08-622-001/_'�X f /_'�k i tK �P P� G O KITCHEN HOOD FIRE SUPPRESSION SYSTEM N.T.s Z\� ANSUL R -102 F.S.S. KITCHEN LAYOUT SCALE: 1/4" = 1' FIRE SYSTEMI PULL STATION ANSUL SYSTEM SIGN DIETAIL Y2 " EMT TO SHUT OFF GAS VALVE 3�" EMT TO FUSIBLE LINK DETECTORS J2" EMT TO ANSUL PULL STATI 0 N NOZZLE PLACEMENT REQUIREMENTS ^ HAZARD MAXIMUM HAZARD NOZZLE NOZZLE NOZZLE TIP NOZZLE DIMENSIONS QTY. PART No. STAMPING— HEIGHT FLOW No. DUCT LENGTH — UNLIMITED 2 419337 2W - - - - - -- PERIMETER— 100in DIAMETER -31 %in PLENUM LENGTH -10 ft. 2 419335 1N - - - - - -- RANGE LONGEST SIDE -28in. 2 419340 245 40 -50in. AREA -672 sq. in. GAS RADIANT LONGEST SIDE -36in. 1 419335 1N 15 -40in. CHAR — BROILER AREA -864 sq. in. FRYER MAXIMUM SIZE 2 419338 3N 21 -34in. (with drip board) 25 %in. x 19Y2in. Fry pot must not exceed 19Y2in. x 19in. DISTRIBUTION PIPING REQUIREMENTS DISTRIBUTION PIPING REQUIREMENTS — 3.OGAL. AGENT TANK (EA.) REQUIREMENTS SUPPLY /LINE DUCT PLENUM APPLIANCE ENT TANK BRANCH LINE BRANCH LINE BRANCH LINE PIPING SIZE Y8 in. -Y8 in. % in. % in. MAXIMUM LENGTH 40 ft. 8 ft. 4 ft. 12 ft. ANSUL R -102 REGULATED AUTOMAN RELEASE ASSEMBLY (MECHANICAL) TYPICAL INSTALLATION ANSUL R -102 (UL300) TWO 3.OGAL AGENT TANK MAXIMUM RISE 6 ft. 4 ft. 2 ft. 2 ft. MAXIMUM 90' 9 4 4 6 ELBOWS MAXIMUM TEES 1 2 2 4 MAXIMUM FLOW 11 4 2 4 NUMBERS GENERAL NOTES: 1.— SYSTEM ,SHALL BE PROVIDED WITH A LOCAL INDICATOR /ALARM AND WITH A RELAY TO SHUT DOWN THE +SUPPLY FAN (IF APPLICABLE) WHEN THE SYSTEM IS ACTIVATED, TURN ON EXHAUST FAN AND SHUT OFF ALL ELECTRIC UNDER THE HOOD. (BY OTHERS) 2.— KITCHEN FIRE SUPPRESSION SYSTEM WILL SHUT OFF THE GAS VALVE TO BE INSTALLED IN AN ACCESSIBLE PLACE BELOW THE CEILING. (IF APPLICABLE) 3.— PIPE SHALL BE 3/8" SCHEDULE 40 BLACK IRON. 4.— ONE "K" CLASS FIRE EXTINGUISHER WILL BE LOCATED WITHIN 30 FEET OF THE COOKING HOOD AS PER THE FLORIDA FIRE PREVENTION CODE. 5.— A BALLOON TEST TO BE PERFORMED TO ENSURE THAT THE SYSTEM FUNCTIONS PROPERLY. NITROGEN WILL BE BLOWN THROUGH THE LINES TO VERIFY PIPING IS UNOBSTRUCTED. 6.— THE INSTALLATION COMPLIES WITH NFPA 17A AND NFPA 96. 7.— ONLY MANUFACTURES LISTED COMPONENTS ARE USED FOR AND WITH THIS SYSTEM. 8.— IN AREA OF PENETRATION, CONDUIT AND PIPING WILL HAVE GREASE TIGHT FITTINGS. 9.— THE SYSTEM IS TO BE REVIEWED AND TESTED BY THE LOCAL (AHJ). I.E. FIRE MARSHALL. THIS HOOD IS PROTECTED BY THE ANSUL R -102 FIRE SUPPRESSION SYSTEM WITH TWO 3.OGAL. AGENT TANKS. THE TOTAL NUMBER OF FLOW POINTS OCCUPIED BY THE SYSTEM IS 17 FLOW POINTS OF THE 22 AVAILABLE FLOWS. -- i0 BE T�'p Sl ACCORDANCE, "'i iL tai :3t;i ' ✓ .,�,iTII N. F.P.A. F! RST PAGE a Q Z Lv J_ LL Triangle Fire, Inc. 7720 N.W. 53rd Street, Miami, FL 33166 (305) 592-3011, Fax: (305) 592 -5254 RA SUSHI 5829 SW 73rd STREET SOUTH MIAMI, FLORIDA SCALE AS SHOWN DRAWN BENY NAJARRO DATE APRIL 2, 2008 REVISED MAY 23, 2008 KITCHEN HOOD FIRE SUPPRESSION SYSTEM SHEET ANSUL R -102 FIRE SUPPRESSION SYSTEM 1 WITH TWO 3.OGAL. AGENT TANKS OF 3 SHEETS