=� Fire Alarm Pre - Submittal Checklist
CQtltr]'i!1
Designed by: `i; �F "r�ls Phone:
Signature: A Created by: ZGH 03/07
t=�
Fire Department Application #
YES
NO
N/A
LOCATION /COMMENTS
Project Name: �'�i `+ t and is provided in title block.
Address: t r and Is provided In title block.
A copy of the contract is provided or a notarized affidavit from the owner showing the
I �r .
ric-
1
total cost of the equipment and installation. Cost $
2
Systems costing more than $5,000 are sealed by a State of Florida Reg. Prof. Engineer.
3
The total number of devices and components being installed is �i
v
4
A copy of alarm qualifier's state license is attached. EC EF EH EY #
A copy of UL or FM certificate for contractor pulling permit or,
a copy of the contract between Owner and Central Station Service company to provide
O FF1G
5
Supervision of the installation, servicing and monitoring of the system is attached.
Complete, current manufacturer's specification sheets are provided for all devices,
(�
6
modules, control units, and components.
7
Manufacturer's documentation of device compatibility has been provided.
A copy of the Notice of Violation from Miami -Dade County Fire Rescue, or a copy of the
8
relevant sections of the approved Life Safety Plan, is attached.
This fire alarm: %< is required under G�' le l L — I C"' =i (fill in the code
{Ex: Occupancy chapter /section from NFPA 101) or indicate if it is a life safety
9
equivalency), or is a non- required system or component.
For non - required systems or components, a statement is included indicating which code
or AHJ (See def. AHJ in NFPA 72) is requiring the system or component and the
--
10
parameters of the requirement.
This system is a "Local" Fire Alarm System or a "Proprietary Supervising Station" Fire
11
Alarm System and is stated as such on the plans. 24 hours seconds power)
This system will be "certificated or placarded" as a "Central Station Service"
C/
12
Fire Alarm System and is stated as such on the plans. 24 hours seconds ower
This system is an "Existing Remote Supervising Station"
C
13
Fire Alarm and is stated as such on the plans. 24 hours seconds power)
14
_System
A complete detailed statement of the scope of work is stated on the plan.
(•i
A description of the building and/or section of the building is provided including, fire
suppression systems, number of stories, square footage, and elevation of the last
15
occupied floor if over 5 stories.
All interconnected fire alarm control panels are arranged to function as a single system
/
16
and monitored for integrity er NFPA 72.
The class and /or style are shown for all initiating device circuits, signal line circuits and
17
notification appliance circuits.
The maximum number of each device type is provided for each IDC based on device
01,;
IUQU U� l:u ,1 JLI,, U......0 V11 Vlu...r u11U ♦i: , ��I ... , .. 72 uI,U
18
s ecifications.
A specific sequence of operation including all alarm, supervisory, trouble and control
functions such as fire suppression, door release, smoke control, elevator recall,
19
transmission of signal offsite, etc., are explained in detail in the Se g. of O s.
/
20
Elevator recall is connected to the fire alarms stem.
C
Manufacturer, model number and unique symbol for each device, module, power supply
21
1 and component are specified in the symbol legend.
Emergency forces notification or sprinkler supervision fis required or _ is provided,
22
but is not required.
23
Off -site monitoring �s provided is not provided.
.
24
The method of communication to the monitoring station is included on the riser.
��25A
Each device, module, appliance and component is identified with it's own unique
number and indicated on the floor plan and riser.T
lo��
Also label each module and relay with it's intended function on riser.