08-497-023SUPPORT FROM UNDERSIDE
PAIR AT
OF STRUCTURE.
PAIR AT
PAIR AT
ROUND SPIN IN BELL MOUTH
1 1/2" X 22 GA. GALV.
MOUNT IN SIDE OF DUCT
STEEL HANGER STRAP
UNLESS SPECIFICALLY
(5' O.C.)
SHOWN OTHERWISE.
FLEXIBLE DUCT
ADJUSTABLE CLAMP
WITH R/D = 1.0
16
MAXIMUM D/8 OFFSET
MAX. SAG 1/2- PER FOOT
ALLOWED IN LAST
BETWEEN SUPPORT POINTS
D INCHES TO DEVICE
ROD
WHERE D IS THE
ROD
STRAP
INTERNAL FLEX
STRAP
ROD
DIAMETER.
\
DUCT SEALER AT SPIN
COLLAR CONNECTION TO
MAIN.
SUPPLY DUCT SIZE
AS SHOWN ON PLANS
NECK SIZE TO TRAP
MATCH FLEX ADJUSTABLE CLAMP INSULATION SEE PLANS
DUCT SIZE OR SPECS FOR VALUE
INDICATED. DUCT SEALER
VOLUME DAMPER WITH LOCKING
INSULATE TOP PANEL OF LAY -IN QUADRANT AND 2" STANDOFF
DIFFUSER WHERE REQ'D. SEAL INSULATION
TO DIFFUSER -NOT TO T -BAR GRID.
CEILING ----' AIR DISTRIBUTION DEVICE, SEE `— CEILING ACCESS PANEL
(T -BAR SHOWN. SCHEDULE. (LAY -IN SHOWN, FOR DAMPER ACCESS IN
GYP -BOARD SIMILAR). SURFACE MOUNT SIMILAR). NO- ACCESSIBLE CEILINGS.
FLEXILE F D 1 NOIND
1. FLEXIBLE DUCTS SHALL BE ONE -PIECE AND SHALL NOT BE SPLICED TOGETHER.
2. EXTEND FLEXIBLE DUCT INSULATION TO DUCT /DIFFUSER PANEL INSULATION AND SEAL WITH MASTIC.
3. MINIMUM 1" WIDE 22 GALVANIZED STRAP HANGER WITH HEMMED EDGES PER SMACNA. FIGURE 3 -10
4. FLEXIBLE AIR DUCT SHALL BE FULLY EXTENDED AND NOT COMPRESSED WITH ELBOW RADIUS NOT
LESS THAN R/D = 1.0
5. PROVIDE NON METALLIC, INSULATED FLEXIBLE DUCT.
FLEXIBLE DUCT CONNECTION DETAIL
N.T.S.
1 "X16 GA. STRAPPING
WITH 1" RETURN BEND
ON BOTTOM AND SCREWED
TO SIDE OF DUCT.
NOTE:
SCREWS MAY BE
OMITTED IF HANGER LOOPS
STRAP HANGERS
CONC. SLAB
PSI JOIST.
60" MAX
HANGER
STRAPS -
SCREWS OR POWDER
ACTUATED FASTENERS.
UNLESS FOOT
OF STRAP
IS PLACED
DUCT UNDER A
I BOTTOM
REINFORCEMENT
SUSPENDED CEILING
(SEE ARCH. DRAWINGS)
TRAPEZE HANGERS CONC. SLAB
STRAP OR
A Mf'A r
SIZE BOLT(S)
FOR LOAD
SCREWS FASTENERS.
HANGER WIRE
12 GAUGE (MIN.)
DUCT
DUCT HANGER DETAIL
SHEET METAL CHANNEL
N.T.S.
TABLE 4 -1
RECTANGULAR DUCT HANGERS
MINIMUM SIZE
MAXIMUM
PAIR AT
PAIR AT
PAIR AT
PAIR AT
HALF OF
10 FT SPACING
8 FT SPACING
5 FT SPACING
4 FT SPACING
DUCT
12" THRU 24" 2 #14
WIRE /
1/4"
WIRE /
16
WIRE /
1/4- DIA. 1 1/2-
WIRE/
PERIMETER
STRAP
ROD
STRAP
ROD
STRAP
ROD
STRAP
ROD
P
F = 30"
2
1 "x22 GA
10 GA.
(.135 ")
1 x .
. GA
10 GA.
(.135 ")
1 "x22 CA.
12 GA.
(.106 ")
1 "x22 GA
12 GA.
(.106 ")
2 Q 72"
1 "x18 GA.
