06-240-018PROJECT.... KYOJON. BUFFET
................................................................................
SANITARY SIZING
FIXTURE TYPE NO. F.0 /EACH TOTAL MIN. TRAP SIZE
URINAL
1
4.0
4.0
3"
WATER CLOSET
5
4.0
20.0
3"
LAVATORY
6
1.0
6.0
11/4"
FLOOR DRAIN
16
30
480
3"
HAND SINK
5
2.0
10.0
1 1/2"
3-COMP SINK
1
30
30
2"
DISHWASHER
1
3.0
3.0
2"
MOP SINK
1
2.5
2.5
3"
FLOOR SINK
2
3.0
6.0
2"
TOTAL
38
2S 5
102.5
-
TOTAL SANITARY FIXTURE UNITS= ............ 1025
MINIMUM SIZE MAIN SANITARY LINE @ 1/8" SLOPE...............4 ...........
HOT & COLD WATER SIZING
FIXTURE TYPE NO. C.W F U /EA. TOTAL H W.F U /EA. TOTAL
URINAL
1
3.0
3.0
-
-
WATER CLOSET
5
5.0
25.0
-
-
LAVATORY
6
1.5
9.0
1.5
9.0
HAND SINK
5
1.5
7.5
1.5
7.5
3-COMP SINK
1
30
30
30
30
DISHWASHER
1
2.25
2.25
2.25
2.25
MOP SINK
1
2.25
225
2.25
2.25
ICE MACH.
1
1.5
1.5
-
-
HOSE BIBB
1
3.0
3.0
-
-
TOTAL
22
23.0
56.5
10.5
24.0
TOTAL C.W.F.U.
MINIMUM SIZE WATER SERVICE.....�.��4
MINIMUM SIZE WATER METER.....)..........
WATER CLOSET (REGULAR)
® WATER CLOSET (HANDICAP) (1)
® URINAL
LAVATORY (REGULAR)
LAVATORY (REGULAR)
® LAVATORY IHANDICAPI 11)
SINK
MOP SINK
NOTES:
AMERICAN STANDARD "CADET" 16-1/2"H.
MODEL #2377.100 COLOR WHITE. SEAT
"LAUREL" MODEL #5311.012 COLOR WHITE.
AMERICAN STANDARD "CADET" 16-1/2"H.
MODEL #2377.100 COLOR WHITE. SEAT
"LAUREL" MODEL #5311012 COLOR WHITE
INSTALLED SO TOP OF SEAT 11"-19" FROM
FINISHED FLOOR.
AMERICAN STANDARD "TRIMBROOK"
MODEL # 6561017 COLOR WHITE
FLUSH VALVE"SLOAN ROYAL"
MODEL # 186-1. MT. 17" TO TOP OF
RIM FOR HANDICAPPED USE.
AMERICAN STANDARD "AQUALYN"
MODEL # 0476 028 COLOR WHITE
FAUCET SET AMERICAN
STANDARD "RELIANT" MODEL #
2385.500
AMERICAN STANDARD "DECLYN"
MODEL # 0321.026 COLOR WHITE
FAUCET SET AMERICAN
STANDARD "RELIANT" MODEL #
2385.060
AMERICAN STANDARD "CADET" MOD
# 0419 444sg COLOR WHITE. FAUCET
SET AMERICAN STANDARD "RELIANT
MODEL # 2385.500
AMERICAN STANDARD "PENLYN"
MODEL # 0373.027 COLOR WHITE .
FAUCET MODEL # 2385.060.
AMERICAN STANDARD "FLORWELL"
MODEL # 7741000 COLOR WHITE
RIM GUARD MODEL # 7745 811
FAUCET MODEL # 8344.112
1 MOUNTING HEIGHT PER ADA STANDARD INSULATE WATER AND DRAIN LINE
2. PROVIDE CUT SHEETS FOR REVIEW PRIOR 10 PURCHASE.
3 PLUMBING FIXTURES TO COMPLY WITH TABLE 604 4 F B C
4. ALL WALL HUNG PLUMBING FIXTURES SHALL COMPLY WITH F.B C. 2510.5.1.1. 2510.5.1.2 AND 2510.5.1.3
PLUMBING FIXTURES
INTERIOR PARTITION
WALL CONSTRUCTION
CHROME PLATED ACCESS
/ COVER W/ CLEANOUT PLUG.
PIPE SIZE
WALL SIZE
2"
4"
3"
4"
4"
6"
WALL CLEANOUT DETAIL
N.T.S.
