08-623-013ELECTRICAL GENERAL NOTES 1. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE DRAWINGS FOR EXACT LOCATION OF EQUIPMENT. THESE DRAWINGS ARE NOT INTENDED TO SHOW EVERY MINOR DETAIL HOWEVER, THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS REQUIRED FOR A COMPLETE AND ACCEPTABLE WORKING INSTALLATION PER CODE. 2. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC AND SHALL COMPLY WITH ALL LOCAL RULES AND ORDINANCES. 3. ALL MATERIAL SHALL BE NEW AND SHALL BEAR UL LABEL WHERE APPLICABLE. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT FOR A COMPLETE INSTALLATION. ALL MOUNTING HARDWARE AND WIRING HARDWARE SHALL BE FURNISHED BY THE CONTRACTOR. 4. CIRCUITS SHOWN ON THESE PLANS ARE SYMBOLICALLY SHOWN TO DETERMINE LOAD DATA AND EQUIPMENT SIZES. THE CONTRACTOR SHALL PHYSICALLY PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. THE LOADS SHALL BE BALANCED THROUGHOUT. THE CONTRACTOR SHALL ENSURE THAT NEUTRAL WIRES AND EQUIPMENT GROUND WIRES ARE INSTALLED WHERE EVER APPLICABLE. 5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH THE POWER UTILITY TO OBTAIN TEMPORARY POWER DURING CONSTRUCTION. THE CONTRACTOR SHALL IMMEDIATELY CONTACT THE POWER UTILITY TO SCHEDULE INSTALLATION OF TEMPORARY POWER SO THAT CONSTRUCTION DELAYS ARE AVOIDED. 6. THE CONTRACTOR SHALL COORDINATE WITH THE POWER UTILITY TO OBTAIN PERMANENT POWER IN ACCORDANCE WITH THESE DRAWINGS. THE CONTRACTOR SHALL IMMEDIATELY CONTACT THE POWER UTILITY To SCHEDULE THE INSTALLATION OF PERMANENT POWER SO THAT DELAYS ARE AVOIDED. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THE POWER UTILITY EARLY ON TO IDENTIFY ANY ISSUES AFFECTING PERMANENT POWER SERVICE AND TO WORK TOWARDS RESOLVING ANY ISSUES REGARDING PERMANENT SERVICE. 7. THE CONTRACTOR SHALL COORDINATE WITH THE TELEPHONE COMPANY TO OBTAIN TELEPHONE SERVICE. THE CONTRACTOR SHALL IMMEDIATELY CONTACT THE TELEPHONE COMPANY TO SCHEDULE INSTALLATION OF TELEPHONE SERVICE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THE TELEPHONE COMPANY EARLY ON TO IDENTIFY ANY ISSUES AFFECTING TELEPHONE SERVICE AND TO WORK TOWARDS RESOLVING ANY ISSUES DELAYING INSTALLATION. B. IF APPLICABLE, THE CONTRACTOR SHALL COORDINATE WITH THE CABLE TV COMPANY IN THE SAME MANNER AS DESCRIBED IN PARAGRAPHS 6 AND 7 FOR POWER AND TELEPHONE UTILITIES. 