08-668-002- SY
SYM. DESCRIPTION.
FcP FIRE ALARM CONTROL
PwR AUDIBLE POWER P
ANN REMOTE ANNUNCIATOR
FIRE ALARM TERMINAL,
B PHOTOELECTRIC DETECTOR W/ DB'
L LEGEND
DESCRIPTION
MODEL
EL
CP -35 If
PAD -2
EL
LED -3/4
NET
F.B.O.
& DB -11 SEAL
PE -11
8 R
D
0
PHOTOELECTRIC DETECTOR W/ DB `,r,
b;
CEILING THERMAL DE
MANUAL PULL STA ,
Rr RR -11 RELAY
PE -11
R
DT -11
FPL
MS -151
CAUSE THE FOLLOWING ACTIONS AND INDICATIONS:
ELEVATOR WARNING '
T
SSU620
N
TAMPER SWITCH t(BY :
FLOW SWITCH (BY pY
RS)
F.B.O.
#14
F.B.O.
FPL
2
CONDUCTOR
#14
AWG
FPL
E
11
2
CONDUCTOR
SYM.
THE
DESCRIPTION
A
SOUND THE AUDIBLE CIRCUITS WITH THE EVACUATION TONE AND
ACTIVATE
THE VISUAL SIGNALS OF THROUGHOUT THE FACILITY.
11
2
CONDUCTOR
#18
AWG
FPL
B
11
2
CONDUCTOR
#14
AWG
FPL
c
CAUSE THE FOLLOWING ACTIONS AND INDICATIONS:
1)
SOUND THE AUDIBLE CIRCUITS WITH THE EVACUATION TONE AND
ACTIVATE
11
2
CONDUCTOR
#14
AWG
FPL
2
CONDUCTOR
#14
AWG
FPL
E
11
2
CONDUCTOR
#18
AWG
FPL
M
11
2
CONDUCTOR
#18
AWG
FPL
vfA
ffd � Js
%wa)
ai
FTl
Yk ~�
W IpE LEGEND I
CONNECTIONS
FOR CONNECTION TO CONVENTIONAL DEVICES
FOR CONNECTION TO HORN CIRCUITS
FOR CONNECTION TO STROBE CIRCUITS
FOR UNSWITCHED 24VDC POWER
FOR SWITCHED 24VDC POWER
FOR MONITOR MODULES TO DIRECT SHORTING DEVICES
7
fog
All
i kv,
D I
its. � "� � •5
i
FIRE ALA` M NOTES — SYSTEM 3 SYSTEM
1. ALL WIRING t� ST CONFORM WITH NEC ARTICLE 760 AND LOCAL CODES.
ALL EQUIPMENT SHALL BE UL LISTED. ALL DEVICES SHALL BE
COMPATIBLE ;WITH THE CONTROL PANELS. SYSTEM IS POWER LIMITED
PER NEC 76a AND UL 864 REQUIREMENTS.
2. ALL. INITIATING AND INDICATING' CIRCUITS MUST BE SUPERVISED.
3. CIRCUIT POLARITY MUST BE OBSERVED.
4. WIRE RUNS A E SHOWN DIAGRAMMATICALLY. EXACT LOCATION OF ALL
EQUIPMENT T ) BE DETERMINED IN THE FIELD, BUT SHALL CONFORM
WITH THE BA 31C LAYOUT AS SHOWN ON DRAWINGS TO PREVENT
CIRCUIT OVE LOAD.
5. MINIMUM CON UIT SIZE WILL BE 3/4 ". CONDUIT SHALL BE NO MORE
THAN 40% LED PER NEC REQUIREMENTS.
6. POWER UP & `, OWER DOWN ON PANEL MUST BE DONE IN PROPER
SEQUENCE.
POWE DOWN
A — SCONNECT BATTERY.
B — RN OFF AC POWER PRIMARY & SECONDARY.
POWE UP
A — T RN ON AC POWER PRIMARY & SECONDARY.
B — T ECONNECT BATTERIES.
i
7. THE FIRE ALAFM CONTROL PANEL SHALL NOT BE USED TO POWER ANY
UNAUTHORIZED EXTERNAL DEVICE.
8. SIEMENS, CER�ERUS DIVISION IS RESPONSIBLE FOR FIRE ALARM EQUIPMENT
ONLY. ALL ..,HER EQUIPMENT111 SHOWN ARE FOR DIAGRAMMATICAL PURPOSES.
II
9. DAMPER MOTOI AND FAN SHUTDOWN CONNECTIONS (IF ANY) ARE TO BE
COORDINATE. IN FIELD WITH HVAC CONTRACTOR.
10. FIRE ALARM FOWER SUPPLIES AND ALL REMOTE SUPPLIES MUST BE CONNECTED
TO BUILDING,,,OR COLD —WATER GROUND VIA 1 GREEN #10 THHN OR EQUIV.
11. ALL SURGE /T ANSIENT SUPRESSORS MUST BE CONNECTED TO BUILDING
OR COLD — WATER GROUND.
12. FIRE ALARM INITIATING DEVICES SHALL NOT BE INSTALLED UNTIL CLEANUP
OF ALL TRA S ARE COMPLETE. FAILURE TO COMPLY WITH THIS NOTE
WILL VOID A°L WARRANTIES.
13. EVACUATION :IGNALS SHALL BE TEMPORAL IN ACCORDANCE WITH
NFPA 72 3 ` .2 (A) AND ANSI S3.41.
