08-497-026GENERAL ELECTRICAL NOTES: I ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND OTHER APPLICABLE CODES AND STANDARDS 2 THE CONTRACTOR SHALL SATISFACTORILY REPAIR/REPLACE EQUIPMENT OR PART OF STRUCTURE DAMAGED AS A RESULT OF HIS WORK SURFACES AND FINISHED AREAS SHALL BE RESTORED TO MATCH ADJACENT AREAS 3. APPROVAL SHALL BE OBTAINED FROM THE ARCHITECT PRIOR TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT MEMBER 4, ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN/ NOTED OTHERWISE S INSTALL POWER AND CONTROL WIRING & REQUIRED CONTROL COMPONENTS FOR AIR CONDITIONING SYSTEMS AS SHOWN/ NOTED ON THESE DRAWINGS AND PER OTHER APPLICABLE DRAWINGS/ INSTRUCTIONS SEE AIR CONDITIONING DRAWINGS 6. MINIMUM WIRE SIZE SHALL BE #12 THHN/TT-(WN UNLESS OTHERWISE NOTED ON PLANS CONDUCTORS #6 AND LARGER SHALL BE THW. 7. ALL CONDUCTORS SHALL BE COPPER 8. ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALIC TYPE). IF PVC SCHEDULE 40 IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN ACCORDANCE WITH THE NEC 250 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED. 9. ALL MATERIALS SHALL BE UL APPROVED. 111 ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED. It CONTRACTOR SHALL SEAL ALL FIRE RATED PENETRATIONS WITH A FIRE SEALANT EQUAL TO THE RATINGS OF THE PENETRATION. V_ ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS U FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED 14 A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT SPECIFIED ON CONTRACT DRAWINGS CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE W/ A/C EQUIPMENT NAMEPLATE REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST. 15 CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS AS SHOWN ON THE AIR CONDITIONING DRAWINGS OR SPECIFICATIONS IF AIR CONDITIONING DRAWINGS REFER TO MANUFACTURERS WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY WITH SAID MANUFACTURER ALL REQUIREMENTS AND INCLUDE ALL RELATED WORK IN HIS CONTRACT. 16. ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS, 1T. RISERS ARE DIAGRAMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR THE INSTALLATION. 111 THESE DRAWING ARE A GUIDE FOR THE INSTALLATION OF ELECTRICAL SERVICE THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM la ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT AS OTHERWISE INDICATED. 20: ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES 21 EXACT POINT AND METHODS OF CONNECTIONS TO EQUIPMENTS SHALL BE DETERMINED IN FIELD. 22 ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER 23. COORDINATE LOCATION OF ALL DISCONNECT SWITCHES WITH OTHER TRADES TO ALLOW NEC. REQUIREMENTS CLEARANCES. 