9. IF ANY OR ALL OF THE UTILITIES (ELECTRICAL. TELEPHONE, CATV) ARE EXISTING, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO BECOME FAMILIAR WITH THE EXISTING SYSTEMS PRIOR TO BID. THE CONTRACTOR SHALL TRACE DOWN ALL CIRCUITS AND WIRING AND SHALL VERIFY THAT CAPACITY IS AVAILABLE FOR THE SCOPE OF THE PROJECT. THE CONTRACTOR SHALL FIELD INSPECT ALL EXISTING EQUIPMENT AND SHALL ENSURE THAT ALL RATINGS, FUSES, ENCLOSURES, ETC. ARE PROPER FOR THE SCOPE OF THE PROJECT. THE CONTRACTOR SHALL INSPECT ANY EQUIPMENT. WIRING ETC. THAT IS REUSED AND SHALL GUARANTEE THE PERFORMANCE OF SUCH EQUIPMENT FOR ONE YEAR. THE CONTRACTOR SHALL REPLACE ANY EQUIPMENT THAT IS DAMAGED OR IN POOR CONDITION. A LIST OF EQUIPMENT IDENTIFIED FOR REPLACEMENT SHALL BE PROVIDED TO THE OWNER (OR THE OWNER'S REPRESENTATIVE) AND THE ENGINEER PRIOR TO REPLACEMENT. 10. THE CONTRACTOR SHALL THOROUGHLY REVIEW THESE DRAWINGS AND SHALL VISIT AND BECOME FAMILIAR WITH THE JOB SITE AND ALL EXISTING CONDITIONS PRIOR TO BID. ANY QUESTIONS, COMMENTS, DISCREPANCIES OR PERCEIVED AMBIGUITIES SHALL BE DISCUSSED WITH THE ENGINEER PRIOR TO BID. 11. ELECTRICAL DESIGN IS BASED UPON THE BEST AVAILABLE INFORMATION. THE CONTRACTOR SHALL REVIEW NAMEPLATE DATA AND MANUFACTURER SUPPLIED LITERATURE FOR ALL PIECES OF EQUIPMENT PRIOR TO ROUGH ELECTRICAL WIRING. THE CONTRACTOR SHALL CHECK ALL EQUIPMENT FOR PROPER VOLTAGE, PHASE AND AMP RATING PRIOR TO INSTALLATION. THE CONTRACTOR SHALL CONTACT ENGINEER PRIOR TOO ANY FIELD ADJUSTMENTS. 12. ALL CONDUCTORS SHALL BE COPPER WITH THWN INSULATION. 13. ALL PANELS SHALL BE CLEARLY LABELED ON THE OUTSIDE FOR QUICK AND EASY IDENTIFICATION. ALL CIRCUITS IN ALL PANELS SHALL BE CLEARLY IDENTIFIED AND SHALL APPEAR WITH COMPLETE INFORMATION (DESCRIPTION OF CIRCUIT, BREAKER SIZE, NUMBER OF POLES AND BREAKER POSITION NUMBERS) ON THE PANEL DIRECTORIES. IN ADDITION, THE VOLTAGE, PHASE AND AMP RATING OF THE PANEL SHALL CLEARLY BE IDENTIFIED ON THE INSIDE DOOR. THE ABOVE APPLIES FOR ANY AND ALL EXISTING TO REMAIN PANEL BOARDS AND CIRCUITS. 14. PLANS SHOWING AS -BUILT CHANGES SHALL BE DELIVERED TO THE OWNERS REPRESENTATIVE UPON COMPLETION OF WORK. 15. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE THIS INSTALLATION IN COMPLIANCE WITH ALL FIRE PREVENTION CODES SUPERCEDING ALL DRAWINGS, SPECIFICATIONS AND NOTES. THE CONTRACTOR SHALL COMMUNICATE AND COORDINATE WITH THE FIRE MARSHALL AND SHALL PROVIDE ALL NECESSARY INFORMATION NEEDED TO SATISFY THAT LIFE SAFETY SYSTEMS ARE TO LOCAL CODE ACCEPTANCE. 