08-552-003FIRE ALARM INSTALLATION & OPERATION NOTES: SCOPE OF WORK: 1. INSTALL A NEW MANUAL INITIATING CERTIFICATED CENTRAL STATION STATION FIRE ALARM SYSTEM WITH HORN STROBE NOTIFICATION, 60 HOUR STANBY AND 2 LINE DACT FOR EMERGENCY FORCES NOTIFICATION. 2. IN ADDITION TO THE REQUIRED MANUAL INITIATION CERTIFICATED CENTRAL STATION FIRE ALARM SYSTEM PARTIAL COVERAGE AUTOMATIC SMOKE DETECTION WILL BE INSTALLED IN HAZARDOUS b AREAS. OCCUPANCY INFORMATION: QQ 1. THIS IS A NEW RESTAURANT OCCUPANCY TYPE; NFPA 101 REEF. 38.3.4 -. O� (2000). c�`gI/m 2. THIS IS A SINGLE STORY OCCUPANCY. 3. THE SIZE OF THIS OCCUPANCY IS APPROXAMATELY 7,320 SQUARE FEET. SEQUENCE OF OPERATION: 1. UPON THE ACTIVATION OF A CEILING SMOKE DETECTOR OR A CEILING HEAT DETECTOR ON ANY LEVEL THE FACP WILL ACTIVATE GENERAL ALARM TURNING ON ALL THE AUDIBLE / VISUAL NOTIFICATION DEVICES ON ALL LEVELS, THE SIGA -CR RELAYS WILL SHUT DOWN ALL AHUS OVER 2000 CFM, CLOSE THE FSUS ON ALL LEVELS AND DE- ENERGIZE ALL MAGLOCKS. THE FACP AND ANNUNCIATOR WILL DISPLAY THE ALARM LOCATION ILLUMINATE THE ALARM LED AND THE DIALER WILL CALL THE LISTED CENTRAL STATION THAT WILL DISPATCH EMERGENCY FORCES. 2. UPON THE ACTIVATION OF A MANUAL PULL STATION ON ANY LEVEL THE FACP WILL ACTIVATE GENERAL ALARM TURNING ON ALL THE AUDIBLE / VISUAL NOTIFICATION DEVICES ON ALL LEVELS, CONTROL RELAYS WILL SHUT DOWN ALL AHUS OVER 2000 CFM, CLOSE THE FSUS ON ALL LEVELS AND DE- ENERGIZE ALL MAGLOCKS. THE FACP AND ANNUNCIATOR WILL DISPLAY THE ALARM LOCATION ILLUMINATE THE ALARM LED AND THE DIALER WILL CALL THE LISTED CENTRAL STATION THAT WILL DISPATCH EMERGENCY FORCES. 3. UPON THE ACTIVATION OF THE ALARM SILENCE SWITCH AT THE FACP ALL AUDIBLE / VISUAL NOTIFICATION DEVICES ON ALL LEVELS WILL TURN OFF. ANY NEW ALARMS DETECTED AFTER THE NOTIFICATION DEVICES HAVE BEEN SILENCED WILL REACTIVATE THE AUDIBLE / VISUAL DEVICES ON ALL LEVELS. SPRINKLER WATER FLOW ALARMS CANNOT BE SILENCED UNTIL THE WATER FLOW IS SHUT OFF. 4. THE FACP WILL MONITOR THE SYSTEM FOR REMOVED DEVICES, OPEN FIELD WIRING, GROUNDS ON SYSTEM WIRING, AC POWER FAILURE, LOW BATTERY VOLTAGE AND PHONE LINES 1 & 2 TROIUBLE. ALL SYSTEM TROUBLES WILL INDICATE A ALARM AT THE FACP. THE DIALER WILL CALL THE LISTED CENTRAL STATION THAT WILL DISPATCH THE ALARM SERVICE COMPANY. POWER SUPPLY OPERATION: 1. EACH REMOTE NOTIFICATION POWER SUPPLY WILL ANNUNCIATE ONLY ONE SYSTEM TROUBLE MESSAGE AT THE FACP FOR THE FOLLOWING ABNORMAL CONDITIONS; REMOVED DEVICES OR OPEN WIRING FOR ARE SERVED AC POWER LOSS, BATTERY TROUBLE AND GROUND FAULT. WHEN A REMOTE POWER SUPPLY TROUBLE IS DISPLAYED AT THE FACP THE RESPONDING PERSONAL MUST USE THE LED INDICATORS AT THE REMOTE POWER SUPPLIES TO DETERMINE THE SPECIFIC TROUBLE CONDITION. PS SIGNALING WILL NOT PROVIDE INDIVIDUAL TROUBLE ANNUNCIATION AT THE FACP. INSTALLATION NOTES: 1. THIS IS A COMPLETE NEW POWER LIMITED ADDRESSABLE FIRE ALARM SYSTEM. 