07-1406R-001DETECTION #2
! I DUCT
' x 8'
ANSUL R -102 F,S,S.
TWO 3.0 GAL. TANKS
s CT,
DETECTION #1 ANSUL R -102 F,S.S.
LOCATED ,INSIDE A -
FIRE CABINET LOCATED `
AT END OF HOOD o ��
DUCT, 11 12'
1 1 1 3 \ .
1 1 I
i 1
1 3
r� DUCTS x 8'
I �
y r� DUCTS x 8
.� ,(DI 1
i O
10' x 8'
I
1
I — I
s 1
ti
-p
KITCHEN H1111D EIRE SUPPRESSION SYSTEM
DETECTION #2
Y2" EMT TO
FUSIBLE LINK Ns" PIPE
DETECTORS TO NOZZLE
DETECTION #1
Y," EMT TO
FUSIBLE LINK a�8.� PIPE
DETECTORS
TO NOZZLE
Y2" EMT TO
ANSUL PULL
STATION
PIPE
TO NOZZLEI�
�5
3.0 !AGENT TANK
THE ANSUL R -102 FIRE SUPPRESSION SYSTEM IS
PROTECTING FOUR HOODS WITH FIVE 10GAtL, AGENT
TANKS,
THIS USING 48 FLOW POINTS OUT OF THE 55
jJ
NOZZLE PLACEMENT REQUIREMENTS
HAZARD MAXIMUM HAZARD NOZZLE NOZZLE NOZZLE TIP TOTAL NUMBER ITEM NOZZLE J
DIMENSIONS QTY. PART No. STAMPING— OF FLOW POINTS HEIGHT I
L'
r
FLOW No.
DUCT LENGTH — UNLIMITED 8 430912 1W 8 - - - - - --
PERIMETER-50in
DIAMETER -16 in
PLENUM LENGTH — 1 OFT. 6 419335 1 N 6 - - - - - --
O
RANGE LONGEST SIDE — 28in. 16 419333 1F 16 40 — 48 in.
AREA -336 in. O
GRIDDLE LONGEST SIDE — 36in. 2 419335 1N 2 35 — 40 in.
AREA -1080 In. O
FRYER MAXIMUM SIZE: 3 419339 230 6 27 — 47 in.
151in. X 14in. O
TILT BRAISING MAXIMUM SIZE: 3 419338 3N 9 21 — 34 in.
PAN 25—j" in. X 19—j" in.
(Fry pot side must not
exd 19— " x
cee 1�9 ice.
SALAMANDER DEEP — 16in. 1 419335 1N 1 - - - - - --
WIDTH — 29in. O
DISTRIBUTION PIPING REQUIREMENTS
DISTRIBUTION PIPING REQUIREMENTS — 3.OGAL. AGENT TANK (EA.)
REQUIREMENTS
SUPPLY /LINE
DUCT
BRANCH LINE
PLENUM
BRANCH LINE
APPLIANCE
BRANCH LINE
PIPING SIZE
3/8 i n.
3/8 in.
3/8 in.
3/8 in.
MAXIMUM LENGTH
40 ft.
8 ft.
4 ft.
12 ft.
MAXIMUM RISE
6 ft.
4 ft.
2 ft.
2 ft.
POSSIBLE FLOW POINTS, I MAXIMUM 900 9 4 4 6
J ELBOWS
PIPE
TO NOZZ
PIPE I
TO NOZZ
3.0 kGEN1 TANK
3.0 kGENT TAN
ANSUL R -102
DOUBLE TANK
3 0 AGENT TANK ENCLOSURE
ANSUL R -102
REGULATED ACTUATOR
AUTOMAN ASSEMBLY
ANSUL R -102
REGULATED RELEASE
AUTOMAN ASSEMBLY
3.0 AGENT TANK (MECHANICAL)
ANSUL R -102 TYPICAL INSTALLATION
REGULATED RELEASE
AUTOMAN ASSEMBLY ANSUL R -102 UL3OO
(MECHANICAL)
FIVE 3.OGAL AGENT TANKS
1.- ADDED 1 CYLINDER TO SYSTEM TO PROTECT
THE BRICK OVEN HOOD.
2.- SEPARATED DETECTION INTO TWO SYSTEMS.