16. ALL SERVICE ENTRANCE EQUIPMENT IS TO BE RATED AT 100,000 AIC UNLESS OTHERWISE NOTED. TO PROVIDE SERVICE ENTRANCE EQUIPMENT WITH LOWER RATINGS THE CONTRACTOR SHALL PROVIDE IN WRITING INFORMATION FROM THE POWER UTILITY VERIFYING THAT CALCULATED FAULT CURRENTS ARE AT AN ACCEPTABLE LEVEL TO ACCOMMODATE THE LOWER RATED EQUIPMENT. IF SERVICE ENTRANCE EQUIPMENT IS EXISTING, THE CONTRACTOR SHALL VERIFY THAT AC RATINGS OF EXISTING EQUIPMENT ARE PROPER. THE CONTRACTOR SHALL COORDINATE WITH THE POWER UTILITY AND THE ENGINEER PRIOR TO BID. 17. ALL OUTSIDE EQUIPMENT, OUTLETS, LIGHTING FIXTURES, ENCLOSURES, ETC. SHALL BE WEATHERPROOF. 18. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED CONNECTIONS FOR ALL OTHER TRADES. 19. THE CONTRACTOR SHALL OBTAIN ALL PERMITS FOR WORK UNDER THIS CONTRACT. 20. THE NUMBER, EXACT LOCATION AND MOUNTING HEIGHTS OF ALL OUTLETS, LIGHTS AND ELECTRICAL FIXTURES SHALL BE DETERMINED BY THE OWNER AND ARCHITECT. THE CONTRACTOR SHALL VERIFY ALL NUMBERS AND LOCATIONS WITH ARCHITECT AND OWNER PRIOR TO BID AND TO INSTALLATION. 21. THE CONTRACTOR SHALL PROVIDE ROUTING FOR ALL FLOOR MOUNTED OUTLETS AND OTHER LOADS AND CONNECTIONS NOT READILY ACCESSIBLE VIA WALL OR CEILING. THE CONTRACTOR SHALL COORDINATE WITH ARCHITECT AND OWNER TO DETERMINE THE METHOD TO SERVE SUCH AREAS (I.E. TRENCHING, CORE AND BORING, POWER POLE. ETC.) PRIOR TO BID. 22. ALL RACEWAYS AND PIPES PLACED IN OR THROUGH ANY CONCRETE SLAB SHALL BE SPACED A MINIMUM OF THREE DIAMETERS OF THE LARGEST CONDUIT OR PIPE OF ANY OTHER SERVICE. 23. ALL RACEWAYS UNDERGROUND AND /OR LARGER THAN 2 INCHES IN DIAMETER SHALL BE GALVANIZED RIGID STEEL PVC SCH 40 WILL BE ACCEPTABLE IF APPROVED BY LOCAL REGULATIONS CONTRACTOR TO VERIFY. ALL OTHER RACEWAYS 2" AND SMALLER IN DIAMETER MAY BE EMT. 24. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS AND CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS. 25. DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED, HEAVY DUTY, QUICK MAKE, QUICK BREAK, IN NEMA 1 OR NEMA 3R ENCLOSURES AS REQUIRED BY EXPOSURE. 26. THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED PER NEC REQUIREMENTS AND STATE AND LOCAL CODE REQUIREMENTS. 27. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY OPERATIVE. ACCEPTANCE BY ENGINEER /ARCHITECT MUST BE A CONDITION OF THE CONTRACT. 28. IT IS NOT THE INTENTION OF THESE DRAWINGS TO ESTABLISH LIGHTING LEVELS OF ANY KIND. THE NUMBER, STYLE AND LOCATION OF LIGHTING FIXTURES ARE DETERMINED BY THE ARCHITECT AND /OR THE OWNER. THE LIGHTING FIXTURE SCHEDULE IF APPEARING ON THESE DRAWINGS IS FOR INFORMATIONAL PURPOSES AND HAS BEEN DEVELOPED BY THE ARCHITECT AND /OR OWNER. FOR DETAILED QUESTIONS REGARDING LIGHTING FIXTURES CONTACT THE ARCHITECT OR OWNER. 