DIFFER IN TWO ' 1.5 VERTICAL REINF. IN CONC.FILLED CELL (SEE FOUNDATION FOR LOCATION) mk-'11 x CITE" OF �Mfll Bi lILDIN PE -PT. STFtkJCj'L1RAL. S CT10N A ADJACENT SPANS AT A COMMON SUPPORT, THE LARGER BARS SCHEDULED SHALL BE USED. TOP CONT. (CONTINUOUS TOP BARS) UP IN MIDDLE 1/3 OF SPANS WHERE REQUIRED. i 1/3 LMMR 1(�3 L 1/3 MAW OV3 L2 GREATER OF 5„ -� 36 DIAL P L3 OR 1/3 l„2, CL. BARS 3'-6" MIN. 3'-6" MIN 3'-6" MIN. TTT- " 6" 6" N 6r L CONT. _ �, "I" BARS 6 6" MIN. ALL REINF. STEEL IN SAME STIRRUP SPACING AS LAYER UNLESS OTHERWISE NOTED. SCHEDULED. 2" FIRST STIRRUP SPACED FROM FACE OF SUPPORT. L1 L2 NOTES: 1. "L" INDICATES THE URGER OF ADJACENT SPANS. 2, WHERE BOTTOM BARS ARE INDICATED AS CONTINUOUS WITH ADJACENT SPANS, SPLICES, WHERE NEEDED, SHALL BE MADE IN THE END 1/3 OF SPAN WITH 24 DIA. UP. 3. "1" BARS AS SCHEDULED SHALL BE PLACED EACH SIDE OF BEAM. TYPICAL BEAM REINF. PLACING DIAGRAM N. T. S. C1_ U O r- Of�2t1)Ln 1- 0rnLv, N Ln E z `r' 0 M cn ' w = CD c.0 00 LJ U Q W M d' M M r w C) O f 0 00 0 0 �10 O O 0 00 rLLJ l�/ J 0 L� O n REVISION( REVISION2 REMSION3 REVISION4 w S 3