13-441-071r PLUMBING GENERAL NOTES 1. ALL WORK PERFORMED UNDER THIS CONTRACT SHALL COMPLY WITH THE FLORIDA BUILDING CODC 2010 AND ALL APPLICABLE STATE, COUNTY AND LOCAL ORDINANCES. 2. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE COMPLETE INSTALLATION OF THE PLUMBING SYSTEMS, ALL IN ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS. 3. THE CONTRACTOR IS RESPONSIBLE FOR VISITING THE SITE OF THE WORK AND BECOMING FAMILIAR WITH THE CONDITIONS OF THE WORK PRIOR TO SUBMITTING A BID. THE CONTRACTOR IS REQUIRED TO BECOME FAMILIAR WITH ALL THE CONTRACT DOCUMENTS PERTAINING TO THE PROPOSED WORK, THE SUBMISSION OF A BID SHALL BE SUFFICIENT TO ESTABLISH THAT THE CONTRACTOR HAS INVESTIGATED THE SITE OF THE WORK AND IS SATISFIED AS TO ALL REASONABLE CONDITIONS TO BE ENCOUNTERED, THE WORK TO BE PERFORMED AND THE MATERIALS TO BE PROVIDED IN THE COMPLETION OF THE PROJECT. 4. FAILURE OF BIDDERS TO MAKE REQUIRED VISITATIONS AND /OR INVESTIGATIONS TO INFORM THEMSELVES FULLY OF EXISTING CONDITIONS, AND TO INCLUDE IN THEIR PROPOSALS A SUM SUFFICIENT TO COVER ALL POSSIBLE FIELD CONDITIONS, WILL NOT IN ANY WAY ENTITLE THEM TO ANY EXTRA CHARGES OVER AND ABOVE THEIR ORIGINAL PROPOSALS. 5. IT IS THE INTENT OF THE PLANS AND GENERAL NOTES TO PROVIDE A COMPLETE AND OPERATING INSTALLATION INCLUDING ALL NECESSARY ITEMS REQUIRED, EVEN THOUGH ITEMS ARE NOT INDICATED ON THE DRAWINGS OR IN THE NOTES. ALL WORK CONSIDERED NECESSARY FOR THE COMPLETION OF THE WORK IN PROPER MANNER NOT SHOWN ON THE PLANS OR NOTES SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER IN WRITING PRIOR TO BIDS OTHERWISE WORK SHALL NOT BE ADDITIONALLY CHARGED AFTER BID IS AWARDED. 6. UPON COMPLETION, CONTRACTOR SHALL CLEAN ALL DUST AND DEBRIS IN AREAS WHERE WORK WAS CONDUCTED. 7. ALL WORK SHALL BE COORDINATED WITH ALL OTHER TRADES AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF EQUIPMENT. S. THE WORK THAT IS TO BE DONE UNDER THIS CONTRACT INCLUDES THE FURNISHING OF ALL LABOR, MATERIALS AND EQUIPMENT REQUIRED FOR THE COMPLETION OF THE SYSTEMS SHOWN ON DRAWINGS. 9. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC. THEY DO NOT SHOW EVERY BEND, OFFSET, ELBOW OR OTHER FITTINGS WHICH MAY BE REQUIRED FOR THE INSTALLATION IN THE SPACE ALLOCATED. 10. DRAWINGS ARE NOT TO BE SCALED, UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE ARCHITECTURAL AND /OR SITE CONDITIONS SHALL GOVERN EXACT LOCATION OF PIPING AND EQUIPMENT TO BE INSTALLED. 11. ALL MATERIALS AND EQUIPMENTS SHALL BE NEW AND OF GOOD QUALITY OF RESPECTIVE KIND AND GRADE AND MUST BE FURNISHED SO AS TO PREVENT ANY DELAY IN THE PROGRESS OF THE WORK, ALL WORK THROUGHOUT SHALL BE PERFORMED IN A WORKMANLIKE MANNER BY SUFFICIENT NUMBER OF SKILLED WORKMEN. 