07-1401-005FLEX DUCT
AIR FL
T,4.
PROVIDE VOLUME CONTROL
DAMPER 0 FLEX DUCT
CONNECTION ON LAYIN
CT
AIR FLOW
DIFFUSER. (TYPICAL)
BRANCH 'FAKE -OFF DETAIL
NO SCALE
UNIT UPLIFT CALLS
ACCU -1
F ACCU -1
—===4> � n I cv
W-4650 tc'
SIDE AREA OF UNIT : 24'x(32' +18') - 83 SOFT.
144'
VELOCITY PRESSURE:
ASCE -1 140 MPH Hs 22' -0'
MWFRS
Ial
C140.00256)1085) lU 1140)? C1)
Cj -42b PSF,
P- (0.8+0.5)X4210 P6F (WINDWARD+ LEEWARD)
P =5538 PSF.
F -(83 OF x5538 PSF) ■459 .60
Mo =459.60 x 2.1'= 96510 -1
T- C- 96520-1 /2'- 482.60
UPL IFT ON TOP- 24'x24' ,x ( -0.9) x 42.6 - -15630
144
NET UPLIFT - 15630 -1330= 2330
MIN. ANCHOR 0 EA CORNER = 2 ! +_4$2k"- 126,5* 0
4 4
DOWN LOAD a EA CORNER- I"_ +_4jN_rk - 214.6. 4
4 2
EQUIPMENT TIE-120K
• DOWNWARD SUPPORT a EA CORNER= 214100
UPWARD SUPPORT a EA CORNER ■ 126.50
-2010 SCREWS TO STRAP * EA CORNER - 400 0 IS OK
-1/410 TAPCON = 2500 is EA COMER IS ALSO OK
)mss.
"CAL Z -Ali
HANG DUCTS ACCOWM
AND LURE DUCT
TO SHACNA STANDARDS L
HANGQ14 DETAIL
STATIC
PRES.
CONDENSING
TYPICAL. HAN4RJG
STRAW AND SADDLE
tYPiCAI. CHANNi:I.
AND STRAP DUG?
HANGM DETAIL
NANOWs DETAIL.
ALL STRAPS TO 13E 14#2',26 GA. GALV. STEEL W -0' 0jM MAX. SPACM4
METHODS
OF HANT,ING
DUCTS
DETAIL
A/ C UNIT
2' MIN. AROUND
PERIMETER, TYP.
1'x12' 16 GA MTL
_ STRAP. ONE AT
EVERY CORNIER
2 -812 SHEET
MTL SCREWS
PER STRAP
I/4' TAPCON
THK CONC. PAD,
GRADE
9 , a a
W.4'
4. a a a ....�+...�...�.�.
a
C OND . PAD DETAIL
NOT TO SCALE
NOTE, SMOKE (DUCT) DETECTOR TO BE CONNECTED TO BUILDING
FIRE ALARM PANRL / SYSTEM
SYMBOL/LEGEND:
CEILING
RETURN AIR GRILL
- j SIB WALL DIFUSSER
AIR FLOW
SIZE (24x24) MULTIDIRECTIONAL
AIR FLOW (200 CFM) CEILING DIFFUSER (TYP -)
,,......., SUPPLY
��► • MAX. LENGTH 14'
�.�� FLEX DUCT
'''•....•'' 400
RETUR
\ MAX. LLEN GTH 14'
FLEX DUCT
44
SIZE CIRCULAR AIR DIFFUSER
AIR FLOW
----- ROUND SHEET METAL DUCT
IN AIR CONDITIONED SPACE
SUPPLY AIR DUCT
18 X 14
12x14 8x14
SUPPLY AIR DUCT
NOTE. ALL SUPPLY DUCTS TO HAVE
R -6 INSULATION VALUE
4 EXHAUST FAN
O THERMOSTAT a 48' AFF
W /SHUT OFF t SET BACK
SD SMOKE DETECTOR
MANUAL VOLUMEN DAMPER
FLOOR SLAB
d. d
n
tOTHREADED RED-
HEAD FASTENER
HDI 1/4' No 00045752
- FLUSH ANCHOR BY HILTI
ALLOWABLE WORKING LOADS
CONCRETE
570 LB 2 TENSION
OTHREADED COUPLING
03 THREADED ROD
UNDER SLAB
AHU
D -I SUPPORT
NO SCALE PP -HANG1
POWER ACTUATED PIN �- CONCRETE PECK
1' WIDE 26 GA STRAP
FLEX- DUCT
FLEXIBLE DUCT CONNECTION DETAIL
FNAC NOTES:
1. HvAC SUBCONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS TOOLS AND EQUIPMENT
TO INSTALL A COMPLETE AND OPERATIVE A/C SYSTEM.
