Loading...
08-552R-004.,da. Miami -Dade Fire Rescue Fire Alarm Pre - Submittal Checklist MCOUNTIt LJ Designed by: ' �� % — ' Phone: I / 1 Signature: Created by: ZGH 03/07 YES NO N/A A location key is provided showing the area of proposed work within the building. Also a site key with north arrow for projects with multiple buildings showing locations of all (� 26 buildings with addresses. Floor plans are drawn to 1/8" scale or, if using another scale, all device coverage is 27 diagrammed on the plan and all room dimensions are included. All rooms & spaces are labeled indicating their use. Also, for all assembly use rooms r/ 28 with an occupant load of 50 or greater the occupant load has been provided. / 29 All new, existing, relocated or replaced devices are indicated on the floor plan & riser. 30 Ceiling a /condition and height is provided for all ceiling mounted devices. All devices in areas in which the voltage, temperature, and humidity variations exceed those conditions stated in NFPA 72, are listed for conditions and all such ( / 31 areas are identified. 32 The FACP or remote annunciator is located at the main entrance/lobby. The FACP and all sub panels in unoccupied rooms are protected with a smoke 33 detector. If a complete automatically activated system, there is at least 1 pull station on each / 34 floor or 2 for large buildings. If a manually activated system, the travel distance to reach a pull station is less than 35 200' feet and within 5' feet of exits. All automatic initiating devices are shown and are located in accordance with NFPA 36 72, the manufacturer's specifications, and accepted engineering ractices. All visual notification appliances are placed per the tables in NFPA 72 and each 37 strobe has it's candela rating listed on the floor plan and riser. All corridor spaced strobes are placed a maximum of 100' feet apart and within 15' 38 feet from ends of the corridor. 39 All spaces meet the audible characteristics of NFPA 72 and NFPA 101. Walls /partitions that do not extend to ceiling and racks, shelves and equipment, (; 40 which may block devices, are shown with their heights indicated. Duct detectors or relays for duct detectors are shown on the floor plan and riser for 41 all systems over 2000 cfm. These devices are powered by fire alarms stem. A riser diagram is provided showing each floor of building with all zones and circuits 42 labeled. 43 The wire size, type, and number of conductors are provided for each circuit on riser. / The fire pump is monitored for run, phase reversal & phase loss to _ a j 44 continuously manned location, or the supervised fire alarms stem. All relays for automatic extinguishing systems are shown on the floor plan and riser. 4 Hoods, booths, FM -200, spiCinkler, etc. The ampacity of each power supply and circuits is specified for each fire alarm 46 control panel and NAC panel. Also, individual device current is specified on plans. The total footage to the last device is Included with the voltage drop calculations for 47 each notification appliance circuit of each power supply. 48 The wattage tap is indicated for all speakers. 49 The wattage capacity and load calculation is provided for each amplifier. All load values for stand -by and alarm used in calculations are highlighted on mfg. / spec. sheets. Also, ampacity of equipment/components and circuits is highlighted on 50 1 mfg. spec. sheet This system includes Emergency Voice Evacuation and is provided with 15 minutes 51 of secondary alarm power. / This system is being provided back up power by an emergency generator and will / 52 provide 4 hours of standby power plus the appropriate seconds alarm power. Battery calculations, detailed in chart form, showing all information required per NFPA 72 4.4.1.5.3.1 are provided for each back-up power supply. cj LJ Designed by: ' �� % — ' Phone: I / 1 Signature: Created by: ZGH 03/07