06-240-026a PROJECT.... KYOJON BUFFET SANITARY SIZING FIXTURE TYPE NO F U /EACH TOTAL MIN TRAP SIZE URINAL 1 4.0 4.0 3" WATER CLOSET 5 4.0 20.0 3" LAVATORY 6 1.0 60 11/4" FLOOR DRAIN 16 3.0 48.0 3" HAND SINK 5 20 100 1 1/2" 3-COMP SINK 1 3.0 3.0 2" DISHWASHER 1 3.0 3.0 2" MOP SINK 1 2.5 2.5 3" FLOOR SINK 2 3.0 6.0 2" TOTAL 1 38 1 25.5 102.5 1- TOTAL SANITARY FIXTURE UNITS= ............ 102.5 MINIMUM SIZE MAIN SANITARY LINE all 1/8" SLOPE........... 4 ....... . HOT & COLD WATER SIZING FIXTURE TYPE NO. C.W.F.U./EA TOTA H.W F.U./EA. TOTAL URINAL 1 3.0 3.0 - - WATER CLOSET 5 5.0 25.0 - - LAVATORY 6 1.5 9.0 1.5 9.0 HAND SINK 5 15 75 15 is 3-COMP SINK 1 3.0 3.0 3.0 3.0 DISHWASHER 1 2.25 2.25 225 2.25 MOP SINK 1 2.25 2.25 2.25 2.25 ICE MACH. 1 1.5 1.5 - - HOSE BIBB 1 3.0 3.0 - - TOTAL 22 23.0 56.5 10.5 24.0 TOTAL C W F.U. _ ( 56.5 . 24:0 ) = 80.5 MINIMUM SIZE WATER SERVICE.....11T MINIMUM SIZE WATER METER.....1 ........ WATER CLOSET (REGULAR) ® WATER CLOSET (HANDICAP) (1) ® URINAL LAVATORY (REGULAR) LAVATORY (REGULAR) ® LAVATORY (HANDICAP) (1) SINK MOP SINK AMERICAN STANDARD "CADET" 16-1/2"H. MODEL #2377.100 COLOR WHITE. SEAT "LAUREL" MODEL #5311.012 COLOR WHITE, AMERICAN STANDARD "CADET" 16-1/2"H. MODEL #2377100 COLOR WHITE SEAT "LAUREL" MODEL #5311.012 COLOR WHITE. INSTALLED SO TOP OF SEAT 17"-19" FROM FINISHED FLOOR. AMERICAN STANDARD "TRIMBROOK" MODEL # 6561.017 COLOR WHITE FLUSH VALVE "SLOAN ROYAL" MODEL # 186-1. MT.17" TO TOP OF RIM FOR HANDICAPPED USE. AMERICAN STANDARD "AQUALYN" MODEL # 0476.028 COLOR WHITE FAUCET SET AMERICAN STANDARD "RELIANT" MODEL # 2385.500 AMERICAN STANDARD "DECLYN" MODEL # 0321.026 COLOR WHITE FAUCET SET AMERICAN STANDARD "RELIANT" MODEL # 2385.060 AMERICAN STANDARD "CADET" MOD # 0419.444sgg COLOR WHITE. FAUCET SET AMERICAN STANDARD "RELIANT" MODEL # 2385.500 AMERICAN STANDARD "PENLYN" MODEL 1110373.027 COLOR WHITE . FAUCET MODEL # 2385.060. AMERICAN STANDARD "FLORWELL" MODEL # 7741000 COLOR WHITE RIM GUARD MODEL # 7745.811. FAUCET MODEL # 8344.112 WATER HEATER EXISTING 1. MOUNTING HEIGHT PER ADA STANDARD. INSULATE WATER AND DRAIN LINE. 1 PROVIDE CUT SHEETS FOR REVIEW PRIOR TO PURCHASE. 3. PLUMBING FIXTURES TO COMPLY WITH TABLE 604.4 F.B.C. 4. ALL WALL HUNG PLUMBING FIXTURES SHALL COMPLY WITH F.B.C. 2S10.5.1.1, 2510.S.12 AND 2510.5.1.3 PLUMBING FIXTURES FLOOR DRAIN FIN FLOOR FLOOR DRAIN DETAIL N.T.S. NOTES: 1. INSULATION OF ALL GAS PIPING SHALL BE PER F B.0 (GAS PIPING STANDARD) 2, ALL GAS PIPING TO BE #40 GALVANIZED STEEL PIPE. 3. GAS PIPING TO COMPLY WITH ANSI B36.10 ASTM A 53 OR ASTM A 106. 