NOTES-
1. INSULATION OF ALL GAS PIPING SHALL BE
PER F B.C. (GAS PIPING STANDARD)
2. ALL GAS PIPING TO BE #40 GALVANIZED
STEEL PIPE.
3 GAS PIPING TO COMPLY WITH ANSI B3610
ASTM A 53 OR ASTM A 106.
4. PRESSURE TEST GAS PIPING FOR LEAKS
PRIOR TO CONNECTING GAS SUPPLY.
NOTES:
- VERIFY LOCATION OF
EQUIPMENT PRIOR TO
INSTALLATION.
- VERIFY ALL BTU's WITH
MANUFACTURER'S SPECS
PRIOR TO INSTALLATION.
NOTE:
GAS PIPING BASED ON
A PRESSURE DROP OF S IN WC
MAX DISTANCE=80'
SANITARY OR
WASTE PIPING
TOTAL GAS CONSUMPTION
ITEM
NO.
DESCRIPTION
BTUH
1.
15' HOT FOOD COUNTER
10,000
2.
CHINESE COOKING WOK
60,000
3.
CONVECTION OVEN
54,000
4.
GRILLE
120,000
5.
CHAR BROILER
80,000
6A.
FRYER
100,000
68.
FRYER
100,000
7.
FRYER
100,000
8.
JAPANSESE HOT PLATE
24.000
TOTAL
648,000
FLOOR DRAIN
FIN FLOOR
• •. .
..
d
--I11-
III -I _IIIIIII;
III -
I
FLOOR DRAIN DETAIL
N.T.S.
THREADED CLEANOUT PLUG
GRADE
12"x12"x4" CONCRETE SLAB, MIN
1000 WIRE MESH
FILL VOID WITH OILED SAND
CLEANOUT FITTING WITH
PVC PLUG.
TWO-WAY CLEANOUT TEE
OR LONG SWEEP
CLEANOUT TO GRADE (CTG) DETAIL
N.T.S.
O
O
3/4" CD
V
11/4"
+1 1/4"GAS LINE IN SLEEVE
BELOW SLAB.
FILL SLEEVE WITH
O1 1/4" G LIQUID FOAM.
G
1 1/4" 11/4"
1► �
1/4"GAS LINE IN SLEEVE v \` 6
BELOW SLAB. ` /
FILL SLEEVE WITH
LIQUID FOAM
V
V
6
O
6 O
/ 2
6 6A V 1/4"
/ 51/4"
3/4"
3/4"
11/4" G
1 1/2 �GASC GAS SOLENOID
/VALVE. INTERLOCK
W/ ANSUL SYSTEM
1/2" GAS LINE
TO GAS SUPPLY
1 1/2" GAS S.O.V. VERIFY LOCATION
UP f AND CONNECTION
j POINT IN FEILD
REGULATOR
FILL SLEEVE WITH\ GAS RISER
LIQUID FOAM
N.T.S.
PLUMBING:
1. ALL WORKMANSHIP & MATERIALS SHALL BE IN STRICT ACCORDANCE WITH APPLICABLE NATIONAL,
STATE, LOCAL CODES, RULES & ORDINANCES.
2 CONTRACTOR SHALL VISIT THE JOB SITE & THOROUGHLY FAMILIARIZE HIMSELF WITH ALL
EXISTING CONDITIONS.
3. ALL MATERIALS SHALL BE NEW.
4. ALL WORK SHALL BE PERFORMED BY A LICENSED PLUMBING CONTRACTOR IN A FIRST-CLASS
WORKMANLIKE MANNER THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE
5. ALL EXCAVATION & BACK FILL AS REQUIRED FOR THIS PHASE OF CONSTRUCTION SHALL BE A
PART OF THIS CONTRACT.
6• REQUIRED INSURANCE SHALL BE PROVIDED BY THIS CONTRACTOR FOR PROTECTION AGAINST
PUBLIC LIABILITY & PROPERTY DAMAGE FOR THE DURATION OF WORK.
7. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, INSPECTIONS & TEST. SUBSTITUTIONS
BY THE CONTRACTOR SHALL HAVE PRIOR APPROVAL. ANY CHANGES MADE WITHOUT
APPROVAL WILL BE PAID BY THE CONTRACTOR TO RETURN TO THE ORIGINAL DESIGN.
8. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FOR THE EXACT LOCATION OF FIXTURES,
PIPING, EQUIPMENT, ETC.
9 ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
PROCESS OF CONSTRUCTION.