24, COORDINATE LOCATION OF AIR CONDITIONER DISCONNECT SWITCH WITH A/C CONTRACTOR TO KEEP NEC. CLEARANCE AS REQUIRED. TELEPHONE NOTES 1- ELECTRICAL CONTRACTOR SHALL TERMINATE ALL TELEPHONE CONDUITS AS REQUIRED AND AS RECOMMENDED BY BELL SOUTH TELEPHONE COMPANY, 2- TELEPHONE CABINET SIZES SHALL BE AS REQUIRED BY BELL SOUTH TELEPHONE COMPANY. 3- SERVICE ENTRANCE CONDUITS SHALL NOT HAVE MORE THAN 2 -90 DEGREES BENDS 4- WHEN THE TOTAL CONDUIT RUN IS LONGER THAN 100 FEET OR CONTAINS MORE THAN 2 -90 DEGREES BENDS, OR CONTAINS A REVERSE BEND, PULL BOXES SHALL BE PROVIDED. IF PULL BOXES ARE NECESSARY, THEY SHALL BE INSTALLED IN ACCESSIBLE LOCATIONS 5- ALL WIRING WITHIN THE UNIT MAY BE DONE BY BELLSOUTH OR OTHER COMMUNICATIONS COMPANYY, 6- WIRING WITHIN THE UNIT MAY BE RUN BARE IN CEILING AND WALLS WHERE THERE IS NO CEILING SPACE OR SPACING WITHIN THE FURRING OF WALLS, WIRING IS TO RUN IN CONDUIT. 7- NO CONDUITS SHALL RUN THROUGH OTHER UNITS 8- BELLSOUTH AND /OR SELECTED COMMUNICATION COMPANY IS TO PROVIDE ALL NECESSARY APPARATUS FOR A COMPLETE FUNCTIONING SYSTEM, EXCEPT FOR TELEPHONE SETS 9- ALL CONDUCTORS TO BE CATEGORY S dS CAUTION NOTES 1- IN ORDER TO PREVENT SOUND TRANSMISSION AND THE SPREAD OF FIRE ALL BOXES MOUNTED ON FIRE RATED WALLS MUST BE STAGGERED AND BE WRAPPED WITH UL FIRE RATED MATERIAL EQUAL TO THE RATING OF WALL 2- ALL LOCATIONS OF OUTLETS WITHIN CABINETRY, MUST BE COORDINATED WITH CABINET AND APPLIANCE MANUFACTURES 3- LOCATION OF LIGHT FIXTURES SHALL BE DETERMINED FROM ARCHITECTURAL DRAWINGS AND AFTER FINAL VERIFICATION WITH ARCHITECT AND DECORATORS NOTES 1 ALL PENDANTS, RECESSED DOWNLIGHTS, & WALL WASHERS TO BE ON DIMMERS 2 TV HEIGHTS TO BE COORDINATED WITH INTERIOR ELEVATIONS 3. REFER TO ARCHITECTURAL DRAWINGS FOR LIGHTING LEGEND. II II ll BUI -IN l I CO LER Il t..l_..._..._ ... _... — _.__.__ ..... ...... _1_.� II II I II ,l O -9 II Ili I f I I'I B ALT -IN (T Il F EEZER (I O i\ o �I P -9 PREP. 0 P -19 t I I I I I ELECTRICAL LEGEND OA 'A" INDICATES FIXTURE TYPE REFER TO THE LIGHT FIXTURE SCHEDULE P -9 P-9 DATA OUTLET WALL MOUNTED 18" AFF UNO (STUB UP 3/4" CONDUIT INTO MEN's I I L - - - - -J Q Rolando Maquelra, PE TYP C CEILING SPACE) OR FLUSH FLOOR MOUNTED. m RECESSED OR SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE, SIZE AS PER Tel: 305.669.5595 CA #9088 PLAN CEILING nv DATE TELEPHONE OUTLET WALL MOUNTED AT 18" AFF UNO (STUB UP 3/4' CONDUIT = I 1 02 -20 -08 INTO CEILING SPACE) OR FLUSH FLOOR MOUNTED. • PENDANT MOUNTED FLUORESCENT LIGHT FIXTURE, SIZE AS PER PLAN: COMBINATION TELEPHONE / DATA OUTLET WALL MOUNTED AT 18" AFF UNO WALL