3.- ADDED PROTECTION TO SALAMANDER. m
m
APPROVED Of
A11AR1I -DADS COUNTY EIRE DEPARTNIEN'r
BLDG. PERVIT FIRE ALARM
EIRE SUPPRESSION� WATEA MWN EXT., ,_ �
13 ATE. Z h O 4 7v. ` z
Lli
Li-
Triangle F, ire
Inc.
7720 N.W. 53rd Street, Miami,
MAXIMUM TEES 1 2 2 4
(305) 592-3011, Fax: (305)
MAXIMUM FLOW 11 4 2 4
CARRABBA'S
NUMBERS
5829 SW 73rd Street, Suite #102
GENERAL NOTE:
Miami, Florida 33143
1.- SYSTEM SHALL BE PROVIDED WITH A LOCAL INDICATOR/ALARM AND WITH A RELAY TO
SCALE AS SHOWN
SHUT DOWN SUPPLY FAN WHEN SYSTEM IS ACTIVATEDTURN ON EXHAUST FAN, AND SHUT OFF
DATE JULY 10, 2006
ALL ELECTRIC UNDER HOOD. (BY OTHERS)
2.- KITCHEN FIRE SUPPRESSION CYLINDER ASS'Y SHUT OFF GAS VALVE TO BE
SHEET
INSTALLED IN AN ACCESSIBLE PLACE BELOW CEILING.
ANSUL R -102 FIRE SUPPRESSION SYS,
3.- PIPE SHALL BE 3/8" SCHEDULE BLACK IRON. ,
4.- ONE EXTINGUISHER LISTED AND LABELED REQUIRED FOR CLASS "K" USE.
II-160b gYSfr--M TO 13�
EXTINGUISHER WILL BE LOCATED WITHIN 30FT. OF COOKING HOOD AS PER FLORIDA FIRE PREVENTION
INSTALLED IN ACCORDANCE
CODE,
wi (H N. F. P. A. — 96
5.- BALLOON TEST TO BE PERFORM TO ENSURE SYSTEM FUNCTIONS PROPERLY.
(NITROGEN WILL BE BLOWN THROUGH THE LINES TO VERIFY PIPING IS UNOBSTRUCTED)
6ANSTALLATION COMPLIES WITH NFPA 17A ANb NFPA 96.
7. -ONLY MANUFACTURES LISTED COMPONENTS USE FOR AND WITH THIS SYSTEM.
vSTEMTOGE
8.- IN AREA OF PENETRATION, CONDUIT AND PIPING WILL HAVE GREASE TIGHT FITTINGS.
INSTALLI.O IN ACCORDANCE
%1TM N. F. P. A.._1
A F`I;'= Ex'tr :GU1$H0 LISTED r: 1,A3ELUE0
FJA CLASS "K" USE, SHALL Br LOCATED AUTOMATIC GAS YAl.YS SHALL at
Vallilrl 30' FEET OF HAZARD. ACCESSIBLO5, NOT ABOVE CEltl"
GN UNDER EQUIPIAENT.
\r.� ter- � V � �
� V � �,- ..� � �f- •,i- �,� ��.�� � f. �___�
REVISION
NOTES
1.- ADDED 1 CYLINDER TO SYSTEM TO PROTECT
THE BRICK OVEN HOOD.
2.- SEPARATED DETECTION INTO TWO SYSTEMS.
3.- ADDED PROTECTION TO SALAMANDER. m
m
APPROVED Of
A11AR1I -DADS COUNTY EIRE DEPARTNIEN'r
BLDG. PERVIT FIRE ALARM
EIRE SUPPRESSION� WATEA MWN EXT., ,_ �
13 ATE. Z h O 4 7v. ` z
Lli
Li-
Triangle F, ire
Inc.
7720 N.W. 53rd Street, Miami,
FL 33166
(305) 592-3011, Fax: (305)
592 -5254
CARRABBA'S
5829 SW 73rd Street, Suite #102
Miami, Florida 33143
SCALE AS SHOWN
DRAWN ORLANDO ALFONSO
DATE JULY 10, 2006
REVISED 12/11/2007
KITCHEN HOOD FIRE SUPPRESSION SYS.
SHEET
ANSUL R -102 FIRE SUPPRESSION SYS,
WITH FIVE 3.10GAL. AGENT TANK.
1
OF 3
SHEETS