12. FOR EXACT LOCATION OF ALL PLUMBING FIXTURES, SEE ARCHITECTURAL DRAWINGS. DO NOT ROUGH -IN ANY PLUMBING FIXTURE AND /OR EQUIPMENT WITHOUT AN APPROVED COPY OF THE CORRESPONDING SHOP DRAWINGS. 13. FURNISH AND INSTALL CONNECTIONS TO EQUIPMENT PROVIDED BY THE OWNER UNDER THIS CONTRACT, COORDINATE INSTALLATION WITH MANUFACTURER'S RECOMMENDATION. 14. PLUMBING CONTRACTOR SHALL GURANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF ACCEPTANCES. 15. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL ROUGH INS WITH EQUIPMENT AND FIXTURES MANUFACTURER BEFORE MAKING ANY INSTALLATION. 16. ALL EXPOSED TRIM SHALL BE CHROME PLATED FINISH FOR ALL WATER SUPPLY AND WASTE ASSEMBLIES. 17. CONTRACTOR SHALL PROTECT AND FIRE SEAL ALL OPENINGS AND PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND CEILINGS WITH ADEQUATE FIRESTOPPING MATERIALS TO MAINTAIN THE INDICATED FIRE RATINGS OF THE ASSEMBLIES BEING PENETRATED. 18. PROVIDE CEILING / WALL ACCESS PANELS WHERE INDICATED IN THE DRAWINGS AND WHERE REQUIRED TO ACCESS PLUMBING EQUIPMENT. PANELS SHALL BE RECESSED TYPE, FIRE RATED IF IN FIRE RATED WALLS OR CEILINGS. LOCATIONS OF PANELS SHALL BE COORDINATED WITH ALL THE OTHER TRADES. PLUMBING DEMOLITION NOTES 1. SITE INVESTIGATION: THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH THE LOCATION OF ALL EXISTING UTILITIES STUB -OUTS, PIPING, EQUIPMENT, ETC., AND /OR ANY CONDITION THAT MAY AFFECT HIS WORK. ALL THE NECESSARY RE- ROUTING, RELOCATING AND /OR REMOVAL OF EXISTING PIPING, EQUIPMENT, ETC., SHALL BE INCLUDED IN THE SCOPE OF WORK. IGNORANCE ON THE PART OF THE CONTRACTOR WILL IN NO WAY RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITIES ASSUMED UNDER THIS CONTRACT. 2. THE NATURE OF THE REMODEL TYPE CONSTRUCTION POSES SPECIAL PROBLEMS FOR THE DESIGNER ENGINEERS AS WELL AS THE PLUMBING CONTRACTOR. EVERY EFFORT HAS BEEN MADE BY THE ENGINEERS TO SHOW AND VERIFY, WHERE POSSIBLE, THE LOCATION OF THE EXISTING PLUMBING SYSTEMS. THE MAJOR PORTION OF THE PLUMBING SYSTEMS ARE AS SHOWN ON THE DRAWINGS: HOWEVER MINOR DEVIATIONS MAY BECOME EVIDENT AS THE JOB PROGRESSES. NO ADVANTAGE IS TO BE TAKEN BY THE PLUMBING CONTRACTOR BECAUSE THESE MINOR DIFFERENCES. THE PLUMBING CONTRACTOR SHALL PERFORM A FIELD VERIFICATION BEFORE BIDDING THIS PROJECT. 3. CONTRACTOR WILL BE RESPONSIBLE FOR COORDINATING HIS DEMOLITION WORK WITH OTHER TRADES, AND TO PROTECT FROM DAMAGE EXISTING PIPES USED FOR FUTURE CONNECTIONS. 4. EXISTING PIPES SERVING AREAS REMAINING IN SERVICE AT THIS TIME SHALL NOT BE INTERRUPTED UNLESS A TEMPORARY INTERRUPTION IS COORDINATED WITH THE OWNER. 