08-552-001
i i FIRE ALARM INSTALLATION & OPERATION NOTES: SCOPE OF WORK: 1. THIS IS A CERTIFICATED CENTRAL STATION FIRE ALARM SYSTEM WITH HORN STROBE NOTIFICATION, 24 HOUR STANBY AND 2 LINE DACT FOR EMERGENCY FORCES NOTIFICATION. 2. INSTALL NEW EST (QS1) FIRE ALARM CONTROL PANEL, (BPS6A) REMOTE POWER SUPPLY, INITIATING AND NOTIFICATION DEVICES AS SHOWN ON FLOOR PLAN AND RISER DIAGRAM. SYSTEM WILL BE CONNECTED TO BASE BUILDING FIRE ALARM SYSTEM. AS OCCUPANCYINFORMA NOTED 1. THIS IS A NEW BUSINESS OCCUPANCY TYPE, NFPA 101 CHAPTER 38 (2003). _ 2. THE SIZE OF THIS OCCUPANCY IS APPROXAMATELY 7,320 SQUARE FEET (SINGLE STORY). THIS OCCUPANCY IS FULLY SPRINKLED AND MONITORED BYBUILDINGS BASE FACP. SEQUENCE OF OPERATION: 1. UPON THE ACTIVATION OF A CEILING SMOKE DETECTOR OR A CEILING HEAT DETECTOR ON ANY LEVEL THE FACP WILL ACTIVATE GENERAL ALARM TURNING ON ALL THE AUDIBLE / VISUAL NOTIFICATION DEVICES ON ALL LEVELS, THE SIGA -CR RELAYS WILL SHUT DOWN ALL AHUS OVER 2000 CFM, CLOSE THE FSD'S ON ALL LEVELS AND DE- ENERGIZE ALL MAGLOCKS. THE FACP AND ANNUNCIATOR WILL DISPLAY THE ALARM LOCATION ILLUMINATE THE ALARM LED AND THE DIALER WILL CALL THE LISTED CENTRAL STATION THAT WILL DISPATCH EMERGENCY FORCES. 2. UPON THE ACTIVATION OF A MANUAL PULL STATION ON ANY LEVEL THE FACP WILL ACTIVATE GENERAL ALARM TURNING ON ALL THE AUDIBLE / VISUAL NOTIFICATION DEVICES ON ALL LEVELS, CONTROL RELAYS WILL SHUT DOWN ALL AHUS OVER 2000 CFM, CLOSE THE FSD'S ON ALL LEVELS AND DE- ENERGIZE ALL MAGLOCKS. THE FACP AND ANNUNCIATOR WILL DISPLAY THE ALARM LOCATION ILLUMINATE THE ALARM LED AND THE DIALER WILL CALL THE LISTED CENTRAL STATION THAT WILL DISPATCH EMERGENCY FORCES. 3. UPON THE ACTIVATION OF THE ALARM SILENCE SWITCH AT THE FACP ALL AUDIBLE / VISUAL NOTIFICATION DEVICES ON ALL LEVELS WILL TURN OFF. ANY NEW ALARMS DETECTED AFTER THE NOTIFICATION DEVICES HAVE BEEN SILENCED WILL REACTIVATE THE AUDIBLE / VISUAL DEVICES ON ALL LEVELS. SPRINKLER WATER FLOW ALARMS CANNOT BE SILENCED UNTIL THE WATER FLOW IS SHUT OFF. 4. THE FACP WILL MONITOR THE SYSTEM FOR REMOVED DEVICES, OPEN FIELD WIRING, GROUNDS ON SYSTEM WIRING, AC POWER FAILURE, LOW BATTERY VOLTAGE AND PHONE LINES 1 & 2 TROIUBLE. ALL SYSTEM TROUBLES WILL INDICATE A ALARM AT THE FACP. THE DIALER WILL CALL THE LISTED CENTRAL STATION THAT WILL DISPATCH THE ALARM SERVICE COMPANY. POWER SUPPLY OPERATION: 1. EACH REMOTE NOTIFICATION POWER SUPPLY WILL ANNUNCIATE ONLY ONE SYSTEM TROUBLE MESSAGE AT THE FACP FOR THE FOLLOWING ABNORMAL CONDITIONS; REMOVED DEVICES OR OPEN WIRING FOR ARE SERVED AC POWER LOSS, BATTERY TROUBLE AND GROUND FAULT. WHEN A REMOTE POWER SUPPLY TROUBLE IS DISPLAYED AT THE FACP THE RESPONDING PERSONAL MUST USE THE LED INDICATORS AT THE REMOTE POWER SUPPLIES TO DETERMINE THE SPECIFIC TROUBLE CONDITION. PS SIGNALING WILL NOT PROVIDE INDIVIDUAL TROUBLE ANNUNCIATION AT THE FACP. INSTALLATION NOTES: 1. THIS IS A COMPLETE NEW POWER LIMITED ADDRESSABLE FIRE ALARM SYSTEM. 