MOUNTED FLUORESCENT LIGHT FIXTURE, SIZE AS PER PLAN a (STUB UP 3/4' CONDUIT INTO CEILING SPACE) OR FLUSH FLOOR MOUNTED. FLUORESCENT STRIP LIGHT FIXTURE, SIZE AS PER PLAN. Q a CABLE TV OUTLET WALL MOUNTED AT 18" AFF LINO (STUB UP 3/4' CONDUIT O SURFACE MOUNTED CEILING LIGHT FIXTURE Interior Plan for: CAVAS WINE CAFE SOUTH MIAMI MUNICIPAL GARAGE INTO CEILING SPACE) OR FLUSH FLOOR MOUNTED. South Mlaml, Florida 33143 DRAWING O SPEAKER O RECESSED MOUNTED CEILING LIGHT FIXTURE 114 " =1 a -0" DRAWN YC REVIEWED RM PROJ. NO. •'�.t 123.0 tHEET ab: ►' i 4 aa. `mow SINGLE RECEPTACLE -120 VOLT, 1 PHASE, 3 WIRE, WALL MOUNTED AT 18' AFF I-0 WALL MOUNTED LIGHT FIXTURE MOUNTING HEIGHT AS INDICATED. Fq]) UNO OR FLUSH FLOOR MOUNTER O> RECESSED MOUNTED CEILING LIGHT FIXTURE (WALL WASH). DUPLEX RECEPTACLE - 120 VOLT,1 PHASE 3 WIRE WALL MOUNTED AT 18' AFF ® LINO OR FLUSH FLOOR MOUNTED. O PENDANT MOUNTED CEILING LIGHT FIXTURE QUAD RECEPTACLE -120 VOLT, 1 PHASE; 3 WIRE WALL MOUNTED AT 18" AFF UNO 0< TRACK LIGHT FIXTURE BUS AND LUMINAIRES OR FLUSH FLOOR MOUNTED. %.4P CEILING FAN (SUFFIX F/L DENOTES FAN & LIGHT), INSTALL SPECIAL SUPPORTED n DEDICATED CIRCUIT DUPLEX RECEPTACLE - 120 VOLT,1 PHASE, 3 WIRE WALL JUNCTION BOX x MOUNTED AT 18' AFF UNQ TWO HEADS EMERGENCY LIGHT FIXTURE WITH BATTERY BACK UP. m �" ISOLATED GROUND DUPLEX RECEPTACLE - 120 VOLT,1 PHASE 3 WIRE WALL MOUNTED AT 18' AFF UNO. 1TV COMBINATION TWO HEADS EMERGENCY / EXIT LIGHT FIXTURE WITH BATTERY BACK UP. GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE - 120 VOLT,1 PHASE 3 WIRE, 01 CEILING MOUNTED EXIT LIGHT, ARROW INDICATES DIRECTION OF EGREES WALL MOUNTED AT 18" AFF LINO. SINGLE RECEPTACLE - 240 VOLT, 1 PHASE 4 WIRE MOUNTED AT 18" AFF UNO. H81 WALL MOUNTED EXIT LIGHT, ARROW INDICATES DIRECTION OF EGREES = RECESSED MOUNTED ELECTRICAL PANEL Q CEILING MOUNTED JUNCTION BOX I-Q WALL MOUNTED JUNCTION BOX SURFACE MOUNTED ELECTRICAL PANEL SINGLE POLE TOGGLE SWITCH MOUNTED AT 48' AFF UNQ g ELECTRICAL SERVICE METER TWO POLE TOGGLE SWITCH MOUNTED AT 48' AFF UNO. 60 Q 3 SAFETY DISCONNECT SWITCH, CH, 3 = No OF POLES, 60 = SWITCH SIZE USED AS 2 NF PER MFG NAMEPLATE NF = NON FUSED. $3 THREE WAY POLE TOGGLE SWITCH MOUNTED AT 48' AFF UNO, CY ELECTRICAL MOTOR $p DIMMER SWITCH 600 WATTS MINIMUM MOUNTED AT 48" AFF UNO. ® CEILING OR ROOF MOUNTED EXHAUST FAA MANUAL MOTOR RATED STARTER TOGGLE SWITCH WITH THERMAL OVERLOADS MANUAL PULL STATION MOUNTED AT 48" AFF Q PUSH BUTTON MOUNTED AT 48' AFF UNQ. SL STROBE LIGHT MOUNTED AT 80" AFF, 75 ad UNO. OFA DENOTE EXISTING TO REMAIN �H COMBINATION HORN / STROBE MOUNTED AT 80' AFF, 75 cd UNO. (RL) DENOTE EXISTING TO