13-441-081L
System No. C -AJ -1226
F Rating -- 3 Hr
T Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM /Sq Ft
L Rating At 400 F — 4 CFMISq Ft
- A
� —�A
SECTION A -A
1. Floor or Wall Assembly — Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete.
Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 32 in.
2. Metallic Sleeve -- (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or
grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or
beyond both surfaces of wall.
2A. Sheet Metal Sleeve — (Optional) Max 6 in. diam, min 26 ga galy steel provided with a 26 ga galy steel
square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized
to be a min of 2 in, larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in.
below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor,
2B. Sheet Metal Sleeve — (Optional) - Max 12 in. diam, min 24 ga galy steel provided with a 24 ga galy steel
square flange spot welded to the sleeve at approx mid- height, or flush with bottom of sleeve in floors, and sized
to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in.
below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
3. Through - Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically
within the firestop system. The annular space between penetrant and periphery of opening shall be min 0 in.
(point contact) to max 1 -7 /8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly
supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be
used:
A. Steel Pipe — Nom 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. diarn (or smaller) cast or ductile iron pipe.
C. Copper Pipe — Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
D. Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Conduit — Nom 6 in. diam (or smaller) steel conduit.
F. Conduit — Nom 4 in. dia m (or smaller) steel electrical metallic tallic tubin (EMT).
4. Frres.n P S system shall consist of the followin
Y stem —The firesto P Y c n n s
9
A. Packing Material — Min 4 in. thickness of min 4 pcf mineral wool batt insulation fir
nl YP acked into opening
9
as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both
Surfaces o f wall or sleeve as required to accommodate the required thickness of fill material.
B. Fill Void or Cavil Material — Sealant —
t Min 1/4 in. thickness of fill material applied within the annulus
Y Pp ,
flush with lop srarface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous
contact locations between P enetrant and concrete or sleeve, a
min 1/4 in. diam bead of fill material shall be
'
applied at the concrete or sleeve/ pipe penetrant interface on the top surface. of floor and on both surfaces of
wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS -One Sealant
*Bearing the UL Classification Mark
�pS S I -jF
- - Reproduced by HILTI, Inc. Courtesy of ` O
Underwriters Laboratories Inc.
FIRESTOP SYSTEMS June 27, 2007
C �L u5
System No. W -L -1054
F Ratings -1 and 2 Hr (See Items 1 and 3)
T Rating - 0 Hr
L Rating At Ambient - Less Than 1 CFMISq Ft
L Rating At 400 F - 4 CFMISq Ft
SECTION A -A
1. Will Assembly -- The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of
the materials and in the manner specified in the individual U300 or U400 Series Will and Partition Designs
in the UL Fire Resistance Directory.
2. Through - Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or
eccentrically within the firestop system. The annular space shall be min 0 in. to max 2 -1/4 in. Pipe may
be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater
than 45 degrees from perpendicular, Pipe, conduit or tubing to be rigidly supported on bosh sides of wall
assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit.
D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe -- Nom 6 in. diam (or smaller) regular (or heavier) copper pipe.
3. Fill. Void or Cavity Material* -- Sealant -- Min 5/E in. thickness of fill material applied within the
annulus flush with both surfaces of wall. At the oin n
P
t or continuous contact locations between P i p e and
wall a min 1/2 in. diam bead of fill material shall be applied at the pipe wall interfac e on both
surfaces
of wall .
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTi INC -- FS -One Sealant
"Bearing the UL Classification Mark
® Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
FIRESTOP SYSTEMS December 4, 2002
S I Fj�o
u uL
C US
System No. C -AJ -5091
F Rating — 2 Hr
T Ratings — 0 and 1 Hr (See Items 2 and 4)
L Rating At Ambient -- 4 CFM /Sq Ft
L Rating At 400 F — Less Than 1 CFMISq Ft
M
L;�.. A 4
3 SECTION A -A
1. Floor or Wall Assembly — Min 4 -1/2 in. (114 mm) thick reinforced lightweight or normal weight (100 -150 pcf or
1600 -2400 kg /m') concrete. Wall may also be constructed of any UL Classified Concrete Blocks'. Max diam of
opening is 29 in. (737 mm)
See Concrete Blocks (CAZT) category in the Fire Resistance directory for narnes of manufacturers.