4. PRESSURE TEST GAS PIPING FOR LEAKS PRIOR TO CONNECTING GAS SUPPLY, NOTES: - VERIFY LOCATION OF EQUIPMENT PRIOR TO INSTALLATION. - VERIFY ALL BTU's WITH MANUFACTURER'S SPECS PRIOR TO INSTALLATION. NOTE. GAS PIPING BASED ON A PRESSURE DROP OF .5 IN WC MAX DISTANCE =80' PLUMBING LEGEND - - - - - COLD WATER LINE - - 1102 - - 110s - - 110" HOT WATER LINE uo9 16oa• 140• HOT WATER LINE SANITARY LINE WASTE/ VENT LINE G GAS LINE ® 12" x 12" FLOOR SINK )E) FLOOR DRAIN ►N SHUT-OFF VALVE BIBB WITH S.O.V. H B +HOSE & VACUUM BREAKER A.A.V. AIR ADMITTANCE CHAMBER TOTAL GAS CONSUMPTION ITEM N0. DESCRIPTION BTUH 1. 15' HOT FOOD COUNTER 10,000 2. CHINESE COOKING WOK 60,000 3. CONVECTION OVEN 54,000 4. GRILLE 120,000 5. CHAR BROILER 80,000 6& FRYER 100,000 68. FRYER 100,000 7. FRYER 100,000 8. JAPANSESE HOT PLATE 24,000 TOTAL 648,000 CD O 3/4" O V 1„ 11/4 � V ^1 1/4"GAS LINE IN SLEEVE BELOW SLAB. OFILL SLEEVE WITH 1 1 1/4" G LIQUID FOAM. G 1/4" 1 114" I 1 c� 114"GAS LINE IN SLEEVE �\ �� V BELOW SLAB. FILL SLEEVE WITH LIQUID FOAM. V V O(� 1 if4" V O / 2 6 6A 6 1/4" / 66 O V 1/2" V v c+ 3/4" V �3/4- 3/4" / 3/4" 11/4" G 1 1/2 �GASG GAS SOLENOID .---VALVE. INTERLOCK W/ ANSUL SYSTEM. 1/2" GAS LINE TO GAS SUPPLY 1 1/2" GAS S.O.V. VERIFY LOCATION UP 1 AND CONNECTION POINT IN FEILD -REGULATOR FILL SLEEVE WITH / \ LIQUID FOAM GAS RISER N.T.S. 11/4" CW SUPPLY LINE BACKFLOW PREVENTER ASSEMBLY N.T.S. NOTES: 1. VERIFY LOCATIONS OF EXISTING WATER AND SANITARY SUPPLY CONNECTION POINTS WITH CITY OR LOCATE ON EXISTING SITE. 2. VERIFY EXISTING SIZES AND INVERTS OF EXISTING UTILITIES PRIOR TO INSTALLATION OF NEW WATER AND SANITARY LINES. 3. THE MINIMUM SLOPE FOR ALL SANITARY LINES SHALL BE 1/8" PER FOOT. PIPING TO BE PVC SCHEDULE #40 DWV. 4. ALL INTERIOR POTABLE WATER SERVICE PIPING TO BE COPPER TYPE K OR L. ANY SUBSTITUTIONS MUST BE APPROVED BY ENGINEER 5 ALL HOSE BIBBS TO HAVE SHUT OFF VALVES AND VACUUM BREAKERS. 6 MAIN WATER SERVICE TO BE SIZED PER PLANS. THREADED CLEANOUT PLUG GRADE 12"x12"x4" CONCRETE SLAB, MIN. 1Ox10 WIRE MESH FILL VOID WITH OILED SAND CLEANOUT FITTING WITH PVC PLUG. TWO-WAY CLEANOUT TEE OR LONG SWEEP CLEANOUT TO GRADE (CTG) DETAIL NTS• INTERIOR PARTITION WALL CONSTRUCTION PIPE SIZE 24" 3'WALL A- 4" 46" PLUMBING: 1. ALL WORKMANSHIP & MATERIALS SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE NATIONAL, STATE, LOCAL CODES, RULES & ORDINANCES. 2. CONTRACTOR SHALL VISIT THE JOB SITE & THOROUGHLY FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS. 3. ALL MATERIALS SHALL BE NEW. 4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST-CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE. 5. ALL EXCAVATION & BACK FILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE A PART OF THIS CONTRACT. 6. REQUIRED INSURANCE SHALL BE PROVIDED BY THIS CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY & PROPERTY DAMAGE FOR THE DURATION OF WORK. 7• CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS & TEST. SUBSTITUTIONS BY THE CONTRACTOR SHALL HAVE PRIOR APPROVAL. ANY CHANGES MADE WITHOUT APPROVAL WILL BE PAID BY THE CONTRACTOR TO RETURN TO THE ORIGINAL DESIGN B. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES, PIPING, EQUIPMENT, ETC. 9. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROCESS OF CONSTRUCTION. 10. VERIFY LOCATION, SIZE, TRAPS, INVERTS OF ALL EXISTING UTILITIES PRIOR TO BEGINNING CONSTRUCTION. ADVISE ENGINEER OF ANY DISCREPANCIES ANY COST RESULTING FROM DISCREPANCIES NOT REPORTED AT THIS TIME SHALL BE PAID BY THE CONTRACTOR 11. WATER PIPING TO BE TYPE "L" COPPER BELOW GRADE, TYPE "M" COPPER ABOVE GRADE. 12. SOIL, WASTE & VENT PIPING TO BE PVC. #40 DVW. WASTE & VENT PIPING ABOVE SLAB PVC., IF APPROVED BY LOCAL AUTHORITIES HAVING JURISDICTION. 13. ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS 14. N/A 15. WHERE DISSIMILAR METALS ARE TO BE JOINED, APPROVED INSULATING UNIONS SHALL BE USED. 16. INSULATE HOT WATER LINES WITH 1" THICK SNAP ON INSULATION FIRST 8 FEET FROM WATER HEATER. 17. CONDENSATE LINES TO BE COPPER/PVC DEPENDING ON PROJECT REQUIREMENTS. INSULATE WITH 1/2" THICK ARMAFLEX INSULATION. 18. CONTRACTOR SHALL GUARANTEE ALL MATERIALS & WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 19. NO PVC PIPING TO BE USED IN COMMON PLENUM AREAS. 20. SEE PLUMBING PLANS FOR ADDITIONAL REQUIREMENTS. SPECIFICATIONS WATER HEATER IS EXISTING UPGRADE OR REPLACE IF NECESSARY TO MEET CURRENT CODE REQUREMENTS. MIXING VALVE HEAT TRAPS T&P TO GROUO WITH 2" AIR GAP RELIEF VALVE 2"AIR GAP I I CHROME PLATED ACCESS --- COVER W/ CLEANOUT PLUG. CONCRETE SLAB WALL CLEANOUT DETAIL N.T.S. SANITARY OR WASTE PIPING HOT WATER SUPPLY COLD WATER ,�04• ,14q 1 SUPPLY WATTS BRVT �- PRESSURE RELIEF VALVE PRESSURE RELIEF DRAIN WITH 2" A-- - - 2"AIR GAP WATER HEATER N.T.S. EXISTING WATER TAP M EXISTING WATER METER �BACKFLOW S.O.V. H.B. W/ S.O.V. & VAC BKR WATER SERVICE CONNECTION DETAIL N.T.S. MC c FW W W d) > X # CC_ C i r >,\ 0 (10 lob 'M Sk N 0 (_0 (('') _ N _u ai 0 1. ELM. ap3 CM44 NT 02-24-M no, revision I date REVISION 02/24/06 Issued for permit PERMIT' SET H/30/05 < NOTE: ANY DESIGN CHANGES, TO THE SYSTEM COVERED BY THESE PLANS WITHOUT PRIOR APPROVAL OF THE ENGINEER WHO PREPARED THESE PLANS, WILL Sheet: 1 plumbing risers dtai is & SeCS P NULL AND VOID THESE PLANS AND THE REVISED INSTALLATION. IN ADDITION, ALL EXPENSES ° 1 ASSOCIATED WITH RETURNING THE SYSTEM TO ITS ORIGINAL DESIGN WILL BE THE RESPONSIBILITY OF THE COMPANY WHICH APPROVED THESE CHANGES ' 1 NIIFORMICA ►III ASSOCI ATE6. Consulting Engineers 3100 N.W. Boca Raton Blvd. Suite #117 Boca Raton, R 33431 IF 368-3611 FAX' (561) 368-4733 dwa to #00008818 F. Formica, P.E. �#19733 m*aengkm4ng.c»m Scole: as noted : P't' 25373 Drawn= CPGiKEB QI RFF P2.02 E ai sheets 3 o1 3 opyrko 04 Architecl�s. Ircar•pc ated A0-,ghts reserved t g r Y ab n