06-240-026a
PROJECT.... KYOJON BUFFET
SANITARY SIZING
FIXTURE TYPE NO F U /EACH TOTAL MIN TRAP SIZE
URINAL
1
4.0
4.0
3"
WATER CLOSET
5
4.0
20.0
3"
LAVATORY
6
1.0
60
11/4"
FLOOR DRAIN
16
3.0
48.0
3"
HAND SINK
5
20
100
1 1/2"
3-COMP SINK
1
3.0
3.0
2"
DISHWASHER
1
3.0
3.0
2"
MOP SINK
1
2.5
2.5
3"
FLOOR SINK
2
3.0
6.0
2"
TOTAL
1 38
1 25.5
102.5
1-
TOTAL SANITARY FIXTURE UNITS= ............ 102.5
MINIMUM SIZE MAIN SANITARY LINE all 1/8" SLOPE........... 4 ....... .
HOT & COLD WATER SIZING
FIXTURE TYPE NO. C.W.F.U./EA TOTA H.W F.U./EA. TOTAL
URINAL
1
3.0
3.0
-
-
WATER CLOSET
5
5.0
25.0
-
-
LAVATORY
6
1.5
9.0
1.5
9.0
HAND SINK
5
15
75
15
is
3-COMP SINK
1
3.0
3.0
3.0
3.0
DISHWASHER
1
2.25
2.25
225
2.25
MOP SINK
1
2.25
2.25
2.25
2.25
ICE MACH.
1
1.5
1.5
-
-
HOSE BIBB
1
3.0
3.0
-
-
TOTAL
22
23.0
56.5
10.5
24.0
TOTAL C W F.U. _ ( 56.5 . 24:0 ) = 80.5
MINIMUM SIZE WATER SERVICE.....11T
MINIMUM SIZE WATER METER.....1 ........
WATER CLOSET (REGULAR)
® WATER CLOSET (HANDICAP) (1)
® URINAL
LAVATORY (REGULAR)
LAVATORY (REGULAR)
® LAVATORY (HANDICAP) (1)
SINK
MOP SINK
AMERICAN STANDARD "CADET" 16-1/2"H.
MODEL #2377.100 COLOR WHITE. SEAT
"LAUREL" MODEL #5311.012 COLOR WHITE,
AMERICAN STANDARD "CADET" 16-1/2"H.
MODEL #2377100 COLOR WHITE SEAT
"LAUREL" MODEL #5311.012 COLOR WHITE.
INSTALLED SO TOP OF SEAT 17"-19" FROM
FINISHED FLOOR.
AMERICAN STANDARD "TRIMBROOK"
MODEL # 6561.017 COLOR WHITE
FLUSH VALVE "SLOAN ROYAL"
MODEL # 186-1. MT.17" TO TOP OF
RIM FOR HANDICAPPED USE.
AMERICAN STANDARD "AQUALYN"
MODEL # 0476.028 COLOR WHITE
FAUCET SET AMERICAN
STANDARD "RELIANT" MODEL #
2385.500
AMERICAN STANDARD "DECLYN"
MODEL # 0321.026 COLOR WHITE
FAUCET SET AMERICAN
STANDARD "RELIANT" MODEL #
2385.060
AMERICAN STANDARD "CADET" MOD
# 0419.444sgg COLOR WHITE. FAUCET
SET AMERICAN STANDARD "RELIANT"
MODEL # 2385.500
AMERICAN STANDARD "PENLYN"
MODEL 1110373.027 COLOR WHITE .
FAUCET MODEL # 2385.060.
AMERICAN STANDARD "FLORWELL"
MODEL # 7741000 COLOR WHITE
RIM GUARD MODEL # 7745.811.
FAUCET MODEL # 8344.112
WATER HEATER EXISTING
1. MOUNTING HEIGHT PER ADA STANDARD. INSULATE WATER AND DRAIN LINE.
1 PROVIDE CUT SHEETS FOR REVIEW PRIOR TO PURCHASE.
3. PLUMBING FIXTURES TO COMPLY WITH TABLE 604.4 F.B.C.
4. ALL WALL HUNG PLUMBING FIXTURES SHALL COMPLY WITH F.B.C. 2S10.5.1.1, 2510.S.12 AND 2510.5.1.3
PLUMBING FIXTURES
FLOOR DRAIN
FIN FLOOR
FLOOR DRAIN DETAIL
N.T.S.
NOTES:
1. INSULATION OF ALL GAS PIPING SHALL BE
PER F B.0 (GAS PIPING STANDARD)
2, ALL GAS PIPING TO BE #40 GALVANIZED
STEEL PIPE.
3. GAS PIPING TO COMPLY WITH ANSI B36.10
ASTM A 53 OR ASTM A 106.