10. VERIFY LOCATION, SIZE, TRAPS, INVERTS OF ALL EXISTING UTILITIES PRIOR TO BEGINNING
CONSTRUCTION. ADVISE ENGINEER OF ANY DISCREPANCIES. ANY COST
RESULTING FROM DISCREPANCIES NOT REPORTED AT THIS TIME SHALL
BE PAID BY THE CONTRACTOR.
11. WATER PIPING TO BE TYPE "L" COPPER BELOW GRADE, TYPE "M" COPPER ABOVE GRADE.
12. SOIL, WASTE & VENT PIPING TO BE PVC. #40 DVW. WASTE & VENT PIPING ABOVE SLAB PVC.,
IF APPROVED BY LOCAL AUTHORITIES HAVING JURISDICTION.
13 ALL FIXTURES MUST BE PROVIDED WITH READILY ACCESSIBLE STOPS
14. N/A
15. WHERE DISSIMILAR METALS ARE TO BE JOINED, APPROVED INSULATING UNIONS SHALL
BE USED
16. INSULATE HOT WATER LINES WITH 1" THICK SNAP ON INSULATION FIRST 8 FEET FROM
WATER HEATER.
11. CONDENSATE LINES TO BE COPPER/PVC DEPENDING ON PROJECT REQUIREMENTS
INSULATE WITH 1/2" THICK ARMAFLEX INSULATION.
18. CONTRACTOR SHALL GUARANTEE ALL MATERIALS & WORKMANSHIP FREE FROM DEFECTS CONTRACTOR SHALL GUARANTEE ALL MATERIALS & WORKMANSHIP FREE FROM DEFECTS
FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. CORRECTION
OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE
REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE
BEEN DAMAGED THEREBY.
19. NO PVC PIPING TO BE USED IN COMMON PLENUM AREAS.
20 SEE PLUMBING PLANS FOR ADDITIONAL REQUIREMENTS
SPECIFICATIONS
PLUMBING LEGEND
- - - - -
COLD WATER LINE
- - 1102 - - 1109 - -
110" HOT WATER LINE
1409• 1409-
140° HOT WATER LINE
SANITARY LINE
WASTE/ VENT LINE
G
GAS LINE
®
12" x 12" FLOOR SINK
FLOOR DRAIN
►N
SHUT-OFF VALVE
BIBB WITH S.O.V.
H B +HOSE
& VACUUM BREAKER
A.A.V.
AIR ADMITTANCE CHAMBER
PERMIT SEI`• ll/30/05
NOTE -
ANY DESIGN CHANGES, TO THE SYSTEM COVERED
BY THESE PLANS WITHOUT PRIOR APPROVAL OF
THE ENGINEER WHO PREPARED THESE PLANS, WILL
NULL AND VOID THESE PLANS AND THE REVISED
INSTALLATION. IN ADDITION, ALL EXPENSES
ASSOCIATED WITH RETURNING THE SYSTEM TO ITS
ORIGINAL DESIGN WILL BE THE RESPONSIBILITY
OF THE COMPANY WHICH APPROVED THESE CHANGES.
)))FORMICA &
IIIIASSOCIATEFir,
Consulting Engineers
3100 N.W. Boca Raton Blvd.
Suite #117
Boca Raton, FI 33431
_1 561) 368-3611 FAX: (561) 368-4733
Cerdfa to #00008818
fR,obert F. Formi P.E.
. Lice 733
orrrtImwgineedng.com
•1� r.�+
J!
- I �'l d��i5•�•
�.•0 ••a�tik,
' � C
paUi
M
N c0
�2J/^)1
U
rn 01
O v CJ
rr
NM
r
I`I
O
�
U
-C J
mot' It
(O
Cq
ivy
U
0 O
o
N x
3
3
n v
o
x
L�
l� Ivl
JJ
3
Cn
U
:(D
'
Marcello Penso AR0016862
W
�J
Q�
m
•X
C
E
0c)
�0
0
CN
0 rq
+_1
c
m
+�
•-,
o
N
in
aJ
L
-
U
L
a
0
o
_ --
_
-,--.-
-
no. i
revision
date
Phase:
issued - tor- per, 1 f
Sheet:
plumb;ng risers-
details; &:; spp�-_
Scale: as noted
Prf: 25373
Drawn: CPG/KEB
Chk: RFF
2.0 '2'
sheet 3 of 3
Pyrlght Q M Archltectus, Incorporated
I rights reserved
4