08-668-001SYMBOLLEGEND-,
SYM.
DESCRIPTION
MODEL
MANUFACTURER
El
FIRE ALARM CONTROL PANEL
CP -35
SIEMENS
PwR
AUDIBLE POWER PANEL
PAD -2
SIEMENS
ANN
REMOTE ANNUNCIATOR PANEL
LED -3/4
SIEMENS
�c
FIRE ALARM TERMINAL CABINET
F.B.O.
SIEMENS
B
PHOTOELECTRIC DETECTOR W/ DB -11 & DB -11 SEAL
PE -11
SIEMENS
e R
PHOTOELECTRIC DETECTOR W/ DB -11 & RR -11 RELAY
PE -11
SIEMENS
lD
CEILING THERMAL DETECTOR
DT -11
SIEMENS
LD
MANUAL PULL STATION
MS -151
SIEMENS
-I
ELEVATOR WARNING LIGHT
SSU620
SIEMENS
N
TAMPER SWITCH (BY OTHERS)
F.B.O.
F.B.O.
2
FLOW SWITCH (BY OTHERS)
F.B.O.
F.B.O.
FPL
POST INDICATOR VALVE
F.B.O.
F.B.O.
aP
BACK FLOW PREVENTER
F.B.O.
F.B.O.
FPL
HORN
U -MHST
SIEMENS
FLOW BELL
435 -6G1
EST
L
-C, A Lm
MIAMI MEDI
BUILD,ING
FIRE ALARM NOTES - SYSTEM 3 SYSTEM
1, ALL WIRING MUST CONFORM WITH NEC ARTICLE 760 AND LOCAL CODES.
ALL EQUIPMENT SHALL BE UL LISTED. ALL DEVICES SHALL BE
COMPATIBLE WITH THE CONTROL PANELS. SYSTEM IS POWER LIMITED
PER NEC 760 AND UL 864 ,REQUIREMENTS.
2. ALL INITIATING AND INDICATING CIRCUITS MUST BE SUPERVISED.
3. CIRCUIT POLARITY MUST BE OBSERVED.
4. WIRE RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION OF ALL
EQUIPMENT TO BE DETERMINED IN THE FIELD, BUT SHALL CONFORM
WITH THE BASIC LAYOUT ASIiSHOWN ON DRAWINGS TO PREVENT
CIRCUIT OVERLOAD.
5. MINIMUM CONDUIT SIZE WILL IBE 3/4 ". CONDUIT SHALL BE NO MORE
THAN 40% FILLED PER NEC �IREQUIREMENTS.
6. POWER UP &POWER DOWN ON PANEL MUST BE DONE IN PROPER
SEQUENCE.
POWER DOWN
A - DISCONNECT BATTERY.
B -TURN OFF AC POWER PRIMARY &SECONDARY.
POWER UP I
A -TURN ON AC POWER PRIMARY &SECONDARY.
B - RECONNECT BATTERIES.
I
7. THE FIRE ALARM CONTROL PANEL SHALL NOT BE USED TO POWER ANY
UNAUTHORIZED EXTERNAL DEVICE.
8. SIEMENS, 6BERUS DIVISION IS RESPONSIBLE FOR FIRE ALARM EQUIPMENT
ONLY. ALL OTHER EQUIPMENT SHOWN ARE FOR DIAGRAMMATICAL PURPOSES.
9. DAMPER MOTOR AND FAN SHUTDOWN CONNECTIONS (IF ANY) ARE TO BE
COORDINATED IN FIELD WITH'HVAC CONTRACTOR.
10. FIRE ALARM POWER SUPPLIES AND ALL REMOTE SUPPLIES MUST BE CONNECTED
TO BUILDING OR COLD -WATER GROUND VIA 1 GREEN #10 THNN OR EQUIV.
ii. ALL SURGE /TRANSIENT SUPRESSORS MUST BE CONNECTED TO BUILDING
OR COLD -WATER GROUND.
12. FIRE ALARM INITIATING DEVICES SHALL NOT BE INSTALLED UNTIL CLEANUP
OF ALL TRADES ARE COMPLETE. FAILURE TO COMPLY WITH THIS NOTE
WILL VOID ALL WARRANTIES.
