10-662 (2)-037EXIST. PANEL •A' BUS: 200 oA24av, 10, 3w MAIN: M.LO CU BUS/GND. BUS LOAD: (SEE LOAD ANALYSIS) LOAD COND. WIRE TRIP POLE DESCRIPTION CKT No. CKT No. DESCRIPTION POLE TRIP WIRE COND. LOAD (**} -1/4" 3 80 2 EXISTING PANEL "G" 1 2 EXISTING CU-1 2 4O 8 3/4" 6024 3 4 11032 1" 6 50 2 EXISTING AHU-1 5 6 NEW PANEL "G2" 2 100 2 1 1/2" (**) __ -- -- / 1 7 8 1 -- -- -- (*) 1/2" 14 15 1 EXIST. GEN. LTS & RECS 9 10 EXIST. GEN. LTS & RECS 1 15 14 1/2" (*) (*) 11 12 (*) (*) 13 14 (*) (*) 15 16 (*) (*) 17 18 (*) (*) 19 20o EXISTING CKT T (*) 20b NEW GAS WATER HTR IGNITION Q (*) 210 22a EXISTING CKT Q (*) 21b 2215 NEW GEN LIGHTS & RECS Q (*) 5000 5000 1/2" 1/2- 12 12 2/0 2/0 2 2 EXISTING COOKTAP23 EXISTING COOKTAP 24o EXISTING SMALL APPLIANCES 20 12 1500 2415 EXISTING SMALL APPLIANCES 15W 25 26a EXISTING DW 1000 2615 EXISTING GARBAGE DISP. 900 5000 1/2" 12 20 2/1 EXISTING OVEN 27 28a EXISTING REFRIG. 1400 28b EXISTING GEN. LTS &RECS. (*) 29 30a (*) 3015 (*) (*) PART OF THE 3W/SQ.FT. LOAD (**) SEE LOAD ANALYSIS 1T REMOVE EXISTING FULL SIZE 1P-15A BREAKER AND REPLACE WITH NEW TANDEM BREAKERS AS SHOWN. (10) (ED) VOLTS:1 1 PANELEXISTING 3 iJ M.L.O.LOAD: LOAD i• 1 1®®� 1 .. 1 ®® 1 i • 1 �� 1 1 1 EMISSION INIMINIMME111000101 IME..M®.■® .IN.M....® INE..®®.■ GAME ..EMEM1100110 . m....■... mm ..��..� m........ DEEM .■......® 1001M.■..... �� ..■■.... ®....■... m� monsIM01100110 ®..■..... ®AMIE i MIN / 1�IMMI®® iMENOMONEE GAME % mmm MENOMONEE mmmmm 1. PART 1F THE 3W/SQ.FT. LOAD 1. SEE LOAD i 1 • 1 1 11 LOAD CENTERPANEL MTG: FINISH 1 E1 NEW M.L.O./ LOAD: LOAD CU BUS/GN. BUS i •) 1 1�®� 1 .. 1 �� 1 1��� 1 1 i• 1 NEW AHU/CU-4 ®®®®� M MEESE �• MISIMM® 11 �■.�...�■ ©e NDRY REC ■......■ I f ®IMMEMEME■ GAME ■ENOMINEE®' ®..E..... MEME-� • ■,mmmmm mmmmm mmmmm� ®MIME mmmm� mmmmm MIME �� mmmmm mmmmm MMIMIM mmmmm mmmmm HUE0�� mmmm® PART OF 1 1 1 2. (0) PROVIDE AFCI TYPE BREAKER. PROVIDE E. 11 EXISTING 1 I EXISTING RESIDENCE LAUNDRY 3#350KCMIL, CU. ( I THW IN 2 1/2"C. I I OVERHEAD SERVICE I I EXIST. RESIDENCE KIICHLIIJ EXIST. DETACHED GARAGE 11 11 I I EXIST. EXIST. EXIST. I i 3 # 3/0 CU,THW IN 2"C 3 # 3/0 CU,THW IN 2-C 3 # 3/0 CU,THW IN 2"C I I I EXISTING POOL AREA 11 r - - - - - - - - - - - - ---------------------------- I