2. THIS IS A CERTIFICATED CENTRAL STATION SERVICE SYSTEM WITH 24 HOUR STAND -BY BATTERIES. 3. LOCATE ALL CEILING TYPE DETECTORS AT LEAST 3' AWAY FROM ALL AC DIFFUSERS AND DOORS. 4. THE MANUAL PULL STATIONS WILL BE INSTALLED AT 48' FROM THE FLOOR TO CENTER OF THE DEVICE. 5. THE AUDIBLE / VISUAL NOTIFICATION APPLIANCES IN ALL AREAS WILL BE INSTALLED AT 80' FROM THE FLOOR TO THE BOTTOM OF DEVICE. ALL VISUAL DEVICES ARE SYNCHRONIZED AND THE AUDIBLE SIGNAL IS TEMPORAL PATTERN ALSO SYNCHRONIZED. 6. ALL MONITOR MODULES ARE TO BE INSTALLED WITHIN 3' OF THE POINTS, VALVES OR EQUIPMENT BEING MONITORED. SOME EXCEPTIONS APPLY i.e., PIV, BACK FLOW, ETC. 7. THE FACILITY OWNER MUST PROVIDE TWO DEDICATED PHONE LINES TO THE FACP. 8. ALL EQUIPMENT IS COMPATIBLE AND UL LISTED FOR FIRE ALARM SYSTEM USE- 9. PROVIDE BREAKER LOCKS FOR ALL FIRE ALARM CIRCUITS AND PAINT BREAKERS RED. 10. PAINT ALL FIRE -ALARM JUNCTION BOX COVERS RED. FIRE ALARM LEGEND COUNT SYMBOL DEVICE TYPE MODEL MANUFACTURE 1 FA P FIRE ALARM CONTROL PANEL QS1 E. .T ohms 1 P/S REMOTE POWER SUPPLY BPS6A S.T 3 x 0 i 5 329 x 1 HORN / STROBE (GI RF=HDVM S.T 4/ ® / STROBE ONLY IG1RF-VM V ^ E.S.T 1 ® WEATHERPROOF CS405 -8A T E.S.T 3 0 MANUAL PULL STATION SIGA -278- E.S.T •� 1 QM SIGNAL INPUT MODULE SIGA -CT1 E.S.T 1 © SYNCHRONIZATION MODULE SIGA -CCIIS E.S.T 1 O SMOKE DETECTOR SIGA -PS E.S.T 20 TOTAL DEVICES SCOPE OF WORK INSTALL NEW EST (QS1) FIRE ALARM CONTROL PANEL, (BPS6A) REMOTE POWER SUPPLY, INITIATING AND NOTIFICATION DEVICES AS SHOWN ON FLOOR PLAN AND RISER DIAGRAM. SYSTEM WILL BE CONNECTED TO BASE BUILDING FIRE ALARM SYSTEM. •y• r� . OUTPUT CIRCUfT (mA) OTY ub -Tot (mA) 01Y Sub-Tot VOLTAGE DROP CALCULATIONS (MA) QTY Sub -Tot (mA) QTY Sub-T ( ) TY Sub -Tct (mA) QTY Sub -TD# (mA) (fleet) AWG Volts ohms 20.4V Start Value Voltage(V) PS 1 CIR# 1 28 2 562 3 x 0 0 329 x 1 329 311 x 0 0 239 x 478 9 x 0 0 1.369 106 14 0.926 3.19 19.474 PS 1 CIR# 2 281, x 3 843 x 0 0 329 x 0 0 x 0 0 x 0 9 x 0 0 0.843 118 14 0.635 3.19 19.765 SPARE x 0 0 x 0 0 x 0 , 0 x 0 0 x 0 0 9 x 0 0 0.000 0 14 0.000 3.19 20.400 SPARE 1XI 0 1 0 0 0 1XI 0 0 x 0 0 1 1XI 0 0 9 x 0 0 0.000 0 14 0.000 3.19 20.400 -XI Cable Size Ohm/1000 ft 12 AWG 201 14 AWG 3.19 DEVICE NUMBER CURRENT PER DEVICE STANDBY JALARM 750d BPS6A 75 mA 190 mA NOTIFICATION DEVICES x HIS 5 161 mA 0 mA 805 mA STR75 4 152 mA SCALE: 0 mA 608 mA STR110 WP 1 248 mA 1.1.4 1.1.5 0 mA 248 mA TOT. CURR- RATINGS ALL DEV. line A,B,C 75 mA 1851 mA TOTAL CURR. CONVERTED TO AMPS 0.001 0.075 A 1.851 A NUMBER OF STANDBY HOURS (24 for NFPA) 24 Hr Multiply lines E & F Total standby AH 1.8 AH ALARM SOUNDING PERIOD /HOURS 5 MIN= .0833 HRS 0.0833 Hr MULTIPLY LINES E & H 0.154188 AH ADD LINES G & 1 1.954188 AH 7 A/H PROVIDED MULTIPLY LINE J BY 1.20 (20% EXTRA FOR DESIRED PERFORMANCE (1.2 Derating Factor) 2.345026 AH 80' A.F.F. OR 6" BELOW CEILING (WHICHEVER IS LOWER) STROBE OR HORN/STROBE F O o E O PULL 48' A-F.F ADA HEIGHT REQUIRMENTS N.T.S. CI C!