13. EVACUATION SIGNALS SHALL BE TEMPORAL IN ACCORDANCE WITH
NFPA 72 3 -7.2 (A) AND ANSI 53.41.
14. VERIFY ALL MOUNTING HEIGHTS WITH AUTHORITY HAVING JURISDICTION
PRIOR TO INSTALLATION.
15. UNDERGROUND WIRING IS ACCEPTABLE PROVIDED N.E.C. REQUIREMENTS
FOR UNDERGROUND AND POWER LIMITED WIRING ARE MET.
BUILDING DESCRIPTION
THIS IS AN EXISTING 5 STORIES OFFICE BUILDING, FULLY SPRINKCLERED.
FIRST
PAGE
SEQUENCE OF OPERATION
1. ACTIVATION OF ANY MANUAL INITIATION DEVICE WITHIN THE SYSTEM SHALL CAUSE
THE FOLLOWING ACTIONS AND. INDICATIONS:
1) SOUND THE AUDIBLE CIRCUITS WITH THE EVACUATION TONE AND ACTIVATE
THE VISUAL SIGNALS OF THROUGHOUT THE FACILITY.
2) ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL
PANEL.
3) ACTIVATE THE ALARM LIGHT FOR THE ZONE THAT CONNECT$ TO THE DEVICE
INITIATING THE EVENT.
2. ACTIVATION OF ANY AUTOMATIC FIRE DETECTION DEVICE WITHIN THE SYSTEM SHALL
CAUSE THE FOLLOWING ACTIONS AND INDICATIONS:
1) SOUND THE AUDIBLE CIRCUITS WITH THE EVACUATION TONE AND ACTIVATE
THE VISUAL SIGNALS 'OF THROUGHOUT THE FACILITY.
2) ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL
PANEL. -
3) ACTIVATE THE ALARM LIGHT FOR THE ZONE THAT CONNECTS TO THE DEVICE
INITIATING THE EVENT.
3. ACTIVATION OF ANY DUCT MOUNTED SMOKE DETECTORS SHALL, ACTIVATE A SUPERVISORY SIGNAL
AT THE FACP AND ANNUNCIATORS, CAUSE THE SHUTDOWN OF THE ASSOCIATED AIR HANDLER
OR CLOSURE OF THE ASSOCIATED DAMPER. COORDINATE WITH HVAC CONTRACTOR
AND CONTRACT DOCUMENTS.
4. ACTIVATION OF ANY SMOKE DETECTORS IN A SINGLE ELEVATOR LOBBY, AN
ELEVATOR EQUIPMENT ROOM OR ELEVATOR HOIST WAY SHALL, BESIDES THE ACTIONS
DESCRIBED ABOVE, CAUSE THE'-RECALL OR THAT BANK OF ELEVATORS TO THE
DESIGNATED LEVEL.
5. ACTIVATION OF THE SMOKE DETECTOR IN THE DESIGNATED LEVEL ELEVATOR LOBBY
SHALL, BESIDES THE ACTIONS DESCRIBED ABOVE, CAUSE THE RECALL OF THAT BANK
OF ELEVATORS Td THE ALTERNATE RECALL FLOOR.
6. ACTIVATION OF ANY SMOKE DETECTOR IN AN ELEVATOR EQUIPMENT ROOM SHALL,
BESIDES THE ACTIONS DESCRIBED ABOVE, CAUSE THE ACTIVATION OF THE
ELEVATOR WARNING LIGHTS IN THE MAIN AND ALTERNATE RECALL LOBBIES.
7. ACTIVATION OF ANY FIXED TEMPERATURE HEAT DETECTOR IN AN ELEVATOR HOIST WAY
OR MACHINE ROOM SHALL CAUSE THE POWER TO THE ELEVATORS IN THAT BANK A
TO SHUNT. DO NOT CONNECT SHUNT TRIP HEAT DETECTORS TO THE BUILDING 4laNkT_lw -c k
FIRE ALARM SYSTEM. COORDINATE SHUNT TRIP OPERATION WITH ELEVATOR M
CONTRACTOR. c, NQvcpw'fd
m,
8. ACTIVATION OF ANY SUPERVISORY DEVICE WITHIN THE SYSTEM SHALL CAUSE THE
FOLLOWING ACTIONS AND INDICATIONS:
1) ACTIVATE THE SUPERVISORY LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL
PANEL AND ANNUNCIATORS, IF ANY.