5. ALL SERVICE INTERRUPTIONS SHALL BE SCHEDULED WITH THE AUTHORIZED REPRESENTATIVE OF THE OWNER. ALL REMOVAL AND DISPOSAL WORK SHALL BE COORDINATED WITH THE AUTHORIZED REPRESENTATIVE OF THE OWNER. 6, CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PROTECT PROPERTY IN AREAS WHERE WORK IS BEING CONDUCTED. THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGES CAUSED TO BUILDING COMPONENTS DUE TO WORK OPERATIONS, PATCH AND REPAIR EXISTING SURFACES DAMAGED AS REQUIRED TO MATCH ADJACENT SURFACES. 7. THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR ALL EXISTING CONSTRUCTION, INCLUDING EXISTING TO REMAIN AND TO BE REMOVED. ITEMS AND DEBRIS TO BE REMOVED WILL BE PROPERLY DISPOSED OF BY THE CONTRACTOR, WITHIN HIS CONTRACT, AT NO COST TO THE OWNER. S. ANY UTILITY LINES TO REMAIN AND THAT ARE BROKEN OR DAMAGED DURING DEMOLITION OPERATIONS SHALL BE REPAIRED BY THE CONTRACTOR AT NO ADDITIONAL CHARGE TO THE CONTRACT PRICE, OR SHALL BE REPAIRED BY THE OWNER AT THE CONTRACTOR'S EXPENSE. 9, ANY DISCREPANCIES BETWEEN THE WORK DEPICTED ON THESE DOCUMENTS AND THE ACTUAL CONDITIONS ENCOUNTERED SHALL BE BROUGHT PROMPTLY TO THE ENGINEER FOR REVIEW AND CLARIFICATION. 10. ANY DAMAGED EQUIPMENT SHALL BE REPLACED OR RESTORED TO ORIGINAL CONDITION NOTE: THIS PROJECT WILL NOT INCLUDE OR REQUIRE ANY WET FILM PROCESSING ALL IMAGING WILL BE DIGITAL. PLUMBING SYMBOL LEGEND SYMBOL DESCRIPTION iafiaa�i/a EXISTING LINE TO BE REMOVED C TEMPORARY OR PERMANENT CAP 8" AND ABOVE SANITARY PIPE ------- - - - - -- VENT PIPE RWL RAIN WATER LEADER CD CONDENSATE DRAIN PIPE PT PRESSURE TEMP RELIEF PIPE - - DOMESTIC COLD WATER PIPE - -- - -- DOMESTIC HOT WATER PIPE - -- DOMESTIC HOT WATER RETURN PIPE PD PAN DRAIN PIPE DIRECTION OF FLOW COIF CLEANOUT WCO WALL CLEANOUT FLOOR CLEANOUT FLOOR DRAIN, AREA DRAIN OR ROOF DRAIN WITH FULL GRATE FLOOR DRAIN WITH TRAP RESEAL _11L VTR VENT THRU ROOF GATE VALVE L -1 VALVE IN VERTICAL 1 1/4" BALL VALVE 1/2" CHECK VALVE COUPLING OR UNION -- C� HOSE BIBB WATER HAMMER ARRESTOR POINT OF CONNECTION BETWEEN EXIST AND NEW DEMOLITION TERMINATION POINT ABV. ABOVE AFF ABOVE FINISHED FLOOR LEVEL BLW. BELOW CEIL., CLG. CEILING DN DOWN EXIST. EXISTING FA FROM ABOVE FB FROM BELOW VTR VENT THRU ROOF WS WASTE STACK DRAINAGE SLOPE PER FOOT SCHEDULE DIAMETER OF PIPE PITCH UP TO 2 1/2" MIN. 1/4" / FT 3" TO 6" MIN. 1 /8" / FT 8" AND ABOVE MIN. 1/16" / FT WATER HAMMER ARRESTER SCHEDULE MARK *P.D.I. SIZE CONN. SIZE A A (1 - 11 F.U.) 1/2" B B (12 - 32 F.U.) 3/4" C C (33 - 60 F.U.) 1'" D D (61 - 113 F.U.) 1" E E (114 - 154 F.U.) 1" F F (155 - 330 F.U.) 1" * PLUMBING AND