2. Metallic Sleeve -- (Optional) -- Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe
sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in.
(76 ntm) above floor or beyond both surfaces of wall. If the steel sleeve extends beyond the top surface of the
floor or both surfaces of the wall, the T Rating of the firestop system is 0 hr.
2A, heat Metal Sleeve -�-- O P
S M a e (Optional) -Max 6 in. (152 mm) diam, min 26 ga galy steel provided with a 26 ga galy
steel square flange spot welded to the sleeve at approximately mid - height, or flush with bottom of sleeve in
floors, and sized to be a min of 2 in. (51 mm) larger than the sleeve diam, The sleeve is to be cast in place flush
with bottom surface of fluor and may extend a max of 1 in. (25 mini) above the top surface of the floor.
2B. Sheet Metal Sleeve -- (Optional) - Max 12 in. (305 mm) diam,. mire 24 ga galy steel provided with a 24 ga
galv steel square flange spot welded to the sleeve at approximately mid- height, or flush with bottom of sleeve
in floors, and sized to be a min of 2 in. (51 rnrn) larger than the sleeve diam The sleeve is to be cast in place
flush with bottom surface of floor and may extend a max of 1 in. (25 mot) above the top surface of the floor.
3. Through Penetrants -- One metallic pipe or tubing to be installed either concentrically or eccentrically within
the err estop system. Pipe or tubing to be rigidly supported onbot hs tde
s of floor or wall asserilbly. The follo Inc
types and sizes of metallic pipes or tubing may be used:
YI P P 9 Y
A. Steel Pipe —Norn 12 in (305 root) diam tar smaller) Schedule 10 tar heavier) steel pipe.
B. Iron Pipe - Nom 12 in. (305 rnm) diarn (or smaller) cast or ductile iron pipe.
� —
., Copper Pipe Norn 6 in. (152 mot) diarn (or smaller) Regular {or heavier} cropper pipe.
a
D. Copper Tubing - -Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
j
4. i�; Covering -- fill' rr r r'
P C v r r Min 1 in 13 n n to max 2 in. 51 mm) thick hollow cylindrical beau density Win 3.5 pcf or 56 k /m lass fiber
P 9 ( ) ( ) Y Y Y( p kg /ml)
um t s jacketed on t h o ou ts id e with ar tall -s ery is e jack e t Longitudinal joints sealed with metal fasteners or factory-applied, self - sealing lap
tape Transverse joints secured with meta{ fasteners or with butt tape supplied with the product The annular space between the
insulated pipe and the edge of the periphery of the opening shall be min 1/2 in. (13 min) to max 12 in. (305 mm) When thickness of pipe
covering is less than 2 in. (51 mm), the T Rating for the firestop system is 0 hr.
See Pipe Equipment Covering -- Materials — (BRGU) category in the Building Materials Directury for narnes of manufacturers.
Any pipe covering material meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index
of 25 or less and a Smoke Develuped Index of 50 or less may be used
4A. Pipc Covering �-
(Not Shown) As an alternate to Item 4, max 2 in. (51 mm) thick cylindrical c.al .ruin silicate (min 14 pcf or 224
kg /m') unity sized to the outside diarn of the pipe or tube may be used. Pipe insulation secured with stainless steel bands or min 1E
AWG stainless steel were spaced max 12 in. (305 rnm) OC, The annular space shall be ruin 1/2 in. (13 rnrn) to max 12 in. (305 mm).
5. Firestop System --- The firestop system shall consist of the following:
A Packing Material -- Min 4 in (102 mm) thickness of min 4 pcf (64 kg /ml) mineral wool batt insulation firmly packed into opening as
a permanent form Packing material to be recessed from top surface of floor or from both surfaces of wall as required to
accornrnodate the requirud thickness of fill material
B Fill Void or Cavity Material' --- Sealant --- Min 1/2 in, (13 mm) thickness of fill material applied within the annulus, flush with top
surface of floor or with both surfaces of wall
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS -One Sealant
'Bu,,nng ifie UL Classification Mark
FIRESTOP SYS11 MS
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
July 18, 2011
U�V,S l,c- /moo
Classified by
Undcrwrrlers Laboratories, Inc
to UI- 1479 and CAN,U1-C -5115
U
Ui(
iF'FO�. I�r +J. 2JO1HV J U C. r;, 924
♦ U V v J yy C v
U♦ i ♦ V -f. - C 4 4
IOUiS J. AGUIRRE & ASSOCIATES P.A.