2. THIS IS A CERTIFICATED CENTRAL STATION SERVICE SYSTEM WITH 24 HOUR STAND -BY BATTERIES. 3. LOCATE ALL CEILING TYPE DETECTORS AT LEAST 3' AWAY FROM ALL AC DIFFUSERS AND DOORS. 4. THE MANUAL PULL STATIONS WILL BE INSTALLED AT 48" FROM THE FLOOR TO CENTER OF THE DEVICE. 5. THE AUDIBLE / VISUAL NOTIFICATION APPLIANCES IN ALL AREAS WILL BE INSTALLED AT 80" FROM THE FLOOR TO THE BOTTOM OF DEVICE. ALL VISUAL DEVICES ARE SYNCHRONIZED AND THE AUDIBLE SIGNAL IS TEMPORAL PATTERN ALSO SYNCHRONIZED. 6. ALL MONITOR MODULES ARE TO BE INSTALLED WITHIN 3 ' OF THE POINTS, VALVES OR EQUIPMENT BEING MONITORED. SOME EXCEPTIONS APPLY i.e., PIV, BACK FLOW, ETC. 7. THE FACILITY OWNER MUST PROVIDE TWO DEDICATED PHONE LINES TO THE FACP. 8. ALL EQUIPMENT IS COMPATIBLE AND UL LISTED FOR FIRE ALARM SYSTEM USE. 9. PROVIDE BREAKER LOCKS FOR ALL FIRE ALARM CIRCUITS AND PAINT BREAKERS RED. 10. PAINT ALL FIRE ALARM JUNCTION BOX COVERS RED. 1 FIRE ALARM LEGEND COUNT SYMBOL DEVICE TYPE MODEL MANUFACTURE 1 FACN FIRE ALARM CONTROL PANEL QS1 E.S.T PS 1 CIR# 1 1 FA-AR REMOTE ANNUNCIATOR PANEL SRA E.S.T 0 1 FE-771 REMOTE POWER SUPPLY BPS6A E.S.T 0 5 ® HORN / STROBE G1RF -HDVM E.S.T 4 ® STROBE ONLY G1RF -VM E.S.T 1 0 ®STROBE 0 x 0 ONLY WEATHERPROOF CS405-8A -T E.S.T 3 0 MANUAL PULL STATION SIGA -278 E.S.T 1 QM SIGNAL INPUT MODULE SIGA -CT1 E.S.T 1 © SYNCHRONIZATION MODULE SIGA -CC1S E.S.T 1 O SMOKE DETECTOR SIGA -PS E.S.T 20 TOTAL DEVICES OUTPUT CIRCUIT (mA) QTY Sub -Tot (mA) QTY Sub -Tot (mA) VOLTAGE DROP CALCULATIONS JQTY Sub -Tot (mA) QTY Sub-Tot (mA) QTY Sub -Tot (mA) QTY Sub -Tot (mA) (feet) PS 1 CIR# 1 281 x 2 562 0 x 0 0 329 x 1 329 x 0 1 0 255 x 2 510 0 X1 0 0 1.401 106 PS 1 CIR# 2 281 x 3 843 0 x 0 0 0 x 0 0 x 0 0 255 x 2 510 0 x 0 0 1.353 118 SPARE 0 x 0 0 0 x 0 0 0 x 0 0 x 0 0 x 0 0 0 x 0 0 0.000 0 SPARE 0 x 0 0 0 x 0 0 0 x 0 0 x 0 0 x 0 0 0 x 0 0 0.000 0 ` MONITOR MODULE FOR FIRE r. DEVICE NUMBER CURRENT PER DEVICE STANDBY JALARM BPS6A 70 mA 190 mA NOTIFICATION DEVICES x HIS 5 161 mA ®j - - - 1.521A 0 mA 805 mA STR75 4 152 mA 1.1.4 1.1.5 0 mA 608 mA STR110 WP 1 248 mA 75cd 110cd 0 mA 248 mA TOT. CURR. RATINGS ALL DEV. line A,B,C 70 mA 1851 mA TOTAL CURR. CONVERTED TO AMPS 0.001 0.07 A 1.851 A NUMBER OF STANDBY HOURS (24 for NFPA) 24 Hr Multiply lines E & F Total standby AH 1.68 AH ALARM SOUNDING PERIOD /HOURS 5 MIN= .0833 HRS 4 0.0833 Hr MULTIPLY LINES E & H 0.154188 AH ADD LINES G & 1 1.834188 AH 7 A/H PROVIDED MULTIPLY LINE J BY 1.20 (20% EXTRA FOR DESIRED PERFORMANCE (1.2 Derating Factor) 2.201026 AH 80" A.F.F. OR 6" BELOW CEILING (WHICHEVER IS LOWER) STROBE OR HORNISTROBE F O ' O E O PULL 48" A.F.F ADA HEIGHT REQUIRMENTS N.T.S. I M04 7 1 1 ELEC. RM. V�R.R C 7 1.1.1 75cd Ly 1.2.1 75cd /1.2.2 / R.R DINING AREA 7 1.2.4 FIRE PENETRATION DETAIL U.L SYSTEM # F-C -1149 WP 110cd 1.1.3 75cd 1.1.2 N, EOL -2 1.353A ri \& \ A.2 1. PRE -RATED CONCRETE FLOORS OR BLOCK WALLS = MIN. 4-1/2" THICKNESS. 