4. PRESSURE TEST GAS PIPING FOR LEAKS
PRIOR TO CONNECTING GAS SUPPLY,
NOTES:
- VERIFY LOCATION OF
EQUIPMENT PRIOR TO
INSTALLATION.
- VERIFY ALL BTU's WITH
MANUFACTURER'S SPECS
PRIOR TO INSTALLATION.
NOTE.
GAS PIPING BASED ON
A PRESSURE DROP OF .5 IN WC
MAX DISTANCE =80'
PLUMBING LEGEND
- - - - -
COLD WATER LINE
- - 1102 - - 110s - -
110" HOT WATER LINE
uo9 16oa•
140• HOT WATER LINE
SANITARY LINE
WASTE/ VENT LINE
G
GAS LINE
®
12" x 12" FLOOR SINK
)E)
FLOOR DRAIN
►N
SHUT-OFF VALVE
BIBB WITH S.O.V.
H B +HOSE
& VACUUM BREAKER
A.A.V.
AIR ADMITTANCE CHAMBER
TOTAL GAS CONSUMPTION
ITEM
N0.
DESCRIPTION
BTUH
1.
15' HOT FOOD COUNTER
10,000
2.
CHINESE COOKING WOK
60,000
3.
CONVECTION OVEN
54,000
4.
GRILLE
120,000
5.
CHAR BROILER
80,000
6&
FRYER
100,000
68.
FRYER
100,000
7.
FRYER
100,000
8.
JAPANSESE HOT PLATE
24,000
TOTAL
648,000
CD
O
3/4" O
V
1„ 11/4 �
V
^1 1/4"GAS LINE IN SLEEVE
BELOW SLAB.
OFILL SLEEVE WITH
1 1 1/4" G LIQUID FOAM.
G
1/4" 1 114"
I 1 c�
114"GAS LINE IN SLEEVE �\ �� V
BELOW SLAB.
FILL SLEEVE WITH
LIQUID FOAM.
V
V
O(� 1 if4"
V O
/ 2
6 6A 6 1/4"
/ 66
O V 1/2"
V
v c+ 3/4"
V
�3/4- 3/4"
/ 3/4"
11/4" G
1 1/2 �GASG GAS SOLENOID
.---VALVE. INTERLOCK
W/ ANSUL SYSTEM.
1/2" GAS LINE
TO GAS SUPPLY
1 1/2" GAS S.O.V. VERIFY LOCATION
UP 1 AND CONNECTION
POINT IN FEILD
-REGULATOR
FILL SLEEVE WITH / \
LIQUID FOAM GAS RISER
N.T.S.
11/4" CW SUPPLY LINE
BACKFLOW PREVENTER ASSEMBLY
N.T.S.
NOTES:
1. VERIFY LOCATIONS OF EXISTING WATER AND SANITARY SUPPLY CONNECTION POINTS WITH CITY OR LOCATE ON EXISTING SITE.
2. VERIFY EXISTING SIZES AND INVERTS OF EXISTING UTILITIES PRIOR TO INSTALLATION OF NEW WATER AND SANITARY LINES.
3. THE MINIMUM SLOPE FOR ALL SANITARY LINES SHALL BE 1/8" PER FOOT. PIPING TO BE PVC SCHEDULE #40 DWV.
4. ALL INTERIOR POTABLE WATER SERVICE PIPING TO BE COPPER TYPE K OR L. ANY SUBSTITUTIONS MUST BE APPROVED BY ENGINEER
5 ALL HOSE BIBBS TO HAVE SHUT OFF VALVES AND VACUUM BREAKERS.
6 MAIN WATER SERVICE TO BE SIZED PER PLANS.
THREADED CLEANOUT PLUG
GRADE
12"x12"x4" CONCRETE SLAB, MIN.
1Ox10 WIRE MESH
FILL VOID WITH OILED SAND
CLEANOUT FITTING WITH
PVC PLUG.
TWO-WAY CLEANOUT TEE
OR LONG SWEEP
CLEANOUT TO GRADE (CTG) DETAIL
NTS•
INTERIOR PARTITION
WALL CONSTRUCTION
PIPE
SIZE
24"
3'WALL
A-
4"
46"
PLUMBING:
1. ALL WORKMANSHIP & MATERIALS SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE NATIONAL,
STATE, LOCAL CODES, RULES & ORDINANCES.
2. CONTRACTOR SHALL VISIT THE JOB SITE & THOROUGHLY FAMILIARIZE HIMSELF WITH ALL
EXISTING CONDITIONS.
3. ALL MATERIALS SHALL BE NEW.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST-CLASS
WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE.
5. ALL EXCAVATION & BACK FILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE A
PART OF THIS CONTRACT.
6. REQUIRED INSURANCE SHALL BE PROVIDED BY THIS CONTRACTOR FOR PROTECTION AGAINST
PUBLIC LIABILITY & PROPERTY DAMAGE FOR THE DURATION OF WORK.
7• CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS & TEST. SUBSTITUTIONS
BY THE CONTRACTOR SHALL HAVE PRIOR APPROVAL. ANY CHANGES MADE WITHOUT
APPROVAL WILL BE PAID BY THE CONTRACTOR TO RETURN TO THE ORIGINAL DESIGN
B. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES,
PIPING, EQUIPMENT, ETC.
9. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
PROCESS OF CONSTRUCTION.
10. VERIFY LOCATION, SIZE, TRAPS, INVERTS OF ALL EXISTING UTILITIES PRIOR TO BEGINNING
CONSTRUCTION. ADVISE ENGINEER OF ANY DISCREPANCIES ANY COST
RESULTING FROM DISCREPANCIES NOT REPORTED AT THIS TIME SHALL
BE PAID BY THE CONTRACTOR
11. WATER PIPING TO BE TYPE "L" COPPER BELOW GRADE, TYPE "M" COPPER ABOVE GRADE.
12. SOIL, WASTE & VENT PIPING TO BE PVC. #40 DVW. WASTE & VENT PIPING ABOVE SLAB PVC.,
IF APPROVED BY LOCAL AUTHORITIES HAVING JURISDICTION.
13. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS
14. N/A
15. WHERE DISSIMILAR METALS ARE TO BE JOINED, APPROVED INSULATING UNIONS SHALL
BE USED.
16. INSULATE HOT WATER LINES WITH 1" THICK SNAP ON INSULATION FIRST 8 FEET FROM
WATER HEATER.
17. CONDENSATE LINES TO BE COPPER/PVC DEPENDING ON PROJECT REQUIREMENTS.
INSULATE WITH 1/2" THICK ARMAFLEX INSULATION.
18. CONTRACTOR SHALL GUARANTEE ALL MATERIALS & WORKMANSHIP FREE FROM DEFECTS
FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. CORRECTION
OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE
BEEN DAMAGED THEREBY.
19. NO PVC PIPING TO BE USED IN COMMON PLENUM AREAS.
20. SEE PLUMBING PLANS FOR ADDITIONAL REQUIREMENTS.
SPECIFICATIONS
WATER HEATER IS EXISTING
UPGRADE OR REPLACE IF
NECESSARY TO MEET CURRENT
CODE REQUREMENTS. MIXING
VALVE
HEAT
TRAPS
T&P TO GROUO
WITH 2" AIR GAP
RELIEF VALVE
2"AIR GAP
I I CHROME PLATED ACCESS
--- COVER W/ CLEANOUT PLUG.
CONCRETE SLAB
WALL CLEANOUT DETAIL
N.T.S.
SANITARY OR
WASTE PIPING
HOT WATER
SUPPLY
COLD WATER
,�04• ,14q 1 SUPPLY
WATTS BRVT
�- PRESSURE
RELIEF VALVE
PRESSURE
RELIEF DRAIN
WITH 2" A-- - -
2"AIR GAP
WATER HEATER
N.T.S.
EXISTING
WATER TAP
M EXISTING
WATER METER
�BACKFLOW
S.O.V.
H.B. W/ S.O.V.
& VAC BKR
WATER SERVICE CONNECTION DETAIL
N.T.S.
MC
c
FW
W
W d) >
X
#
CC_
C i
r
>,\
0
(10
lob
'M
Sk
N
0
(_0
(('')
_
N
_u
ai
0
1.
ELM. ap3 CM44 NT
02-24-M
no,
revision I
date
REVISION 02/24/06
Issued for permit
PERMIT' SET H/30/05
<
NOTE:
ANY DESIGN CHANGES, TO THE SYSTEM COVERED
BY THESE PLANS WITHOUT PRIOR APPROVAL OF
THE ENGINEER WHO PREPARED THESE PLANS, WILL
Sheet:
1
plumbing risers
dtai is & SeCS
P
NULL AND VOID THESE PLANS AND THE REVISED
INSTALLATION. IN ADDITION, ALL EXPENSES
°
1
ASSOCIATED WITH RETURNING THE SYSTEM TO ITS
ORIGINAL DESIGN WILL BE THE RESPONSIBILITY
OF THE COMPANY WHICH APPROVED THESE CHANGES
'
1 NIIFORMICA
►III ASSOCI ATE6.
Consulting Engineers
3100 N.W. Boca Raton Blvd.
Suite #117
Boca Raton, R 33431
IF
368-3611 FAX' (561) 368-4733
dwa to #00008818
F. Formica, P.E.
�#19733
m*aengkm4ng.c»m
Scole: as noted : P't' 25373
Drawn= CPGiKEB QI RFF
P2.02
E
ai
sheets 3 o1 3
opyrko 04 Architecl�s. Ircar•pc ated
A0-,ghts reserved
t
g r Y
ab
n