3/8"
1 "x20 GA.
1/4'
1 "x22 GA.
1/4"
1"x22 GA.
1/4"
2 = 96"
1 "x16 GA.
3/8"
1 "x18 GA.
3/8"
1"x20 GA.
3/8"
1 "x22 GA.
1/4"
F = 120"
1.5 "x16 GA.
1/2"
1 "x16 GA.
3/8"
1 "x18 GA.
3/8'
1"x20 GA.
1/4"
2
- 168"
1.5 "x16 GA.
1/2"
1.5"x16 GA.
1/2*
1"x1 6 GA.
1/2*
1"x18 GA.
3/8"
2
= 192"
-
1/2'
1.5"x16 GA.
1/2'
1 "x16 GA.
1/2*
1"x16 GA.
3/8"
2
2 - 193" UP
SPECIAL ANALYSIS REQUIRED
AS PER SMACNA TABLE 4 -1 & FIG. 4 -4
CLINCH EN
1/4" 0 GALV.
TO BRANCH DI
TYPICAL DETAIL OF A 900 DUCT TAP
WITH DAMPER BLADE N.T.S.
PROVIDE VIBRATION ISOLATORS
MASON MODEL PC30N OR EQUAL
ROOF
WALL
RETURN AIR PLENUM — RETURN AIR DUCT
PROVIDE 3/4" DRAIN CONNECTION
W/ REMOVABLE PLUG. 24 GA. MIN.
GALV. STEEL DRAIN PAN 1 -1/2"
DEEP MIN. ALL WELDED CONSTRUCTION.
BOWS SHALL HAVE
'ANES AS PER SMACNA.
TRUNK DUCT
18 GAGE GALV. SHEET
STEEL DAMPER BLADE,
FULL HEIGHT OF MAIN
DUCT. DOUBLE BEND
LEADING EDGE OF
DAMPER BLADE.
FLOW
D DUCTS
FIBROUS GLASS DUCT.
GLASS FABRIC AND
AND MASTIC (GFM)
CLOSURE OVER POCKECT LOCK
AND DUCT BOARD.
FAN COIL UNIT
SURFACE.
#10 X 1-1/4- SHEET METAL SCREWS
12" MAX. O.C. MIN. 2 PER SIDE.
�— 22 Go. SHEET METAL
POCKET LOCK 1 "X 1 "X 1 "
CONNECTION DETAIL
N.T.S.
NOTE. 1-1/2- PVC SCH. 40
I. S -0" CLEAR FROM FAN COIL UNIT MAINTENANCE. SLEEVE (TYP.)
REFRIGERANT
PIPES
DISCONNECTED SWITCH FAN COIL UNIT SECURED TO STRUCTURE
WITH 3/8" DIA GALV. THREADED RODS.
REFRIGERANT SCREEN GALV. STEEL 16
PIPES i SUPER STRUT -
HANGER RODS
DISCHARGE DUCT 8" MIN. PIPE
SUPPORT
3' IN ALL FOUR
SIDES
�— FIN. CEILING
AUXILIARY DRAIN PAN W/ FLOAT SWITCH,
FLOAT SWITCH TO STOP UNIT WHEN SWITCH OPENS.
CONDENSATE DRAIN LINE AND
TRAP REFER TO DWG.
HORIZONTAL FAN COIL UNIT MOUNTING DETAIL
N.T.S.
CONDENSING
UNIT
6" MIN. --�
REFER CONDENSING UNIT
TIE DOWN DETAIL
CONCRETE BASE W/ . '.
6 X 6 - 10/10 WWF
6" MIN.
REFRIGERANT SUCTION &
LIQUID LINES TO FCU.
POWER & CONTROL
CONNECTIONS
6" MIN.
6" MIN.
/..
\� / SUCTION LINE W/ 1/2"
ARMAFLEX INSULATION
& VAPOR BARRIER
NOTE: CONCRETE SCREWS SHALL BE RATED
FOR 500 LBS. MIN. PULL -OUT CAPACITY.
CONDENSING UNIT MOUNTING DETAIL
N.T.S.
EZ TRAP EZT- SERIES 200 -
CONNECT SWITCH TO SHUT
DOWN SYSTEM ON OVERFLOW
SECONDARY /OVERFLOW
DRAIN LINE
GALVANIZED SHEET
METAL COWL
FILL WITH FOAM
INSULATION (TYP.)