BERELOCATED AS SHOWN O DUCT SMOKE DETECTOR GENERAL ELECTRICAL NOTES: I ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND OTHER APPLICABLE CODES AND STANDARDS 2 THE CONTRACTOR SHALL SATISFACTORILY REPAIR/REPLACE EQUIPMENT OR PART OF STRUCTURE DAMAGED AS A RESULT OF HIS WORK SURFACES AND FINISHED AREAS SHALL BE RESTORED TO MATCH ADJACENT AREAS 3. APPROVAL SHALL BE OBTAINED FROM THE ARCHITECT PRIOR TO CUTTING OR DRILLING ANY STRUCTURAL SUPPORT MEMBER 4, ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN/ NOTED OTHERWISE S INSTALL POWER AND CONTROL WIRING & REQUIRED CONTROL COMPONENTS FOR AIR CONDITIONING SYSTEMS AS SHOWN/ NOTED ON THESE DRAWINGS AND PER OTHER APPLICABLE DRAWINGS/ INSTRUCTIONS SEE AIR CONDITIONING DRAWINGS 6. MINIMUM WIRE SIZE SHALL BE #12 THHN/TT-(WN UNLESS OTHERWISE NOTED ON PLANS CONDUCTORS #6 AND LARGER SHALL BE THW. 7. ALL CONDUCTORS SHALL BE COPPER 8. ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALIC TYPE). IF PVC SCHEDULE 40 IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN ACCORDANCE WITH THE NEC 250 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED. 9. ALL MATERIALS SHALL BE UL APPROVED. 111 ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED. It CONTRACTOR SHALL SEAL ALL FIRE RATED PENETRATIONS WITH A FIRE SEALANT EQUAL TO THE RATINGS OF THE PENETRATION. V_ ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS U FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED 14 A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT SPECIFIED ON CONTRACT DRAWINGS CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE W/ A/C EQUIPMENT NAMEPLATE REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST. 15 CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS AS SHOWN ON THE AIR CONDITIONING DRAWINGS OR SPECIFICATIONS IF AIR CONDITIONING DRAWINGS REFER TO MANUFACTURERS WIRING DIAGRAMS, THE CONTRACTOR SHALL VERIFY WITH SAID MANUFACTURER ALL REQUIREMENTS AND INCLUDE ALL RELATED WORK IN HIS CONTRACT. 16. ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS, 1T. RISERS ARE DIAGRAMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR THE INSTALLATION. 111 THESE DRAWING ARE A GUIDE FOR THE INSTALLATION OF ELECTRICAL SERVICE THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM la ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT AS OTHERWISE INDICATED. 20: ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES 21 EXACT POINT AND METHODS OF CONNECTIONS TO EQUIPMENTS SHALL BE DETERMINED IN FIELD. 22 ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER 23. COORDINATE LOCATION OF ALL DISCONNECT SWITCHES WITH OTHER TRADES TO ALLOW NEC. REQUIREMENTS CLEARANCES. 