KITCHEN HOOD FIRE SUPPRESSION SYSTEM
N.T.s
Z\�
ANSUL R -102 F.S.S.
KITCHEN LAYOUT
SCALE: 1/4" = 1'
FIRE SYSTEMI
PULL STATION
ANSUL SYSTEM SIGN DIETAIL
Y2 " EMT TO
SHUT OFF
GAS VALVE
3�" EMT TO
FUSIBLE LINK
DETECTORS
J2" EMT TO
ANSUL PULL
STATI 0 N
NOZZLE PLACEMENT REQUIREMENTS ^
HAZARD
MAXIMUM HAZARD
NOZZLE
NOZZLE
NOZZLE TIP
NOZZLE
DIMENSIONS
QTY.
PART No.
STAMPING—
HEIGHT
FLOW No.
DUCT
LENGTH — UNLIMITED
2
419337
2W
- - - - - --
PERIMETER— 100in
DIAMETER -31 %in
PLENUM
LENGTH -10 ft.
2
419335
1N
- - - - - --
RANGE
LONGEST SIDE -28in.
2
419340
245
40 -50in.
AREA -672 sq. in.
GAS RADIANT
LONGEST SIDE -36in.
1
419335
1N
15 -40in.
CHAR — BROILER
AREA -864 sq. in.
FRYER MAXIMUM SIZE 2 419338 3N 21 -34in.
(with drip board)
25 %in. x 19Y2in.
Fry pot must not
exceed 19Y2in. x 19in.
DISTRIBUTION PIPING REQUIREMENTS
DISTRIBUTION PIPING REQUIREMENTS — 3.OGAL. AGENT TANK (EA.)
REQUIREMENTS SUPPLY /LINE DUCT PLENUM APPLIANCE
ENT TANK BRANCH LINE BRANCH LINE BRANCH LINE
PIPING SIZE Y8 in. -Y8 in. % in. % in.
MAXIMUM LENGTH 40 ft. 8 ft. 4 ft. 12 ft.
ANSUL R -102
REGULATED AUTOMAN
RELEASE ASSEMBLY
(MECHANICAL)
TYPICAL INSTALLATION
ANSUL R -102 (UL300)
TWO 3.OGAL AGENT TANK
MAXIMUM RISE 6 ft. 4 ft. 2 ft. 2 ft.
MAXIMUM 90' 9 4 4 6
ELBOWS
MAXIMUM TEES 1 2 2 4
MAXIMUM FLOW 11 4 2 4
NUMBERS
GENERAL NOTES:
1.— SYSTEM ,SHALL BE PROVIDED WITH A LOCAL INDICATOR /ALARM AND WITH A RELAY TO SHUT
DOWN THE +SUPPLY FAN (IF APPLICABLE) WHEN THE SYSTEM IS ACTIVATED, TURN ON EXHAUST FAN
AND SHUT OFF ALL ELECTRIC UNDER THE HOOD. (BY OTHERS)
2.— KITCHEN FIRE SUPPRESSION SYSTEM WILL SHUT OFF THE GAS VALVE TO BE
INSTALLED IN AN ACCESSIBLE PLACE BELOW THE CEILING. (IF APPLICABLE)
3.— PIPE SHALL BE 3/8" SCHEDULE 40 BLACK IRON.
4.— ONE "K" CLASS FIRE EXTINGUISHER WILL BE LOCATED WITHIN 30 FEET OF THE COOKING
HOOD AS PER THE FLORIDA FIRE PREVENTION CODE.
5.— A BALLOON TEST TO BE PERFORMED TO ENSURE THAT THE SYSTEM FUNCTIONS PROPERLY.
NITROGEN WILL BE BLOWN THROUGH THE LINES TO VERIFY PIPING IS UNOBSTRUCTED.
6.— THE INSTALLATION COMPLIES WITH NFPA 17A AND NFPA 96.
7.— ONLY MANUFACTURES LISTED COMPONENTS ARE USED FOR AND WITH THIS SYSTEM.
8.— IN AREA OF PENETRATION, CONDUIT AND PIPING WILL HAVE GREASE TIGHT FITTINGS.
9.— THE SYSTEM IS TO BE REVIEWED AND TESTED BY THE LOCAL (AHJ). I.E. FIRE MARSHALL.
THIS HOOD IS PROTECTED BY THE ANSUL R -102 FIRE
SUPPRESSION SYSTEM WITH TWO 3.OGAL. AGENT TANKS.
THE TOTAL NUMBER OF FLOW POINTS OCCUPIED BY THE
SYSTEM IS 17 FLOW POINTS OF THE 22 AVAILABLE FLOWS.
-- i0 BE
T�'p Sl ACCORDANCE,
"'i iL tai :3t;i ' ✓
.,�,iTII N. F.P.A.
F! RST
PAGE
a
Q
Z
Lv
J_
LL
Triangle Fire, Inc.
7720 N.W. 53rd Street, Miami, FL 33166
(305) 592-3011, Fax: (305) 592 -5254
RA SUSHI
5829 SW 73rd STREET
SOUTH MIAMI, FLORIDA
SCALE AS SHOWN DRAWN BENY NAJARRO
DATE APRIL 2, 2008 REVISED MAY 23, 2008
KITCHEN HOOD FIRE SUPPRESSION SYSTEM SHEET
ANSUL R -102 FIRE SUPPRESSION SYSTEM 1
WITH TWO 3.OGAL. AGENT TANKS OF 3 SHEETS