TYPICAL SUPPORT
BETWEEN FLOORS
AT 8' -0" 0/C
VERTICALLY
T1I1111�
12"
ROOF CURB
ROOFING —
REFRIGERANT PIPE
CHASE IN PARTITION
REFRIGERANT PIPING COWL DETAIL
N.T.S.
NOTE: GROUND MOUNTED UNITS, IS BASED ON
THE REQUIREMENTS OF THE FLORIDA
BUILDING CODE. TO COMPLY WITH THE
WIND RESISTANCE AND ANCHORING AS
SPECIFIED IN SECTIONS 301.13 AND 301.13.1
COND. UNIT TIE DOWN SCHEDULE
UNIT SIDES # SCREWS
PER SIDES
ANCHOR EMBEDMENT
DIA.
# CONCRETE
SCREWS BOLTS
STEEL
ANGLE
GAGE
12" 1 #14
3/16" DIA. 1 1/4"
1/4"
1 "X1 "X1"
18
12" THRU 24" 2 #14
1/4" DIA. 1 1/2"
1/4"
2 "X2 "X2"
16
24" THRU 36" 3 #14
1/4- DIA. 1 1/2-
1/4-
2*X2"X2"
16
36" OR 5 TONS 3 #12
1/4" DIA. 1 3/4"
1/4"
2"X2"X2*i
16
MAXIMUN WIND SPEED OF 150 MILES PER HOUR.
2 "X2 "X2" LONG 16 GAGE FABRICATED
STEEL ANGLE (G90) FASTENED TO THE
UNIT FRAME USING 2- #14 SCREWS
WITH GASKETED WASHERS. (REFER TABL
ISOLATOR PAD --� \-1/4- CONCRETE SCREWS BOLTS
& WASHERS, PENETRATE 1 1/2" MIN.
(BY MECHANICAL CONTRACTOR)
C.U. UNIT TIE DOWN DETAIL
N.T.S.
3/4'
—I-
3/4'
REMOVABLE SCREW-CAP
(TYPICAL FOR ALL AHU)
PERFORATED
VENT CAP
z
t UNION
COMPLIES WITH FBC -2001 MECH VOL SECTION 307.2
PIPES TO BE COMM, CPVC FLOWGUARD SCHED 40,
OR REGULAR PVC SCHED 40 W/FIREPROOF WRAPPING.
AHU COND. DRAIN LINE W f
AUX. OVERFLOW SWITCH
N.T.S
TURNING VANI
FOR SMACNA
STANDARDS.
TYPICAL 90— DEGREE
VANED ELBOW DETAIL.
N.T.S.
CITY OF SOUTH MIAMI
BUILDING DEPT.
MECHANICAL SECTION
STEEL BLADES W/
INTERLOCKING JOINTS
MOUNTING ANGLES.
FASTENED TO SLEEVE
NOTE: FIRE DAMPER TYPE WITH BLADES
OUT OF AIR STREAM.
VERTICAL FIRE DAMPER DETAIL
N.T.S.
MOUNT DAMPER AS PER U.L. STANDARDS
AND MANUFACTURER RECOMMENDATIONS.
DYNAMIC FIRE DAMPER
UL 5% RATED WITH
165F FUSIBLE LINK.
FIRE DAMPER
100% FREE AREA
DUCTWORK.
SEE PLAN FOR SIZES.
"S" SUP BREAKAWAY
JOINT, ALL AROUND,
BOTH SIDES,
6" MAX. ON
ALL SIDES.
K0(NOTES -
10LOcus
ARCHITUCrURs
INCOR/ORATID
CONSULTANT(S)
T T Consufting Engineers, Inc.
CA 26441
MECHANICAL - PLUMBING - ELECTRICAL
9520 S.W. 40 8T. BUTTE 207 - MIAMI FLORIDA 33155
OFFICE (305) 225$377 - FAX (305) 225 -8378
EMAIL 7FENGINEER8®BO I OL THNEt
NO. REVISION /SUBMISSION DATE
SPECIAL USE PLANNING12 -14 -07
BOARD REVIEW
PERMIT SET 02 -20 -08
PROJECT
Interior Plan for:
CAVAS WINE CAFE
SOUTH MIAMI MUNICIPAL GARAGE
5829 SW 73rd Street, Units #7-8
South Miami, Florida 33143
DRAWING
DETAILS
MECHANICAL
SEAL
SCALE
Nestor J. Cifuentes
114 " =1' -0"
PE # 29450
CC
1 . •
I�
Signature
Date ��� �$ ±'�� �
k I� • -
- 123.0 •••
SHEET NO. � j
AC -2