DRAINAGE INSTITUTE STANDARD WH -201 PLUMBING SPECIFICATIONS HANGERS AND SUPPORTS A. PROVIDE ADJUSTABLE HANGERS, INSERTS, BRACKETS, ROLLS, TRAPEZE, CLAMPS AND SUPPLEMENTARY STEEL AS REQUIRED FOR PROPER SUPPORT OF PIPE LINES. B. HANGERS SHALL ALLOW FOR EXPANSION AND CONTRACTION OF PIPE LINES AND OF ADEQUATE SIZE TO PERMIT COVERING TO RUN CONTINUOUSLY THROUGH HANGERS. C. COORDINATE LOCATION OF HANGERS WITH OTHER TRADES. D. HANGERS SHALL BE PLACED WITHIN 18 INCHES OF HUB OR JOINT FOR HORIZONTAL CAST IRON PIPE. HUBLESS JOINTS MUST BE SUPPORTED AT EVERY OTHER JOINT EXCEPT THAT WHEN THE LENGTH BETWEEN SUPPORTS EXCEEDS FOUR FEET THEY SHALL BE PROVIDED AT EACH JOINT, E. HANGERS SHALL BE PLACED AT EACH CHANGE OF DIRECTION, WITHIN ONE FOOT OF VALVES AND OTHER APPURTENANCES INSTALLED IN HORIZONTAL PIPING AND NOT MORE THAN THREE FEET FROM END OF EACH BRANCH RUNOUT. F. HANGERS SHALL BE ADJUSTABLE CLEVIS TYPE WITH CONTINUOUS THREADED RODS. SANITARY WASTE AND VENT PIPING A. ALL HORIZONTAL BRANCHES, SEWER AND DRAIN LINES SHALL BE SLOPED A MINIMUM OF 1/8 INCH PER FOOT UNLESS OTHERWISE INDICATED ON PLANS. B. EVERY FIXTURE CONNECTED TO THE DRAINAGE SYSTEM SHALL BE EQUIPPED WITH A WATER SEAL TRAP. C. VENT STACKS SHALL NOT PASS THROUGH ROOF AT VALLEYS, ROOF CRICKETS, IN FRONT OF WINDOWS OR WITHIN 6' -0" OF ROOF EDGE, D. MATERIALS SHALL BE AS FOLLOWS: 1) DRAINAGE AND VENT PIPING (BELOW GRADE): a. SHALL BE HUB AND SPIGOT SERVICE WEIGHT CAST IRON WITH GASKETED PUSH -ON JOINTS. 2) DRAINAGE AND VENT PIPING (ABOVE GRADE): a. HUBLESS SERVICE WEIGHT CAST IRON WITH NEOPRENE GASKETS AND STAINLESS STEEL BAND JOINTS. b. LESS THEN 2" - COPPER DRAINAGE TUBE, TYPE DWV ASTM B306 WITH WROUGHT COPPER FITTINGS AND 95 -5 SOLDERED JOINTS. DOMESTIC COLD AND HOT WATER PIPING A. PROVIDE WATER HAMMER ARRESTERS SIZED AS INDICATED ON THE DRAWINGS. B. PROVIDE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED. C. ESCUTCHEONS SHALL BE CHROME PLATED BRASS WITH LOCKING SCREWS WHERE PIPES PASS THROUGH FINISHED WALLS. D. EACH HOSE BIBB SHALL BE FURNISHED WITH A VACUUM BREAKER AND SHUT -OFF VALVE, E. PROVIDE PIPING AS FOLLOWS: 1) WATER PIPING (BELOW GRADE): SHALL BE COPPER TYPE "K " ASTM B -88 WITH WROUGHT COPPER FITTINGS AND 95 -5 SOLDERED JOINTS. PAINT WITH BITUMASTIC WHEN INSTALLED IN GRADE. 2) WATER PIPING (ABOVE GRADE): a. COPPER TYPE "L " ASTM B-88 WITH WROUGHT COPPER FITTINGS AND 95 -5 SOLDERED JOINTS. COPPER TYPE "K" ASTM B -88 UNDER GROUND. 