GGNSUL 71N- y �N NG1 EERS
`910 S&Ulll vOAOR,, ND BLVD) . SUIT[ 900
V101, , FLORIDA V 53156
IELEPHONF: (305) 670 -0141
TU 'U A X: U i 0a ) e V 1 0 l 44
ww;v.ljonpa;:_om
Y�+4U
U
System No. W -L -5029
ANSI /UL 1479 (ASTM E8 14) CAN /ULC 5115
( ir 'o F Ratings -- 1 2 and 3 Hr See Items 1 3 and 4
F Ratings 1, 2 and 3 H (See Items 1, 3 and 4) R g ( )
T Ratings — 0, 1/2. 1 and 1 -1/4 Hr (See Item 3) FT Ratings — 0, 1/2, 1 and 1 -114 Hr (See Item 3)
- - - -- - - - -- -- -- ... - -
----------- _-__ _
L Rating At Ambient — 4 CFMISq Ft FH Ratings --- 1, 2 and 3 Hr (See Items 1, 2 and 4)
L Rating At 400 F - Less Than 1 CFM /Sq Ft FTH Ratings — 0, 112, 1 and 1 -114 Hr (See Item 3)
L Rating At Ambient — 4 CFM /Sq Ft
-L Rating At 400 F — Less Than 1 CFM /Sq Ft
■--A
L_a
t
SECTION A -A
1, Wall Assembly — The 1, 2 or 3 hr firer- rated gypv�uin board;stUd wall assembly shall be constructed of the
materials and in the manner specified in the individual U300, U400, V400 or W400 Series Wall and Partition
Designs in the UL Fire Resistance Directory and shall include the following constructi6Aeatures:
A. Studs -- Wall frarning may consist of eithei wood studs or steel channel studs. Wood studs to consist of
nom 2 by 4 in. (51 by 102 mrn) lumber spaced 16 in (406 film) OC. Steel studs to be min 2 -1/2 in (64 noel)
wide for 1 and 2 hr F and FH rating and 3 -1/2 fit. (89 mot) wide for 3 hr F and FH rating and spaced max 24
in. (610 mrn) OC.
B. Gypsum Board* — Min 5/8 in (16 nom) thick vvith square or tapered edges. The gypsum board type, r
thickness, number of layers, fasten, ?r type, art(] sheet orientation shall be as specified in the individual Wall
and Partition Design. Max diam of open infl is 18-5/8 in, (473 rrim),
The hourly F and FH Ratings of the: titustop system are equal to the hourly fire rating of the wall assembly fit
which it is installed.
2 Through Penetrants - -- One e metallic pipe or IlLjbillc j to be installed within the firestop system. Pipe or t ub t nU to
be rigidly supported on both sides of wall assembly The following types and sizes of metallic pipes or tubing
may be lased.
A. Steel Pipe Nom 12 nn. ( 305 i nto ) diam ( . t Schkdu , 10 (Or heavier) steel pipe.
B Iron Pipe -- Norn 12 in. ( 305 nfir) dram ( or smaller ) Cast or ductile iloll pipe.
5
C Copper Tuhinc -- iJom 6 in. 1eZ mrn diam c.I �rn�,ll��r Type L or heavier copper (.r lubirr . When the,
!F U ( YP ) {P g
A 7
haurl For FH Ratio of the ftresto system is 3 fir" the rrc,m dli.irrt of copper tube. shall not exceed 4 ire. 1l 2
Y g P Y Pf
mot).
D. Copper Pipe — Nom 6 in. (152 rnm) d an) tar !:onalle) Regular (or heavier) copper pipe. Whur'r'the hourly F
or FH luting of the firestop systurn is 3;1if, the mono -diam of cropper pipe: shall riot exceed 4 in. (102 mrn).