24, COORDINATE LOCATION OF AIR CONDITIONER DISCONNECT SWITCH WITH A/C CONTRACTOR TO KEEP NEC. CLEARANCE AS REQUIRED. TELEPHONE NOTES 1- ELECTRICAL CONTRACTOR SHALL TERMINATE ALL TELEPHONE CONDUITS AS REQUIRED AND AS RECOMMENDED BY BELL SOUTH TELEPHONE COMPANY, 2- TELEPHONE CABINET SIZES SHALL BE AS REQUIRED BY BELL SOUTH TELEPHONE COMPANY. 3- SERVICE ENTRANCE CONDUITS SHALL NOT HAVE MORE THAN 2 -90 DEGREES BENDS 4- WHEN THE TOTAL CONDUIT RUN IS LONGER THAN 100 FEET OR CONTAINS MORE THAN 2 -90 DEGREES BENDS, OR CONTAINS A REVERSE BEND, PULL BOXES SHALL BE PROVIDED. IF PULL BOXES ARE NECESSARY, THEY SHALL BE INSTALLED IN ACCESSIBLE LOCATIONS 5- ALL WIRING WITHIN THE UNIT MAY BE DONE BY BELLSOUTH OR OTHER COMMUNICATIONS COMPANYY, 6- WIRING WITHIN THE UNIT MAY BE RUN BARE IN CEILING AND WALLS WHERE THERE IS NO CEILING SPACE OR SPACING WITHIN THE FURRING OF WALLS, WIRING IS TO RUN IN CONDUIT. 7- NO CONDUITS SHALL RUN THROUGH OTHER UNITS 8- BELLSOUTH AND /OR SELECTED COMMUNICATION COMPANY IS TO PROVIDE ALL NECESSARY APPARATUS FOR A COMPLETE FUNCTIONING SYSTEM, EXCEPT FOR TELEPHONE SETS 9- ALL CONDUCTORS TO BE CATEGORY S dS CAUTION NOTES 1- IN ORDER TO PREVENT SOUND TRANSMISSION AND THE SPREAD OF FIRE ALL BOXES MOUNTED ON FIRE RATED WALLS MUST BE STAGGERED AND BE WRAPPED WITH UL FIRE RATED MATERIAL EQUAL TO THE RATING OF WALL 2- ALL LOCATIONS OF OUTLETS WITHIN CABINETRY, MUST BE COORDINATED WITH CABINET AND APPLIANCE MANUFACTURES 3- LOCATION OF LIGHT FIXTURES SHALL BE DETERMINED FROM ARCHITECTURAL DRAWINGS AND AFTER FINAL VERIFICATION WITH ARCHITECT AND DECORATORS NOTES 1 ALL PENDANTS, RECESSED DOWNLIGHTS, & WALL WASHERS TO BE ON DIMMERS 2 TV HEIGHTS TO BE COORDINATED WITH INTERIOR ELEVATIONS 3. REFER TO ARCHITECTURAL DRAWINGS FOR LIGHTING LEGEND. II II ll BUI -IN l I CO LER Il t..l_..._..._ ... _... — _.__.__ ..... ...... _1_.� II II I II ,l O -9 II Ili I f I I'I B ALT -IN (T Il F EEZER (I O i\ o �I P -9 PREP. 0 P -19 t I I I I I I 1 I I 1 ! I l.. —•___J L----J (D JAN. CLO. (F J� l LrA4 LA 0641-1 NA�DE� Pwv.'- F E -9 P ' JESTIBUL P -9 P -9 P-9 RESTROOM HTYP P -9 - P -9 P -9 10LOCUS ARCHITICCTURQ P-11 �� GN J mm_J I I �./ 1 i I t ! ! I I I I � 1 P -9 P-9 P -17 MEN's I I L - - - - -J P RESTROOM Rolando Maquelra, PE I 1 I I 1 ! I l.. —•___J L----J (D JAN. CLO. (F J� l LrA4 LA 0641-1 NA�DE� Pwv.'- F E -9 P ' JESTIBUL P -9 P -9 P-9 RESTROOM HTYP P -9 - P -9 P -9 10LOCUS ARCHITICCTURQ P-11 IWTIN6 I I P -9 P-9 P -17 MEN's I I L - - - - -J P RESTROOM Rolando Maquelra, PE TYP C ! i I i •I ! 