3) PRESSURE AND TEMPERATURE RELIEF LINES: SHALL BE TYPE "M" COPPER WITH WROUGHT COPPER FITTINGS AND 95 -5 SOLDERED JOINTS. F. ALL EXPOSED PIPING WITHIN TOILET ROOMS SHALL BE CHROME PLATED. VALVES A. PROVIDE CONTROL VALVES WHERE NOTED ON PLANS, AND AS REQUIRED FOR COMPLETE REGULATION OR CONTROL OF ALL SYSTEM MAINS, BRANCHES TO GROUP OF FIXTURES, AND TO EACH PIECE OF EQUIPMENT. B. PROVIDE ACCESS PANELS AS REQUIRED TO VALVES, OR GROUP OF VALVES, WHERE CONCEALED AND FOR PROPER MAINTENANCE AND OPERATION OF SYSTEM. C. GATE VALVES (WATER SERVICE): 1) 2 -1/2 INCHES AND SMALLER SHALL BE BRONZE BODY, SCREWED BONNET, NON - RISING STEM, SOLID WEDGE, CLASS 125, 200 PSI NON -SHOCK WATER; THREADED END WATTS WGV- SERIES, SOLDERED END WATTS WGVS - SERIES. TESTING A. COMPLETE WATER PIPING SYSTEM SHALL BE PRESSURE TESTED BY CAPPING OR PLUGGING OPENINGS, FILLING SYSTEM WITH WATER AND APPLYING HYDROSTATIC PRESSURE OF 200 PSI FOR PERIOD OF NOT LESS THAN 2 HOURS. B. SOIL, WASTE AND VENT PIPING SHALL BE TESTED BY CAPPING OR PLUGGING THE ENDS OF THE SYSTEM AND ALL LINES FILLED WITH WATER TO 10 FEET OF HEAD AND ALLOW TO STAND UNTIL INSPECTION IS MADE AND WATER LEVEL REMAINS CONSTANT FOR A PERIOD OF NOT LESS THAN 2 HOURS. INSULATION A. INSULATION SHALL RUN CONTINUOUS THROUGH WALLS, FLOORS AND CEILINGS. B. WHERE INSULATION PASSES THROUGH HANGERS IT SHALL BE PROVIDED WITH A PROTECTION SHIELD, 180 DEGREE ARC GALVANIZED SHEET METAL COVERING 12 INCHES LONG. C. ALL A/C CONDENSATE DRAIN LINES ABOVE GRADE SHALL BE INSULATED WITH 1/2" ARMAFLEX PIPE INSULATION. SEAL ALL SEAMS WITH INSULATION MANUFACTURER'S SOLVENT. NO TAPES ARE ALLOWED. D. GLASS CLOTH JACKET: FACTORY SIZED WHITE, STANDARD WEIGH F, WITH 1 -112 INCH MINIMUM LONGITUDINAL PRESSURE SEALING LAP, AND SEAL STRIPS FOR BUTT JOINTS. E. VAPOR BARRIER JACKET: FLAME RESISTANT GLASS FIBER ADHERED TO OUTSIDE OF A 1 -MIL ALUMINUM FOIL SHEET WITH LONGITUDINAL PRESSURE SEALING LAP AND SEAL STRIPS FOR BUTT JOINTS. END JOINT CEMENT PERM RATING NOT TO EXCEED .05. F. DOMESTIC HOT WATER SUPPLY AND RETURN PIPING UP TO 1 112" NOMINAL SIZE: 1/2 INCH THICK GLASS FIBER MOLDED INSULATION WITH PRE -SIZED FACTORY APPLIED FIRE RATED JACKET OF GLASS CLOTH WITH LONGITUDINAL LAP AND BUTT JOINT STRIPS WITH SELF - SEALING ADHESIVE. G. CONDENSATE DRAINING, DRINKING FOUNTAIN AND ELECTRIC WATER COOLER DRAINS: ELASTOMERIC (FOAM PLASTIC) THERMAL INSULATION 112 INCH THICK WITH BUILT -IN VAPOR BARRIER RATED SELF- EXTINGUISHING. INSULATION SHALL HAVE A MAXIMUM THERMAL CONDUCTIVITY OF 0.26K FACTOR AT 70 DEGREES F. MEAN TEMPERATURE, DENSITY OF 5 -6 POUNDS PER CUBIC FOOT AND A WATER VAPOR TRANSMISSION OF 0.1 PERMS. BID NOTE THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS OTHER THAN TO IDENTIFY MODIFICATIONS OR EXTENSIONS THERETO. VISIT THE SITE AND ASCERTAIN THE EXISTING CONDITIONS. REVIEW