% ORA FIRE PENETRATION DETAIL U.L SYSTEM # F- 0-1149 1. PRE -RATED CONCRETE FLOORS OR BLOCK WALLS = MIN. 4-1/2' THICKNESS. 2. MAX. AREA OF OPENING = 288 SO. IN., WITH A MAX. DIMENSION OF 24'. METALLIC PIPE - A) STEEL PIPE - 8- DIAM. (OR SMALLER) SCH. 40 (OR HEAVIER) STEEL PIPE. B) CONDUIT - 4- DIAM. (OR SMALLER) EMT OR 6- DIAM. (OR SMALLER) STEEL CONDUIT. C) IRON PIPE - 8- DIAM. (OR SMALLER) CAST OR DUCTILE IRON PIPE. D) COPPER TUBING - 4- DIAM. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING. E) COPPER PIPE - 4" DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. NOTE: THE MAXIMUM NUMBER OF PIPES WITHIN OPENING IS 3. THE ANNUNLAR SPACE BETWEEN PIPES SHALL BE MIN. 1 -1/2' AND A MIN. 1/2' BETWEEN PIPES AND EDGE OF OPENING. 3. FORMING MATERIAL (NOT SHOWN, OPTIONAL) - NOM. 1- THICK POLYURETHANE BACKER_ 4. FYRE-SHIELD - MIN. 1/2" THICKNESS MASTIC APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF THE WALL ASSEMBLY. FIRE ALARM RISER DIAGRAM 1.2.3 1.2.4 1.2.5 ALL CIRCUITS ARE CLASS S' 1.2.1 1.2.2 750d 75od 750d (1B) 75od 75odj (B) SIGNAL (2# 14 T.H.H.N. - FPLP OR FPLR) .� • 1.521A F- NUMBER: F -00334 DATE: SCALE: 10/26/07 1/8 DRAWN BY: CHECKED BY: D.A.L. 1.1.4 1.1.5 I OF I 1.1.1 1.1.2 1.1.3 75od 750d (1B) 75cd 75cd 110cd EOL -1 &1.401A WP TO BASE BLDG. FACP PIS FACP (1A) D01 MM002� M�03_ MM004� M05 BPS6A (QS1) `MONITOR MODULE FOR FIRE SUPPRESSION SYSTEM M01 iNrHN L--- -1A - -J -120V (3) (# 12 T.H.H.N.) CIRCUIT #22 1 #12 TNHN DEDICATED PHONE LINES 120V (3) (# 12 T.H.H.N.) CIRCUIT #24 �V Y i SMOKE DETECTOR MINIMUM DISTANCE T AWAY FROM DUCT KEY PLAN N.T.S. A/C DEFUSER AND / OR FLOUORECENT LIGHT SMOKE DETECTOR MOUNTING DETAIL NOTE: DO NOT INSTALL A SMOKE DETECTOR IN DIRECT AIRFLOW DUCT FIRE ALARM LIRE LEGEND WIRE SYMBOL WIRE TYPE - - - - - (A) INITIATING (16-2 T.H.H.N. - FPLP OR FPLR) (B) SIGNAL (2# 14 T.H.H.N. - FPLP OR FPLR) .� • F- NUMBER: F -00334 DATE: i SMOKE DETECTOR MINIMUM DISTANCE T AWAY FROM DUCT KEY PLAN N.T.S. A/C DEFUSER AND / OR FLOUORECENT LIGHT SMOKE DETECTOR MOUNTING DETAIL NOTE: DO NOT INSTALL A SMOKE DETECTOR IN DIRECT AIRFLOW DUCT FIRE ALARM LIRE LEGEND WIRE SYMBOL WIRE TYPE - - - - - (A) INITIATING (16-2 T.H.H.N. - FPLP OR FPLR) (B) SIGNAL (2# 14 T.H.H.N. - FPLP OR FPLR) b 11.0,J a r' v w . O�D z p two 5� � W w wtv' H 3,vt 1 O Ci Ae Q > 1-0 N p0 amonD 10 (1 ' [l ,g J • w LLI qw LIU c CO• irr " N 4 "7 r y �a lot* • Y P 9 y U W O 1w CL REVISIONS: LICENSED ENGINEER: SHANTILAL C. PATEL (954) 327 -9475 P.E. 0028551 - FIRE PR6TEGTI s• -; C. .� • F- NUMBER: F -00334 DATE: SCALE: 10/26/07 1/8 DRAWN BY: CHECKED BY: D.A.L. B.P. I OF I