1 I I I I ! I I I P -9 - P -9 7487 SW 50th terrace Miami, Florida 33155 fly- O P-17 I I ,I I I I I 1 P -21 P -9 I I• I �• I I I �• I I -, 1_N..__.1 r I I I I ! L_ I 1;1 c I�IO I I I I I I I I P-67 I J CbDfid MTD P -17 f I .COMIwu I• 1 L J P -17 I I I I I •I I 1 I 1 I t I I I I I I L_____I I I I I I I I f I • I I l I I L ---- J r• --I_. I I I � I I I I I I I I I I I I I R� WAfERN....•r" LM SAFETY F16A'TUM / ' �v OW AT TM OF PANCYc S� 6e /��• /n PROPOSED REFLECTED CEILING PLAN - LIGHTING SCALE: 114"=V-0" ! I I 1 ! I I LOUNIE AREA I • I I I I I I I I I I i I I I Pin 1 I ! I B I ! I I I P -17 CITY OF 13OUTH MIAMI BUILE ING DEPT. ELECTR CAL SECTION APPROVED BY DATE' S - 16 - Z .v Apt. NORTH x KEYNOTES 10LOCUS ARCHITICCTURQ P-11 IWTIN6 I I I I P -17 a I L ---- J I I L - - - - -J • Rolando Maquelra, PE 1\ AS ! i I i •I ! 1 I I I I ! I I I P00J 7487 SW 50th terrace Miami, Florida 33155 Tel: 305.669.5595 CA #9088 Fax: 305.669.5596 CEILING REVISIONISUBMISSION DATE mm i I I 1 02 -20 -08 r• --I_. I I I � I I I I I I I I I I I I I R� WAfERN....•r" LM SAFETY F16A'TUM / ' �v OW AT TM OF PANCYc S� 6e /��• /n PROPOSED REFLECTED CEILING PLAN - LIGHTING SCALE: 114"=V-0" ! I I 1 ! I I LOUNIE AREA I • I I I I I I I I I I i I I I Pin 1 I ! I B I ! I I I P -17 CITY OF 13OUTH MIAMI BUILE ING DEPT. ELECTR CAL SECTION APPROVED BY DATE' S - 16 - Z .v Apt. NORTH x KEYNOTES 10LOCUS ARCHITICCTURQ ! I I ! L__.__.1 500 South Dixie Highway, Suite 310 Coral Gables, Florida 33146 P -17 Fax (305) 740 -0520 License No. AA0002733 • Rolando Maquelra, PE 1\ AS ! i I i •I ! 1 I I I I ! I I I r• --I_. I I I � I I I I I I I I I I I I I R� WAfERN....•r" LM SAFETY F16A'TUM / ' �v OW AT TM OF PANCYc S� 6e /��• /n PROPOSED REFLECTED CEILING PLAN - LIGHTING SCALE: 114"=V-0" ! I I 1 ! I I LOUNIE AREA I • I I I I I I I I I I i I I I Pin 1 I ! I B I ! I I I P -17 CITY OF 13OUTH MIAMI BUILE ING DEPT. ELECTR CAL SECTION APPROVED BY DATE' S - 16 - Z .v Apt. NORTH x KEYNOTES 10LOCUS ARCHITICCTURQ I N C O R P O R A T E D 500 South Dixie Highway, Suite 310 Coral Gables, Florida 33146 Tel (305) 740 -0120 Fax (305) 740 -0520 License No. AA0002733 CONSULTANT(S) Rolando Maquelra, PE 1\ AS PE #55482 Maquelra Engineering Consultants, Inc. 7487 SW 50th terrace Miami, Florida 33155 Tel: 305.669.5595 CA #9088 Fax: 305.669.5596 NO. REVISIONISUBMISSION DATE PERMIT SET 02 -20 -08 PROJECT Interior Plan for: CAVAS WINE CAFE SOUTH MIAMI MUNICIPAL GARAGE 5829 SW 73rd Street, Units #7 -8 South Mlaml, Florida 33143 DRAWING Reflected Ceiling Plan SEAL SCALE Q' AAQ `���� .: �. 90 11 t' I' r tx 44 ' r > 7 2009; ; �R�OIOI1a1>Ai� ,'r / 114 " =1 a -0" DRAWN YC REVIEWED RM PROJ. NO. •'�.t 123.0 tHEET ab: ►' i 4 aa. `mow E -2