29. EXISTING LIGHTING FIXTURES WHEN REUSED ARE TO BE RECIRCUITED AND RECONNECTED. THE ARCHITECT AND /OR OWNER SHALL BE INFORMED OF AND SHALL APPROVE THE REUSE OF ALL REUSED LIGHT FIXTURES. ALL REUSED LIGHTING FIXTURES SHALL BE RELAMPED, CLEANED AND REPAIRED IF NECESSARY. ANY EXISTING LIGHTING FIXTURE BEYOND REPAIR SHALL BE REPLACED. ALL LIGHTING FIXTURES SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR. 30. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT ALL ELECTRICAL SERVICES TO MECHANICAL EQUIPMENT IS ACCOUNTED FOR PRIOR TO BID. IN ADDITION, ALL MECHANICAL EQUIPMENT SUBSTITUTIONS ARE TO BE ACCOUNTED FOR PRIOR TO BID AND SHALL BE COORDINATED ELECTRICALLY. 31. R IS THE RESPONSIBILITY OF THE CONTRACTOR TO FORWARD ANY SHOP DRAWINGS TO THE ARCHITECT /OWNER. SHOP DRAWINGS ARE NOT SOLICITED BY THE ENGINEER. 32. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT FIRE STOPPING MEASURES ARE PROVIDED PER LOCAL BUILDING DEPT. REQUIREMENTS. THE FIRE STOPPING MATERIAL AND ITS INSTALLATION SHALL BE UL APPROVED. ALL FIRE STOPPING MATERIAL SHALL BE NON WATER SOLUBLE. 33. ALL CASH REGISTER AND COMPUTER RECEPTACLES ARE TO BE PROVIDED WITH DEDICATED CIRCUITS AND SEPARATE. ISOLATED GROUNDS. CONTRACTOR SHALL COORDINATE WITH ARCHITECT AND OWNER PRIOR TO BID TO IDENTIFY ALL RECEPTACLES REQUIRING ISOLATED GROUND CONNECTIONS. EXISTING ELECTRICAL ROOM r , 277/480 VOLTS r- I I ELECTRICAL METER I I I 4 - #8 THWN CU, IN 1" ;0 CONDUIT i0 ELECTRICAL LEGEND SYMBDL DESCRIPTION SYMBOL DESCRIPTION POL TRIP TO A E SNITCH, SINGLE POLE, ® SMOKE DETECTOR- SINGLE STATION 13 TOGGLE SWITCH, THREE WAY, 0 ELECTRICAL JUNCTION BOX 14 TOGGLE SWITCH, FOUR WAY, 20 A 720 TELEVISION OUTLET D DLItm ma RATED FOR CKT LOAD N TELEPHONE OUTLET -9 SINGLE RECEPTACLE, 20A, 1POV COMB. DATA OUTLET- TELEPHONE OUTLET DUPLEX RECEPTACLE, 20A, 120V WALL MTA AT 18' AFF. ❑.I2 30 20 DISC. SWITCH - POLE 720 DUPLEX RECEPTACLE, 20A, 120V WALL MTA AT 48' AFF. 3 DISC. SWITCH- NEMA 31? 1 20 QUAIIRAPLD( RECEPTACLE, 20A, 1POV #12 -1/2" POWER BRANCH CKT HOME RUN HATCH MARKS DENOTE I OF WIRE 1- DENOTE GROUND WIRE DUPLEX RECEPTACLE, 20A, OV W GROUND FAULT CIRCUIT INTERRUPT =QWP DUPLEX RE01ACLE, 20k 120V W/ WEATHERPROOF, 20 A 4P FAN MOTOR O FLOOR MM DUPLEX RECEPT, 120% 20A A.F.F. ABOVE FINISHED FLOOR ® SPECIAL PURPOSE RECEPTACLE GFI GROUND FAULT INIERRUPTOR FO WALL MM LIGHT FIXTURE WP WATER PROOF RECEPTACLES SURFACE MOUNTED LIGHT FIXTURE C t2TrIDUIT O ROM3SED MOUNTED LIGHT FIXTURE E.C. EMPTY COMIT Q VAPOR PROOF RECESSED U09 Q DOOR BELL BUTTON - - UNDER CARNET UGHT /CONE LIGHT QI DOOR BELT. O RECESSED WALL WASHER LGT FIXT. ® FLOOR MOUNTED RECEPTACLE