2) ACTIVATE THE SUPERVISORY LIGHT FOR THE ZONE THAT CONNECTS TO THE DEVICE
INITIATING THE EVENT.
0 9. FLOW BELL OPERATION:
A) FLOW BELL SHALL SOUND UPON THE ACTIVATION OF THE FLOW SWITCH ONLY.
B) FLOW BELL SHALL SOUND THE ENTIRE TIME OF WATER FLOW. tNSTAUEDN';GC 6_E2D?►NCEWMi
C) FLOW BELL SHALL BE INCAPABLE -OF BEING SILENCED FROM FCP. �/_.Ar�t; p7o; ioi- ay1,�
Z irk ?,r Iif .4•i`'�, �4r� .6,,,`«AFL �I:� A D
a
MfA�t4r -•rar: ..�S``•'f �gtt °. f +r t'% t ; f a::uiyF
3T
SCOPE OF WORKT�:
INSTALLING 1 SMOKE DET. 2 HEAT DET. AND 2 RELAYS AND 1 FLOW BELL.
TO THE EXISTING FIRE ALARM PANEL SYSTEM 3.
THE SMOKE IS GOING ON THE ELEVATOR TOP OF SHAFT.
1 OF THE HEAT DET. IS GOING TO BE INSTALLED AT THE ELEVATOR MACHINE ROOM.
THE OTHER HEAT DET. IS GOING TO BE INSTALLET AT THE ELEVATOR TOP OF SHAFT.
THE RELAYS ARE GOING TO BE INSTALLED AT THE PANEL, ONE IS GOING TO BE USED
FOR THE SHUNT TRIP AND THE OTHER ONE WILL BE USED FOR ELEVATOR WARNING LIGHT:
DAMEL F. GUTIERREZ, PX 9360 CORAL WAY SUM
MC. 1049086 wA a FL 33145
DFG PH.•(905)481 -317'8
CONSULTING ENGINEERS INC.
�L�SZGN — INSPECTIONS
c
VI M
O �1
M
O N
O Ln
♦� C X
AV L 4
W d
C
.M_
W
u
M
W
LL,
o
�i iz o
��'
1
WCL
CJ
Z E0
NW www
ab ��
Z o
0
N
as
Ea
8
� U
HLLj
CL
0
0
LL
Ld M
H
A
g� u
w
z
z
O w
w
ll
SHEET NO.
U
of 4
WIRE LEGEND
SYM.
DESCRIPTION
CONNECTIONS -
A
2
CONDUCTOR
#18
AWG
FPL
FOR CONNECTION TO CONVENTIONAL DEVICES
B
2
CONDUCTOR
#14
AWG
FPL
FOR CONNECTION TO HORN, BELL CIRCUITS
c
11
2
CONDUCTOR
#14
AWG
FPL
FOR CONNECTION TO STROBE CIRCUITS
B
2
CONDUCTOR
#14
AWG
FPL
FOR UNSWITCHED 24VDC POWER
2
CONDUCTOR
#18
AWG
FPL
FOR SWITCHED 24VDC POWER
B
2
CONDUCTOR
#18
AWG
FPL
FOR MONITOR MODULES TO DIRECT SHORTING DEVICES
-C, A Lm
MIAMI MEDI
BUILD,ING
FIRE ALARM NOTES - SYSTEM 3 SYSTEM
1, ALL WIRING MUST CONFORM WITH NEC ARTICLE 760 AND LOCAL CODES.
ALL EQUIPMENT SHALL BE UL LISTED. ALL DEVICES SHALL BE
COMPATIBLE WITH THE CONTROL PANELS. SYSTEM IS POWER LIMITED
PER NEC 760 AND UL 864 ,REQUIREMENTS.
2. ALL INITIATING AND INDICATING CIRCUITS MUST BE SUPERVISED.
3. CIRCUIT POLARITY MUST BE OBSERVED.
4. WIRE RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION OF ALL
EQUIPMENT TO BE DETERMINED IN THE FIELD, BUT SHALL CONFORM
WITH THE BASIC LAYOUT ASIiSHOWN ON DRAWINGS TO PREVENT
CIRCUIT OVERLOAD.
