08-622-00224"
adWa ., adW I-TI TP P cFCTION
1.5 GAL, ANSUL TANK
1,5 GAL, ANSUL TANK
24 "° x 24" FILTER SECTION
NOZZLE PLACEMENT REQUIREMENTS
HAZARD MAXIMUM HAZARD NOZZLE NOZZLE NOZZLE TIP NOZZLE
DIMENSIONS QTY. PART No. STAMPING— HEIGHT
24" FLOW No.
ELECTROSTATIC INDIVIDUAL CELL 4 419334 j2 N - - - - - --
PRECIPITATOR
DISTRIBUTION PIPING REQUIREMENTS
DISTRIBUTION PIPING REQUIREMENTS — 1.5GAL. AGENT TANK (EA.)
240 24" 24" 24" REQUIREMENTS
SUPPLY /LINE
DUCT
PLENUM
APPLIANCE
BRANCH LINE
BRANCH LINE
BRANCH LINE
114110 PIPING SIZE
in.
3/ in.
3/ in.
% in.
Y 414E MAXIMUM LENGTH
40 ft.
6 ft.
4 ft.
10 ft.
INLET
To oar
OUTLET
MAXIMUM RISE
6 ft.
4 ft.
2 ft.
2 ft.
<FT MAXIMUM 90'
9
4
4
6
ELBOWS
MAXIMUM TEES
1
1
2
3
n ?, MAXIMUM FLOW
5
2
2
3
FUSIBLE LIN
DETECTOR
�r
2nd FLOOR PARKING LAYOUT
SCALE: 3/16" = F
NUMBERS
GENERAL NOTE:
1.- SYSTEM SHALL BE PROVIDED WITH A LOCAL INDICATOR/ALARM AND WITH A RELAY TO
SHUT DOWN SUPPLY FAN WHEN SYSTEM IS ACTIVATED TURN ON EXHAUST FAN, AND SHUT OFF
ALL ELECTRIC UNDER HOOD. (BY OTHERS)
2.- PIPE SHALL BE 3/8" SCHEDULE BLACK IRON.
3.- BALLOON TEST TO BE PERFORM TO ENSURE SYSTEM FUNCTIONS PROPERLY.
(NITROGEN WILL BE BLOWN THROUGH THE LINES TO VERIFY PIPING IS UNOBSTRUCTED)
4: INSTALLATION COMPLIES WITH NFPA 17AAND NFPA96.
5.- ONLY MANUFACTURES LISTED COMPONENTS USE FOR AND WITH THIS SYSTEM.
6: IN AREA OF PENETRATION, CONDUIT AND PIPING WILL HAVE GREASE TIGHT FITTINGS.
7.- THERE IS NO GAS ASSOCIATED WITH THIS UNIT.
8.- THIS IS AN EXHAUST UNIT THAT DOES NOT HAVE A FRYER AND THEREFORE SHOULD
NOT REQUIRE A K -TYPE FIRE EXTINGUISHER.
THE ANSUL R -102 FIRE SUPPRESSION SYSTEM IS PROTECTING
WITH ONE 1.5 GAL. AGENT TANK.
THIS SYSTEM IS USING 2 FLOW POINTS OUT OF THE 6
POSSIBLE FLOW POINTS.
- -- , �ve -:,! a w
pf,®101)
�� CQ��� F►aE A���
p�a �S wA�tiRµplN
G.
p4Kr�S
IDACE' J
Q
cy-
W
Z
w
LL-
J
/z" EMT TO
ANSUL PULL
STATION
3 /8p PIPE
TO NOZZLE
L
ANSUL R -102
REGULATED AUTOMAN
RELEASE ASSEMBLY
(MECHANICAL)
Y2W EMT TO
FUSIBLE LINK
DETECTORS
TYPICAL INSTALLATION
ANSUL R- 102(UL300)
ONE 1,5GAL, CYLINDER SYSTEM
N.T.S.
Triangle Fire, Inc.
' 7720 N.W. 53rd Street, Miami, FL 33166
(305) 592-3011, Fax: (305) 592 -5254
RA SUSHI
5829 SW 73rd STREET
SOUTH MIAMI, FLORIDA
SCALE AS SHOWN DRAWN BY BENY NAJARRO
DATE APRIL 2, 2008 REVISED MAY 23, 2008
ANSUL R -102 FIRE SHEET
SUPPRESSION SYSTEM 2
WITH ONE 1.5 GAL. AGENT TANK of 3 SHEETS
i