2• HvAC SUBCONTRACTOR TO PROVIDE ALL REQUIRED HVAC PERMITS
3. HvAC SUBCONTRACTOR SHALL PROVIDE ALL EQjIPMI =NT OF t HE CAPACITIES SHOWN ON
PLAN.
4. COMPLY WITH NFPA, FLORIDA BUILDING CODE, AND ALL APPLICABLE
CODE$.
5- OUTSIDE AIR DUCT SMALL BE GALVANIZED SHEET METAL, CONISTRUCTED AND INSTALLED
IN ACCORDANCE WITH ASHRAE AND SMACNA STANDARDS.
6. ALL AIR DEVICES SHALL BE ALUMINUM CONSTRUCTION.
1. HVAC SUBCONTRACTOR SHALL TEST AND BALANCE TO THE AIIR QUANTITIES SHOWN ON THE
PLAN.
8. HvAc SUBCONTRACTOR SMALL PROVIDE ALL CONTACTORS, R?ELA'S AND THERMOSTATS.
THE ELECTRICAL SUBCONTRACTOR SHALL PROVIDE ALL SWITOHES, DISCONNECTS AND
CONTROL WIRING. T14ERM06TATO SHALL BE AS RECOMMENDED BY EQUIPMENT MANUFACTURER
9- ALL SUPPLY t RETURN DUCTWORK SHALL BE CONSTRUCTED OIF 111/2' THICK STANDARD DUTY
FIBERIGLASS BOARD WITH REINFORCED FLAMEPROOF ALUMINUM FOIL FACED COVERING, R -6
MIN. INSULATION, ALL DUTY SIZES ARE CLEAR INSIDE DIMENSIONS. (SMACNA STANDARDS)
(UON)
FLEXIBLE DUCT RUN OUTS SHALL BE ROUND DUCTWORK REINoRCED WITH A WIRE HELIX AND
INSULATED WITH 1' THICK FIBERGLASS COVERED WITH A VAPOIR BARRIER OF ALUMINUM
METALIZED POLYESTER FILM LAMINATED TO GLASS MESH. wto NECTIONS TO DUCT MAINS
SHALL BE MADE WITH FITTING PROVIDED WITH TWIST RINGS, BUTtTERFLY DAMPERS, QUADRANT
OPERATORS AND INSULATION GUARDS.
10. THE HVAC SUBCONTRACTOR SHALL PROVIDE A WRITTEN GUARANTEE THAT SHALL WARRANT
ALL WORKMANSHIP AND MATERIALS FOR ONE (1) YEAR FROM THE DATE OF FINAL WORK
ACCEPTANCE BY OWNER ANY BREAKDOWN OCCURRING IN THE FIRST YEAR SHALL BE
REPAIRED AT NO EXPENSE TO THE OWNER THE COMPRESOR("3) SHALL HAVE AT FIVE (5)
YEAR WARRANTY.
11. ALL WORK OF THIS TRADE SMALL BE COORDINATE WITH ALL OTHER TRADES TO AVOID
INTERFERENCES THAT MAY DELAY PROGRESS OF WORK
12. FILTERS SHALL BE DISPOSABLE TYPE AND HAVE INITIAL SHARE WEIGHT AND RESISTANCE
OF 10% AND A CLEAN PRESSURE DROP OF 0.15. PROVIDE TWO SETS, ONE DURING
CONSTRUCTION AND OTHER FOR USE AFTER OCCUPANCY.
13. MVAc SUBCONTRACTOR SHALL INSTALL ALL NECESSARY OFFSETS, BENDS AND
TRANSITIONS REQUIRED TO PROVIDE A COMPLETE SYSTEM AT NO ADDITIONAL
COST TO THE OWNER
14. COORDINATE LOCATION OF CEILING DIFFUSERS, GRILLS t RE(I ISTERS IN THE
FIELD WITH LIGHTING AND ARCHITECTURAL ELEMENTS.
15, MOUNT ALL EQUIPMENT FOR WIND LOADS AND MOUNTING HEICtHTS AS REQUIRED
BY LOCAL CODES.
16. MECHANICAL CONTRACTOR SMALL COORDINATE W/ PLUMBINGI CONTRACTOR CONDENSATE
SYSTEM INSTALLATION ( TO BE PROVIDED t INSTALLED BY P'LUM131NG CONTRACTOR).