14. VERIFY ALL M UNTING HEIGHTS WITH AUTHORITY HAVING JURISDICTION
PRIOR TO IN TALLATION.
15. UNDERGROUN WIRING IS ACCEPTABLE PROVIDED N.E.C. REQUIREMENTS
FOR UNDERG OUND AND POWER LIMITED WIRING ARE MET.
BUILDIN('31DESCRIPTION Al
THIS IS AN EXISTING 5 STORIES OFFICE BUILDING, FULLY SPRINKCLERED.
SEQUENCE OF OPERATION
1. ACTIVATION OF ANY MANUAL INITIATION DEVICE WITHIN THE SYSTEM SHALL CAUSE
THE
FOLLOWING ACTIONS AND INDICATIONS:
1)
SOUND THE AUDIBLE CIRCUITS WITH THE EVACUATION TONE AND
ACTIVATE
THE VISUAL SIGNALS OF THROUGHOUT THE FACILITY.
2)
ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM
CONTROL
PANEL.
3)
ACTIVATE THE ALARM LIGHT FOR THE ZONE THAT CONNECTS TO
THE DEVICE
INITIATING THE EVENT.
2. ACTIVATION OF ANY AUTOMATIC FIRE DETECTION DEVICE WITHIN THE SYSTEM SHALL
CAUSE THE FOLLOWING ACTIONS AND INDICATIONS:
1)
SOUND THE AUDIBLE CIRCUITS WITH THE EVACUATION TONE AND
ACTIVATE
THE VISUAL SIGNALS OF THROUGHOUT THE FACILITY,
2)
ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM
CONTROL
PANEL.
3)
ACTIVATE THE ALARM LIGHT FOR THE ZONE THAT CONNECTS TO
THE DEVICE
INITIATING THE EVENT.
3. ACTIVATION OF ANY DUCT MOUNTED SMOKE DETECTORS SHALL, ACTIVATE A SUPERIASORY SIGNAL
AT THE FACP -AND ANNUNCIATORS, CAUSE THE SHUTDOWN OF THE ASSOCIATED AIR HANDLER
OR CLOSURE OF THE ASSOCIATED DAMPER. COORDINATE WITH HVAC CONTRACTOR
AND CONTRACT DOCUMENTS.
4. ACTIVATION OF ANY SM @kE DETECTORS IN A SINGLE ELEVATOR LOBBY, AN
ELEVATOR EQUIPMENT ROOM OR ELEVATOR HOIST WAY SHALL, BESIDES THE ACTIONS
DESCRIBED ABOVE, CAl9SE THE RECALL OR THAT BANK OF ELEVATORS TO THE
DESIGNATED LEVEL.
5. ACTIVATION OF THE SMOKE DETECTOR IN THE DESIGNATED LEVEL ELEVATOR LOBBY
SHALL, BESIDES THE ACTIONS DESCRIBED ABOVE, CAUSE THE RECALL OF THAT BANK
OF ELEVATORS TO THE ALTERNATE RECALL FLOOR.
I
6. ACTIVATION OF ANY SMIOKE DETECTOR IN AN ELEVATOR EQUIPMENT ROOM SHALL,
BESIDES THE ACTIONS DESCRIBED ABOVE, CAUSE THE ACTIVATION OF THE
ELEVATOR WARNING LIGHTS IN THE MAIN AND ALTERNATE RECALL LOBBIES.
7. ACTIVATION OF ANY FIXED TEMPERATURE HEAT DETECTOR IN AN ELEVATOR HOIST WAY
OR MACHINE ROOM SHALL CAUSE THE POWER TO THE ELEVATORS IN THAT BANK
TO SHUNT. DO NOT CONNECT SHUNT TRIP HEAT DETECTORS TO THE BUILDING
FIRE ALARM SYSTEM. COORDINATE SHUNT TRIP OPERATION WITH ELEVATOR
CONTRACTOR.
8. ACTIVATION OF ANY SUPERVISORY DEVICE WITHIN THE SYSTEM SHALL CAUSE THE
FOLLOWING ACTIONS AND INDICATIONS:
1 ACTIVATE THE SUPERVISORY LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL
PANEL AND ANNUNCIATORS, IF ANY.
2) ACTIVATE THE SUPERVISORY LIGHT FOR THE ZONE THAT CONNECTS TO THE DEVICE
INITIATING THE EVENT.
SCOPE OF WORK
5% R, w
INSTALLING 1 SMOKE DET. 2 HEAT DET. AND 2 RELAYS
TO THE EXISTING FIRE ALARM PANEL SYSTEM 3.
THE SMOKE IS GOING ON THE ELEVATOR TOP OF SHAFT. —
1 OF THE HEAT DET. IS GOING TO BE INSTALLED AT THE ELEVATOR MACHINE ROOM.
THE OTHER HEAT DET. IS GOING TO BE INSTALLET AT THE ELEVATOR TOP OF SHAFT_
THE RELAYS ARE GOING TO BE INSTALLED AT THE PANEL, ONE IS GOING TO BE USED
FOR THE SHUNT TRIP AND THE OTHER ONE WILL BE USED FOR ELEVATOR WARNING LIGHT.
DANIEL F. CUTMRREZ, RE
UC. /049088
--�
DF
9� CONSULTIAG ENCI
.D.ESIGN — x
r
C
'a N
N
A� 1U9 [7
W M O
O v �
C
X
a
m
W 0,K)
x�
W W O
r �
Pig
W §�X
S�
NW AI .1M
�o
oN
C3
co
0
0
Z
0
A
H fL
1
V M
vj
80