5. MINIMUM CONDUIT SIZE WILL IBE 3/4 ". CONDUIT SHALL BE NO MORE
THAN 40% FILLED PER NEC �IREQUIREMENTS.
6. POWER UP &POWER DOWN ON PANEL MUST BE DONE IN PROPER
SEQUENCE.
POWER DOWN
A - DISCONNECT BATTERY.
B -TURN OFF AC POWER PRIMARY &SECONDARY.
POWER UP I
A -TURN ON AC POWER PRIMARY &SECONDARY.
B - RECONNECT BATTERIES.
I
7. THE FIRE ALARM CONTROL PANEL SHALL NOT BE USED TO POWER ANY
UNAUTHORIZED EXTERNAL DEVICE.
8. SIEMENS, 6BERUS DIVISION IS RESPONSIBLE FOR FIRE ALARM EQUIPMENT
ONLY. ALL OTHER EQUIPMENT SHOWN ARE FOR DIAGRAMMATICAL PURPOSES.
9. DAMPER MOTOR AND FAN SHUTDOWN CONNECTIONS (IF ANY) ARE TO BE
COORDINATED IN FIELD WITH'HVAC CONTRACTOR.
10. FIRE ALARM POWER SUPPLIES AND ALL REMOTE SUPPLIES MUST BE CONNECTED
TO BUILDING OR COLD -WATER GROUND VIA 1 GREEN #10 THNN OR EQUIV.
ii. ALL SURGE /TRANSIENT SUPRESSORS MUST BE CONNECTED TO BUILDING
OR COLD -WATER GROUND.
12. FIRE ALARM INITIATING DEVICES SHALL NOT BE INSTALLED UNTIL CLEANUP
OF ALL TRADES ARE COMPLETE. FAILURE TO COMPLY WITH THIS NOTE
WILL VOID ALL WARRANTIES.
13. EVACUATION SIGNALS SHALL BE TEMPORAL IN ACCORDANCE WITH
NFPA 72 3 -7.2 (A) AND ANSI 53.41.
14. VERIFY ALL MOUNTING HEIGHTS WITH AUTHORITY HAVING JURISDICTION
PRIOR TO INSTALLATION.
15. UNDERGROUND WIRING IS ACCEPTABLE PROVIDED N.E.C. REQUIREMENTS
FOR UNDERGROUND AND POWER LIMITED WIRING ARE MET.
BUILDING DESCRIPTION
THIS IS AN EXISTING 5 STORIES OFFICE BUILDING, FULLY SPRINKCLERED.
FIRST
PAGE
SEQUENCE OF OPERATION
1. ACTIVATION OF ANY MANUAL INITIATION DEVICE WITHIN THE SYSTEM SHALL CAUSE
THE FOLLOWING ACTIONS AND. INDICATIONS:
1) SOUND THE AUDIBLE CIRCUITS WITH THE EVACUATION TONE AND ACTIVATE
THE VISUAL SIGNALS OF THROUGHOUT THE FACILITY.
2) ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL
PANEL.
3) ACTIVATE THE ALARM LIGHT FOR THE ZONE THAT CONNECT$ TO THE DEVICE
INITIATING THE EVENT.
2. ACTIVATION OF ANY AUTOMATIC FIRE DETECTION DEVICE WITHIN THE SYSTEM SHALL
CAUSE THE FOLLOWING ACTIONS AND INDICATIONS:
1) SOUND THE AUDIBLE CIRCUITS WITH THE EVACUATION TONE AND ACTIVATE
THE VISUAL SIGNALS 'OF THROUGHOUT THE FACILITY.
2) ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL
PANEL. -
3) ACTIVATE THE ALARM LIGHT FOR THE ZONE THAT CONNECTS TO THE DEVICE
INITIATING THE EVENT.
3. ACTIVATION OF ANY DUCT MOUNTED SMOKE DETECTORS SHALL, ACTIVATE A SUPERVISORY SIGNAL
AT THE FACP AND ANNUNCIATORS, CAUSE THE SHUTDOWN OF THE ASSOCIATED AIR HANDLER
OR CLOSURE OF THE ASSOCIATED DAMPER. COORDINATE WITH HVAC CONTRACTOR
AND CONTRACT DOCUMENTS.