O RECESSED LOW VOLTAGE LGT F1XT. ® FLOOR MOUNTED TET.EPF NE OUTLET DRINKING FOUNTAIN SURFACE MOUNTED FUIORESC. LGT. = ELECTRICAL. PANEL 11 POOL LIGHT DOUBLE FLOOD LIGHT FIXTURE GFI BATH RECEPT. # 12-1/2- 1000 1 '20 13 14 TENANT SPACE MCB 50A 3- #8THWN CU, 1" CONDUIT ELECTRICAL PANEL SCHEDULE 'A" TYPE : PANEL BOARD MAINS : M.C.B. A 100A MOUNTING : SURFACE 22,000 A.I.C. BUS RATING : 100 AMP LOCATION : BACK ROOM VOLTAGE : 208 /12OV- 3PHASE -4WIRE DESCRIPTION WIRE & COND. SIZE LOAD (V.A.) POL TRIP CKT No. A B C CKT NO. POL TRIP LOAD (V.A.) WIRE & COND. SIZE DESCRIPTION RECEPTACLES #12 -1/2" 720 1 20 1 2 1 20 600 #12 -1/2" LIGHTS RECEPTACLES #12 -1/2" 720 1 20 3 4 1 20 800 #12 -1/2" LIGHTS RECEPTACLES #12 -1/2" 1000 1 5 6 2 4432 #8 -3/4" AHU RECEPTACLES #12 -1/2" 1000 1 7 8 ROOF MAINT RECE #12 -1/2" 180 1 20 9 10 2 25 3952 #10 -1/2 " CU (NON COINCIDENT) DRINKING FOUNTAIN #12 -1/2" 1600 1 20 11 12 GFI BATH RECEPT. # 12-1/2- 1000 1 '20 13 14 SPARE 1000 1 15 16 SPARE 1000 1 20 17 18 SPARE 1000 1 20 19 20 21 22 23 24 25 26 27 28 29 30 CONTACTOR * CONTROLLED BY TIME CLOCK THROUGH LIGHTING LOAD CALCULATION PANEL CONTINUOUS LOAD AT 1259 = 1400 VA X 1.25 =1750 VA NON CONTINUOUS LOAD AT 1009 = 13652 VA TOTAL DEMANDED LOAD = 15402 VA TOTAL DEMAND AMPS = 43 AMPS PER PHASE 4 -#3 THWN CU, 1 1/2" CONDUIT PANEL "L" OOA MCB 20/208V CITY OF SOUTH MIAMI BUILDING DEPT. ELECTRICAL SECTION APPROVED BY: DATE• G Q ' XMER TI 30KVA 480/277- 120/208V 30 KVA, FLOOR MTD TRANSFORMER 6 THWN CU GRND TO GROUNDING SYSTEM OF ELECTRICAL NOTES, LEYEND, PANEL SCHEDULE & RISER THE BUILDING SCALE: N.T.S. PROJECT N0: 0804045 date MAY 8 2008 sheet t i t l e BLITSTEIN DESIGN •�•` " " "�t! 1'il tl - Interior White -box Build -out ' Scale: a s shown 13780 SW 28th Street, Suits 201 ��• ,"TIC . A S S O C I A T E S MIamI,Florida33175 r °`�� ;;?:•� •• ��<<� ELECTRICAL NOTES J . It revision , sheet number AR0007570 T°' `' �'�°°° �� �' LEYEND, PANE L •.V �xc • Fax: (305)221 8010 ' �. Retail ace Email: ucQucieng.com ; }, SCHEDULE &RISE R ARCHITECTURE" � INTERIOR DESIGN RJ.MlrenaaP.E No. 35579 i; �: ;:,�' k. >' `; 1�.. E -3 .. c is S �,.. ,� ., 285 Sevilla Avem ie Coral Gables, FI 33134 Darla a ���y P.E. "° 37234 O . project number E13000404, ; •.;PLbt��•;;,,� South Miami - Municipal Parking Facility 305.444 -4433 fax 305. 4440181 udengineei ing >, . • • . • • • , mil.. EMAIL bdamiamiobellsouthnet Pro'�iona1°�1end S�;G,:1 5829 S.W. 73rd Street, South Miami, Florida 33143 From Vision to Reality Mechanical Engineers ''��jtf /lt<��t' drawn by M.L., E.F., A.R.