I I _ �------------------T -3#4 & 18(G)-1-1/4"C. I r - - - - - - ------I II I I I I I I s L_ _ 1 L - EXIST. L 1 -I 1 �- 7 r- -� r- 7 3 # 3/0 CU,THW IN 2"C r- 7 r- � r -7 17-----71 EXISTING I I EXISTING I I I NEW I I I I I EXISTING I I / L J 200 A 1 I 1 200 A I I I EXISTING" I PANEL"C" I EXISTING 1 ( EXISTING" I I PANEL"P" I / I I MAIN 1OF2 I I I MAIN tOF2 1 ( I PANEL B ( I PANEL A I ! PANEL G I I I j I I J I ! ! I I I I POOL EQ. I I I I I I I I ! I I I I I PANEL I EXIST 0V I I NEMA 3R I I NEMA 3R ( I I I ( ( ! I I 1 �, 3W, K-7 I TYPE METER l I I I I I I I I I I I I I I I I I I I I I I I I I 7J L____J L__r-_J L__�_�J L__ _._.I L_-__.I EXIST. L-_r.__._I I L 3#4 THW, CU & 1#6 THW, CU. I 1 ( GROUND IN 1 1/4 C. 1 EXIST. L_--------------------------------- ----.-__-__-J I 3#3/0 THW, CU. IN 2"C. I I�'-- EXIST. 1_3 2 & 1#8(G)-1-1/2"C. I 12 CU. GROUND TIED TO MCWP & TO CU. RODS ! `I' METALLIC C.W.PIPE I--- EXIST. u 6'-Ow I 3/4" X 10' LONG COPPER GROUND RODS DRIVEN 1 MIN. I INTO GROUND, MIN. 6'-0" APART. - Electrical Riser Diagram NEW DETACHED GARAGE t I NEW PANEL"G2" TYPE.1 1 NOODVOLTS:120/24OV, • MTG: FLUSH MOUNTED MAIN: 2P-100A CU BUS/GND. BUS LOAD: (SEE LOAD ANALYSIS) i.i 1 1 �� •i 1 1 DESCRIPTION •1 �� 1 1 / 1 mmmmm MIMEM1010 ,mmmmm ®®MMISE M .MIMIMM� �.IMMIMM®® liliiiiiiiiiiil�gvwiltagv-wg� GEN. LIGHTS & RECS GARAGE DOOR OPENER (GFI) ] immoMIME; GEN. LIGHTS & RECS 1 i .........-1,.�M MADE GAME I_�......■ ' 1 11 ■NOMONEE���■t�IMMENIMME■ •, i GEN. LIGHTS & RECS CONCEDE MIN IVAA ®IMMIMEMINE� mmmmm mmmmm 1.■0131001010-FAN .,'=m®=® mmmm® �� mmmmm 1. PART OF 1 1 1 2. COOLING & HEATING LOADS ARE NON -CONCURRENT -PROVIDE HACR TYPE BREAKER. PROVIDE GROUND FAULT TYPE CIRCUIT BREAKER. LOAD ANALYSIS BASED ON 120/208V, 10, 3W I. EXISTING PANEL "A" FEEDS EXIST. PANEL rGr AND NEW PANEL "G2" EXIST. AREA 1596SQFT X 3W/SQFT 4,788 VA NEW AREA 61SQFT X 3W/SQFT 183 VA EXIST. AREA 435SQFT X 3W/SQFT (EXIST. PNL "G7- 1,305 VA NEW AREA 1757SQFT X 3W/SQFT (NEW PNL "G2")- 5,271 VA REST OF LOAD EXCEPT A/C 16,561 VA REST OF LOAD EXCEPT A/C (EXIST. PNL "Gj 11,800 VA REST OF LOAD EXCEPT A/C (NEW PNL "G27 4,200 VA 44,108 VA 1 ST 1 OKVA ® 100% 10,000 VA 24,108 VA @ 40% 13,643 VA A/C 65% HEATER (A/C-1) 