11. REFRIGERANT SUCTION PIPING t CONDENSATE DRAIN LINES SHALL BE INSULATED W/ 3/4'
FOAM PLASTIC PIPE INSULATION
18. MECH- SUBCONTRACTOR SHALL INSTALL CONDENSATE DRAIN ILINES/PI.IMPS AS SHOWN ON PLANS
IMPORTANT NOTE:
INSTALL A.H.U. AS TIGHT
AS POSSIBLE TO DRYWALL LID
d . d d . d CONCRETE SLAB ESTRUCTURAL ABOVE
WTTOM OF
GONG DECK q o d o
/ \
SMOKE DETECTOR FIRE LID D -I
IN UNITS EXEEDING TYP OF 4
2000 CFM
36 --- - - - - -- ------ - - - - --
- -
' MIN. - - - - - -- � -- - -- :
_ r
I II
I I i i i i VIBRATION ISOLATOR
SUPPLY i i I .HEATER A.H.U. I I I 3/8' ALL THREAD ROD
/ L-- AS SCHEDULE
C
FLEXIBLE CONNECTION,
TYP.
1 i RETURN
111
TYP OF 4
L 'FLOW SWITCH'
211/2' STL STRUT (UNIT TO SHUT DOWN, IF FULL) AN
INSULA D CONDENSATE W/ AUX. DRAIN LINE
DRAIN INE
BOTT. OF CEILING III I 1 11 I 111 1 1
SEE SCHEDULE
TILE SYSTEM
SUSPENDED CEILING
AHU MOUNTING DETAIL
SCALE
p
SPLIT
SYSTEM
AIR
CONDITIONING
SCHED L"E'z�= �✓
SYSTEM
STATIC
PRES.
CONDENSING
VOLT. /PH
RPM
SENSIBLE
MODEL
TOTAL
TOTAL
CLG. -TD.
HTR
02 5
ENT, COND.
REMAF
No.
MANUFAC,
QT80
UNIT
A.N.U.
NO
BTU
w�
BTU
CFM
WEIR
KW.
VOLT/PMASE
TW
V
b
►-�
�
H
c
11
A/C -1
CARRIER
3ARZO01 -5
40RM001 -06
54AOO
11,600
2,400
11.0
10
208/240/3 PH
D J
) 61
NOTESs THERMOSTAT , MUST BE PROGRAMMABLE
EXHAUST
FAN
SCHEDULE
FAN No.
TYPE
CFM
STATIC
PRES.
HP
VOLT. /PH
RPM
MANUFACT.
MODEL
REMARKS
EF -1,2
CLG. -TD.
50
02 5
4S WATTS
120/1
g50
NUTONE
QT80
l, 2,
OUTSIDE
AIR CALCULATIONS
THE FOLLOWING OUTSIDE AIR QUANTITIES ARE CALCULATED IN ACCORDANCE WITH ASNRAE 62 -1WS
UNIT TAG
AREA SERVED
ROO
AREA
TOTAL
PEOPLE
CFM PER
PESON
CFM
O/A REQD.
AHU -1
OFFICE SPACE
250
7/1000 =2 PEOPLE
20 CFM
35
REDUCING SALONS
811
2011000 -l8 PEOPLE
15 CFM
262
NO
291 TOTAL CFM
HVAC DESIGN REQUIRES
YES
NO
DUCT SMOKE DETECTOR
YES
FIRE DAMPERS
NO
SMOKE DAMPERS
NO
FIRE RATED ENCLOSURE
»
z
NO
FIRE RATED ROOF / FLOOR CEILING ASSEMBLY
NO
FIRE STOPPING
NO
SMOKE CONTROL
�
NO
NEW CONNECT
EA. TO EXISTING
12' x 12' WALL
LOUVER I
1
4' MTL
6' * MTL
COMPRESSOR UNIT
0 2ND FLOOR
GARAGE LEVEL l
AREA DESIGNED
FOR THIS USE ON
'SHELL' PERMIT
_0_1}
H-0
d
CONNECT TO
EXISTING 3' m
C0ND
c,ITY car- SOU ftl MIAMI
BUILDING WEP r-
I M FlC,IIANICAL S8CI10N
/ �FPROVEo BY: �_� - - - - -� -
7
CATE: - - -- ---- - - - - -- __ _.
MECHANICAL PLAN &,µE ,, . m j,
GUTIERRE7
& LOZANO
ARCHITECTS
2830 W. STATE ROAD 84, SUITE117
FT. LAUDERDALE, FL. 33312
PHONE: (954) 321-3442
FAX: (954) 321-3864
REVISIONS
MA'1o'E.L GUTIERRg7,
STAT OF FLA., RE& ; No. 8253.
E'
CARLOS LOZANO' D
STATE OF FLA.,-'REG. No. 0014722
,
SHEET TITLE :
MECHANICAL PLAN
JOB No.:
DATE: 10/17/07
SHEET
M -1
OF
Draw. ADRIANA C. Fltne6sll DU
»
z
N�
W
^
W
�
W
w�
E__4
f:
TW
V
b
►-�
�
H
c
O
�
�
z
H
�Z^I
E-+ 00
4 U7
cn
SHEET TITLE :
MECHANICAL PLAN
JOB No.:
DATE: 10/17/07
SHEET
M -1
OF
Draw. ADRIANA C. Fltne6sll DU