07-1406-00212" X 24" FILTER SECTI ❑N
A FUSIBLE LINK DETECTOR
1/2N
(D
1/2N
PLENUM
0
• ••••! •rr
•� i i •
• Y
1/2N
(D
1/2N
BRANCH LINE
o
Y • •
Y • •• i• G
4 i••• { •
3 GAL, AGENT TANK
LOCATED ❑PP ❑SITE TO ACCESS DOOR
12" X 24" FILTER SECTION
r- IT ^ r- _T FILTER SECTI ❑N
FUSIBLE LINK DETECTOR
INLET PLENUM:
45x14 UP THRU
FLOOR
CHAINLINK FENCE
AROUND GREASE
EXHAUST UNIT BY
GENERAL CONTRACTOR
TRANSITION: FLAT ON
BOTTOM AND,
ECCENTRIC ON OTHER
THREE SIDES
'`1" L 48x48
3?r30 4Sx4S
GREASE EXHAUST UNIT LOCATIONS
SCALE: 1/4"=l'-O"
THE ANSUL R -102 FIRE SUPPRESSION SYSTEM IS
PROTECTING WITH ONE 3,OGAL, AGENT TANK,
THIS SYSTEM IS USING 4 FLOW POINTS OUT OF THE
11 POSSIBLE FLOW POINTS,
�b a b
Lj
om a o
o � F_
•
SECOND FLOOR EQUIPMENT KEY PLAN
N SCALE: 1/32"=l'—O"
PRECIPITATOR
DISTRIBUTION PIPING REQUIREMENTS
DISTRIBUTION PIPING REQUIREMENTS — 3.OGAL. AGENT TANK (EA.)
REQUIREMENTS SUPPLY /LINE
DUCT
PLENUM
•{Y• r•i •
• Y W Y•
• i { Y • •
• ••••! •rr
•� i i •
• Y
BRANCH LINE
BRANCH LINE
BRANCH LINE
• r i r
i•i ••i • Y
Y • •
Y • •• i• G
4 i••• { •
PIPING SIZE 38 in.
�8 in.
38 in.
38 in.
5829 SW 73rd Street, Suite #102
r r • s
V • i
G a G
000 0
i r•• •
• • Y •
• • • •
MAXIMUM LENGTH 40 ft.
8 ft.
4 ft.
12 ft.
NOZZLE
PLACEMENT
REQUIREMENTS
:iiiu • 0:9.0 •
i!!i• i :a•i• •
HAZARD
MAXIMUM HAZARD
NOZZLE NOZZLE NOZZLE TIP
TOTAL NUMBER ITEM
NOZZLE
of 3 SHEETS
DIMENSIONS
QTY. PART No. STAMPING—
OF FLOW POINTS
HEIGHT
FLOW No.
ELECTROSTATIC
INDIVIDUAL CELL
8 419334 Y2 N
4
T
— — — — — — —
PRECIPITATOR
DISTRIBUTION PIPING REQUIREMENTS
DISTRIBUTION PIPING REQUIREMENTS — 3.OGAL. AGENT TANK (EA.)
REQUIREMENTS SUPPLY /LINE
DUCT
PLENUM
APPLIANCE
7720 N.W. 53rd
BRANCH LINE
BRANCH LINE
BRANCH LINE
Fax: (305) 592 --5254
PIPING SIZE 38 in.
�8 in.
38 in.
38 in.
5829 SW 73rd Street, Suite #102
Miami, Florida, 33143
SCALE AS SHOWN
MAXIMUM LENGTH 40 ft.
8 ft.
4 ft.
12 ft.
MAXIMUM RISE 6 ft. 4 ft. 2 ft. 2 ft.
MAXIMUM 90' 9 4 4 6
ELBOWS
MAXIMUM TEES 1 2 2 4
MAXIMUM FLOW 11 4 2 4
NUMBERS
GENERAL NOTE:
1.- SYSTEM SHALL BE PROVIDED WITH A LOCAL INDICATOR /ALARM AND WITH A RELAY TO
SHUT DOWN SUPPLY FAN WHEN SYSTEM IS ACTIVATED TURN ON EXHAUST FAN, AND SHUT OFF
ALL ELECTRIC UNDER HOOD. (BY OTHERS)
2.- PIPE SHALL BE 3/:3" SCHEDULE BLACK IRON.
3.- BALLOON TEST TO BE PERFORM TO ENSURE SYSTEM FUNCTIONS PROPERLY.
(NITROGEN WILL BE BLOWN THROUGH THE LINES TO VERIFY PIPING IS UNOBSTRUCTED)
4.- INSTALLATION COMPLIES WITH NFPA 17A AND NFPA 96.
5.- ONLY MANUFACTURES LISTED COMPONENTS USE FOR AND WITH THIS SYSTEM.
6.- IN AREA OF- PENETRATION,. CONDUIT AND PIPING WILL.HAVE GREASE TIGHT FITTINGS.
7.- THERE IS NO GAS ASSOCIATED WITH THIS UNIT.
8.- THIS IS AN EXHAUST UNIT THAT DOES NOT HAVE A FRYER AND THEREFORE SHOULD
NOT REQUIRE A K -TYPE FIRE EXTINGUISHER. I.
4
TO
Y2" EMT TO
52ff—SYSTEM TO G4
rw'STA,LLED ItI ACC�1 L
NCf r
;
zITH tl.F.P.A.
ANSUL R -102
REGULATED AUTOMAN
RELEASE ASSEMBLY
TYPICAL INSTALLATION
ONE 3,06AL. AGENT TANK
bi
w
M
t�
U
w
w
/
Tri..angle
Fire,
7720 N.W. 53rd
Street, Miami, FL 33166
(305) 592-3011,
Fax: (305) 592 --5254
CAR RAB BA' S
5829 SW 73rd Street, Suite #102
Miami, Florida, 33143
SCALE AS SHOWN
DRAWN
BEVY NAJARRO
DATE JULY 10, 2006
REVISED
NOVEMBER 14, 2007
ANSUL R -102 SYSTEM
SHEET
2
ONE 3.0 GAL AGENT
TANK
of 3 SHEETS