7.532 VA A/C 65% HEATER (EXIST. PNL "G j 4,932 VA A/C 65% HEATER (NEW PNL "G21 8,156 VA 44,263 VA/240V = 184.4�1 III. EXISTING PANEL "G" FED FROM EXISTING PANEL EXIST. AREA 435SQFT X 3W/SQFT (EXIST. PNL "Gj- 1,305 VA REST OF LOAD EXCEPT A/C (EXIST. PNL "GI11,800 VA 13,105 VA 1 ST 1 OKVA @ 100% 10,000 VA 3105VA @ 40% 1,242 VA A/C 65% HEATER 4,932 VA 16,174 VA/240V = 67.4 A IV. NEW PANEL "G2" FED FROM EXISTING PANEL NEW AREA 1757SQFT X 3W/SQFT (NEW PNL "G2")- 5,271 VA REST OF LOAD EXCEPT A/C (NEW PNL "G21 4,200 VA 9,471 VA DEMAND LOAD 9,471 VA A/C 65% HEATER 8,156 VA 17,627 VA/240V = 73A A II. EXISTING PANEL "B" FEEDS EXISTING PANEL "P" & NEW PANEL "C" IV. EXIST, PANEL "P" FED FROM EXISTING PANEL "B" EXIST. AREA 1484SQFT X 3W/SQFT 4,452 VA LOADS 12,600 VA EXIST. AREA 180SQFT X 3W/SQFT (NEW PNL" C' 540 VA NEW AREA 552SQFT X 3W/SQFT (NEW PNL" C1 1,656 VA REST OF LOAD EXCEPT A/C 4,500 VA 1ST 10KVA @ 100% 10,000 VA REST OF LOAD EXCEPT A/C (NEW PNL" C1 8,000 VA 2,60OVA @ 40% 1,040 VA REST OF LOAD EXCEPT (EXIST. PNL "Pj 12,600 VA 11,040 VA/240V = 46.0 A 31,748 VA 1 ST 10KVA 0 100% 10,000 VA 21,748 VA @ 40% 8,699 VA A/C 65% HEATER (A/C-2) 4,932 VA A/C 100% COOLING (A/C-4) (NEW PNL-C12,016 VA 25,647 VA/240V = 106.9 A IV. SERVICE LOAD TOTAL EXIST. AREA 3,695 SQFT X 3W/SQFT-11,085 VA TOTAL NEW AREA 2,370 SQFT X 3W/SQFT - 2,370 VA TOTAL REST OF LOAD EXCEPT A/C 57,661 VA 71,116 VA Ill. NEW PANEL "C" FED FROM PANEL "B' EXIST. AREA 180SOFT X 3W/SQFT 540 VA 1 ST 1 OKVA @ 100% 10,000 VA NEW AREA 552SOFT X 3W/SQFT 1,656 VA 61,116 @ 40% 24,446 VA REST OF LOAD EXCEPT A/C 8,000 VA A/C 65% HEAT 25,674 VA 10,196 VA 60,120 VA/240V = 250.5 A 1ST 10KVA 0 100% 10,000 VA 196 0 40% 78 VA A/C 100% COOLING (A/C-4 2,016 VA 12,094 VA/240V = 50.4 A 250.5 A < EXISTING 1350 KCMIL WIRE AMPACITY .w1JIA1, :x ~gyp: 018 jkvc to, PROJECT No. 10034.00 Kane Residence 6695 SW 69 Ave South Miami, FL OWNER John and Ellie Kane 6695 SW 69 Ave South Miami, FL OWNERS REVIEW 06/03/11 Pablo Coraaini I AR - 91716 Luigi Vitalini I AR -13513 1\ rt*� vitalini i i A R CH I T E C T S 300 Aragon Avenue, Suite 330 1 Coral Gables, FL 33134 tel: 305.567.0602 1 fax: 305.446.3197 1 www.vcmiami.com FL Registration AA26001654 SHEET NO. E - 201