2. MAX. AREA OF OPENING = 288 SO. IN., WITH A MAX. DIMENSION OF 24 ". METALLIC PIPE - A) STEEL PIPE - 8" DIAM. (OR SMALLER) SCH. 40 (OR HEAVIER) STEEL PIPE. B) CONDUIT - 4" DIAM. (OR SMALLER) EMT OR 6- DIAM. (OR SMALLER) STEEL CONDUIT. C) IRON PIPE - 8- DIAM. (OR SMALLER) CAST OR DUCTILE IRON PIPE. D) COPPER TUBING - 4- DIAM. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING. E) COPPER PIPE - 4" DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. NOTE: THE MAXIMUM NUMBER OF PIPES WITHIN OPENING IS 3. THE ANNUNLAR SPACE BETWEEN PIPES SHALL BE MIN. 1 -112" AND A MIN. 1/2" BETWEEN PIPES AND EDGE OF OPENING. 3. FORMING MATERIAL (NOT SHOWN, OPTIONAL) - NOM. 1" THICK POLYURETHANE BACKER. 4. FYRE- SHIELD - MIN. 10 THICKNESS MASTIC APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF THE WALL ASSEMBLY. FIRE ALARM RISER DIAGRAM WIRE SYMBOL WIRE TYPE 1.2.3 1.2.4 1.2.5 ALL CIRCUITS ARE CLASS B' 1.2.1 1.2.2 750d 75cd 75cd (16) 750d 750d EOL -2 (C) 24V POWER (2# 14 T.H.H.N. - FPLP OR FPLR) LL ®j - - - 1.521A F- NUMBER: F- 003344 DATE: 1.1.4 1.1.5 10/26/07 1.1.1 1.1.2 1.1.3 750d 75cd CHECKED Y: (1B) 750d 75cd 110cd OF IF J EOL -1 1.401A WP 1A TO BASEA INTERCONNECT FIRE ALARM CONTROL S1 P1 PANEL TO FUCTION AS AS A SINGLE SYSTEM. PIS R FACP BPS6A (QS1) D01 (1A\ M02 M03 M04 M05 ` MONITOR MODULE FOR FIRE r. SUPPRESSION SYSTEM �M01 1 #12 � #12 THHN 1A THHN L----- - - - - -J DEDICATED PHONE LINES 120V (3) (# 12 T.H.H.N.) -120V (3) (# 12 T.H.H.N.) CIRCUIT #22 CIRCUIT #24 (� MONITOR MODULE FOR FIRE M03 MO2 SUPPRESSION SYSTEM / KITCHEN BAR 75cd 1.1.5 ';>"� ';>"� ';X� HD ING NEA nnnnnnnn UUUUUU1 11 1 fFa _PlP2 75cd 1.1.4 EOL -1 1.401A ❑+ KEY PLAN SMOKE DETECTOR MINIMUM DISTANCE A/C DEFUSER AND / OR T AWAY FROM DUCT FLOUORECENT LIGHT SMOKE DETECTOR MOUNTING DETAIL NOTE: DO NOT INSTALL A SMOKE DETECTOR IN DIRECT AIRFLOW DUCT N.T.S. FIRE ALARM SHALL BE A CENTRAL STATION SERVICE. A CERTIFICATE OR PLACARD SHALL BE POSTED AT FINAL INSPECTION, AS PER NFPA 72 FIRE ALARM SYSTEM TO BE INSTALLED IN ACCORDANCE WrM NFPA 72; 70; 101• AS APPMOVEO MI"11 -DARE COUNTY FIRE DEPARTMENT BLD3. PERMIT FIRE ALARM �r FIRE SUPPRESSION WATER WATER MAIN EXT. DATE: J� PIP D BY: -- FIRE ALARM WIRE LEGEND WIRE SYMBOL WIRE TYPE - - - - - (A) INITIATING (16-2 T.H.H.N. - FPLP OR FPLR) (B) SIGNAL (2# 14 T.H.H.N. - FPLP OR FPLR) IL (C) 24V POWER (2# 14 T.H.H.N. - FPLP OR FPLR) lTRAWKING #,1� 6� -64' �1�2 R tHt >; OtL6%gNG I.Itt SA�'CY FE TLff EB SHALL BE PROVIDED AT TIME OF OCCUPAN� I�� ���/� ^ /'O v. ,,z liiiiiviiImi W^ � M CIO �Q CO ti Of a. N� H y REVISIONS: CITY COMMENTS 1 (04/23/08) LICENSED ENGINEER: SHANTILAL C. PATEL (954) 327 -9475 P.E. 0028551 FIRE PROTE TQ',N . / 10 T IL LU F- NUMBER: F- 003344 DATE: SCALE:` 10/26/07 '. •1J8 DRAWN BY: CHECKED Y: D.A.L. a OF IF J ;1