3. Pipe Covering' -- Norn 1, 1 -112 or 2 in (25, :38 or 51 rain) thick hollow cylindrical heavy density (min 3.5 pct or
56 kg/n3) glass fiber units jacketed ern the (-misido with an ,ill service jacket. Longitudinal joints sealed with
fit e t al tisle to r s or factory-applied seif- se.ili g lap tape 1 r/1ri. ;Verse t pints secured with metal fasteners or with
butt tape supplied with the product Fe,r 1 and 2 hr F and Ftl Ratings, thO ranl)rilar space between insulated
penetrant and periphery of opening shall be rain 0 in: (potnt (;ontact) to max 1 -718 in. (48 mm). For 3 hr F and
FH Ratings,, the annular space shall be min 0 in. (paint contact) to rnax 1 -1/4 in (32 film)
See Pipe and Eeluipincznt Covering - - -- Materials (BRGU) category in the Building Material Directory for the
names of manufacturers. Any pipe:; cov(:ring material meeting the above, specifications and bearing the UL
Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed Index of 50 or less'
may be used
The hourly T, FT, FTH Ratings of the firestop systern
are 1/2 hr lot- 1 hr rated walls and 1 hr for 2 tit rated walls
For 3 hr rated walls, the hourly T, FT and FTH Ratings whorl steel and non pipes are used are 'I hr For 3 fir
rated walls, the hourly T, F "f and FTH Ratings when copper lat:rie:trants aro u:,ed are 1 -1/4 Pr for 2 in (51 mm)
thick pipe covering and 0 hr for pipe covering thickness less than 2 in (51 nairr).
� � s�iCl Z.U',)
' a"
3A Pipe Covering" --- (Not Shown) -_. As all altuifi,.ctr: to Item 3, max 2 in. (51 m(n) thtcl<
�r� tc I;
silicate (Writ 14 pcf) units sized to the outside diarn of the pipe or tube:'ntay be used. Pi
e, insulation secetred
with stainless steel bands or min 18 AWG stainlei ;s steel were spaced mijx 12 ill (305
alternate pipe covering is used, the, T and FT Rating shall be as spc:cifiod in itein 3 abo
e.
See Pipe and Equipment Covering - Materials (13RGU) category in the Buildwy M,tter
ils Directory for natne,s
of manufacturers. Any pipe covering n)atorial meeting the above specificatio(ts and be.
ing th, UL. lift AVAW
)IT NO
Classification Marking with a Flatnu Spread Index of 25 or less and a Smoke Develnpe
II jwwAlp ,ill' IbInh
pl,
may be used.
4. Fill, Void or Cavity Material" - -- St:alarit '-- For 1 and 2 hr- F arid FH Dating, rain 5/8 in
16 mini) thickness of f
material applied within the annulus, flash with both surfaces of wall For 3 to f= and FH I
at ng�ri�2 nrrn)�
thickness of fill material applied within the annulus, flush with both surfi)Ces of wall. At t
e f , t � t ,ration
between pipe covering and gypsum board, a nun 112 in. (13 mm) diam bead of fill mate
it shalt be applied at
the pipe covering /gypsurn board intimate ()if butt) surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - -- FS -Oise; Sealant
*Bearing the UL Classification Mark
Reproduced by HILT I Inc. Courte:ay of
Underwriters Laboraturies Inc.
FIRFS10P SYSILMS May 30 2012
E, S l//^
fill 11
Cus
Ci,,�,_,1,(d by
Ur,d6ran4az1 ahor „torn:,, Inc,
to 01 1479 and CAN UL.0 -511,
E
Revisions:
Z `
Z
0
Z_\
Z_\
E—+
wa
O
°�
=z
�:D<
C7 ��
u
.1
O �►�
C
-0
+V
(�
it
'ts
t",ft f
►tea r.,,,,� • . * �►
r
(
„r ,
PERMIT SET
DRAWN: J -B.
CHECKED:
DATE: 04 -15 -2013
SCALE: A5 6HOU14
SEIA►1 w
}�►� _N
•�, fit? ,
a: <4 4
`MECHANIC4L' '
EDUAPDO A. SUAREZ, P.E. ti
LICENSE x 64759
Sheet NO.
/
P7.0i r.
JOB # 2 0130 1
... f