4. ACTIVATION OF ANY SMOKE DETECTORS IN A SINGLE ELEVATOR LOBBY, AN
ELEVATOR EQUIPMENT ROOM OR ELEVATOR HOIST WAY SHALL, BESIDES THE ACTIONS
DESCRIBED ABOVE, CAUSE THE'-RECALL OR THAT BANK OF ELEVATORS TO THE
DESIGNATED LEVEL.
5. ACTIVATION OF THE SMOKE DETECTOR IN THE DESIGNATED LEVEL ELEVATOR LOBBY
SHALL, BESIDES THE ACTIONS DESCRIBED ABOVE, CAUSE THE RECALL OF THAT BANK
OF ELEVATORS Td THE ALTERNATE RECALL FLOOR.
6. ACTIVATION OF ANY SMOKE DETECTOR IN AN ELEVATOR EQUIPMENT ROOM SHALL,
BESIDES THE ACTIONS DESCRIBED ABOVE, CAUSE THE ACTIVATION OF THE
ELEVATOR WARNING LIGHTS IN THE MAIN AND ALTERNATE RECALL LOBBIES.
7. ACTIVATION OF ANY FIXED TEMPERATURE HEAT DETECTOR IN AN ELEVATOR HOIST WAY
OR MACHINE ROOM SHALL CAUSE THE POWER TO THE ELEVATORS IN THAT BANK A
TO SHUNT. DO NOT CONNECT SHUNT TRIP HEAT DETECTORS TO THE BUILDING 4laNkT_lw -c k
FIRE ALARM SYSTEM. COORDINATE SHUNT TRIP OPERATION WITH ELEVATOR M
CONTRACTOR. c, NQvcpw'fd
m,
8. ACTIVATION OF ANY SUPERVISORY DEVICE WITHIN THE SYSTEM SHALL CAUSE THE
FOLLOWING ACTIONS AND INDICATIONS:
1) ACTIVATE THE SUPERVISORY LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL
PANEL AND ANNUNCIATORS, IF ANY.
2) ACTIVATE THE SUPERVISORY LIGHT FOR THE ZONE THAT CONNECTS TO THE DEVICE
INITIATING THE EVENT.
0 9. FLOW BELL OPERATION:
A) FLOW BELL SHALL SOUND UPON THE ACTIVATION OF THE FLOW SWITCH ONLY.
B) FLOW BELL SHALL SOUND THE ENTIRE TIME OF WATER FLOW. tNSTAUEDN';GC 6_E2D?►NCEWMi
C) FLOW BELL SHALL BE INCAPABLE -OF BEING SILENCED FROM FCP. �/_.Ar�t; p7o; ioi- ay1,�
Z irk ?,r Iif .4•i`'�, �4r� .6,,,`«AFL �I:� A D
a
MfA�t4r -•rar: ..�S``•'f �gtt °. f +r t'% t ; f a::uiyF
3T
SCOPE OF WORKT�:
INSTALLING 1 SMOKE DET. 2 HEAT DET. AND 2 RELAYS AND 1 FLOW BELL.
TO THE EXISTING FIRE ALARM PANEL SYSTEM 3.
THE SMOKE IS GOING ON THE ELEVATOR TOP OF SHAFT.
1 OF THE HEAT DET. IS GOING TO BE INSTALLED AT THE ELEVATOR MACHINE ROOM.
THE OTHER HEAT DET. IS GOING TO BE INSTALLET AT THE ELEVATOR TOP OF SHAFT.
THE RELAYS ARE GOING TO BE INSTALLED AT THE PANEL, ONE IS GOING TO BE USED
FOR THE SHUNT TRIP AND THE OTHER ONE WILL BE USED FOR ELEVATOR WARNING LIGHT:
DAMEL F. GUTIERREZ, PX 9360 CORAL WAY SUM
MC. 1049086 wA a FL 33145
DFG PH.•(905)481 -317'8
CONSULTING ENGINEERS INC.
�L�SZGN — INSPECTIONS
c
VI M
O �1
M
O N
O Ln
♦� C X
AV L 4
W d
C
.M_
W
u
M
W
LL,
o
�i iz o
��'
1
WCL
CJ
Z E0
NW www
ab ��
Z o
0
N
as
Ea
8
� U
HLLj
CL
0
0
LL
Ld M
H
A
g� u
w
z
z
O w
w
ll
SHEET NO.
U
of 4