CONSTRUCTION DETAILS OF THE EXISTING PORTION OF THE BUILDING DURING THE SITE INSPECTION. INCLUDE ALL WORK REQUIRED TO REMOVE OR MODIFY PORTIONS OF THE EXISTING INSTALLATION IN ORDER TO ACCOMMODATE THE NEW WORK . FAILURE TO COMPLY WITH THIS WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF THE EXISTING INSTALLATION OR INSTALLING ANY NEW OR TEMPORARY WORK. COORDINATION NOTE AS PART OF THIS CONTRACT, THE SUB - CONTRACTOR AND THE CONTRACTOR ARE RESPONSIBLE FOR COORDINATION AND VERIFICATION THAT ALL EQUIPMENT, SHOWN IN THE ARCHITECTURAL DRAWINGS PARTICULARLY, BUT NOT LIMITED TO THE ARCHITECTURAL EQUIPMENT PLAN, INCLUDE ALL SERVICE /UTILITY REQUIRED TO OPERATE THE EQUIPMENT SHOWN. ANY DISCREPANCIES ARE TO BE POINTED OUT DURING THE BIDDING PROCESS. DISCREPANCIES NOT POINTED OUT DURING THE BIDDING PROCESS WILL BE RESOLVED BY THE CONTRACTOR AS PER THE ARCHITECT DETAILS AT NO ADDITIONAL COST TO THE OWNER. c•vc v•• • • ••••• uu• • �, • c• ry • • u OCCUPANCY GENERAL NOTES ` THE OCCUPANCY OF THIS PROJECT IS BUSINESS / DOCTORS" OFFICES. THIS PROJECT IS NOT REVIVABLE BY AHCA. THIS PROJECT DOES NOT FALL UNDER ANY REGULATIONS PERTAINING TO HOSPITAL, AMBULATORY SURGERY OR NURSING HOME. o _ Iry • 1111r.J No. y 301 � „ CA 924 V • WQUIS 10. A CUIRREI ASSOCIATES P.A. 0,0 N ULTI!�G 'ENGINEERS 915.) SOUTH DADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 IEFAf"'&1E: (;;ti5Y670 �141 "rY FAX: u (n5) 670 -( i44 v � v • 6 W G i.; W �'!J ctij.,,� [wr;.i7. (uJ f71 • o r` v w v u v CO C_-_ PLUMBING FIXTURE CONNECTION SCHEDULE MARK DESCRIPTION WASTE CW HW REMARKS A5 SHOLiJN KOHLER MODEL NO. K -4405 HIGHLINE: ELONGATED WC -1 WATER CLOSET -ADA 4" 1" - WATER SAVER 1.28 GALLONS PER FLUSH :17" HIGH (FLOOR MOUNTED) VITREOUS CHINA, WHITE: 10" ROUGH -IN. FLUSH VALVE: SLOAN ROYAL ( *) NO. 111 -1.28 TOILET SEAT CHURCH(`) MODEL NO. 9500C OPEN FRONT SEAT LESS COVER. L -1 LAVATORY -ADA 1 1/4" 112" 1/2" KOHLER ( *) MODEL NO. K -2005 "KINGSTON" (WALL HUNG) WHITE VITREOUS CHINA: TOP OF FRONT RIM MOUNTED AT 34" A.F.F. MAXIMUM FAUCET: CHICAGO ( *) MODEL NO. 895- 317FCCP GOOSENECK SPOUT WITH LAMINAR FLOW CONTROL 0.5 GPM (50- 046KJKNF) CAST BRASS, CHROME PLATED, ADA COMPLAINT. DRAIN: MCGUIRE NO. 8872 1 -114" TAILPIECE AND NO. 155A PERFORATED GRID CHROME FINISH. LAVATORY SUPPLY: MCGUIRE ( *) MODEL NO. H170LK, 3/8 " ANGLE VALVE WITH LOOSE KEY HANDLE, CHROME FINISH. PROVIDE -B (ASSE 1070) MIXING 1DUSG ETWATTS PIPEVUARp �S�F�: TRUEBO LAV SHIELD PROTECTIVE LAVATORY SHIELD( ") NO. #2018 -KO -K FIXTURE CARRIER: BY JOSAM # 17100 OR ACCEPTED EQUIV. SK -1 SINGLE COMP, SINK -ADA 1 1/2" 1/2" 112" ELKAY LUSTERTONE, ADA COMPLIANT MODEL (COUNTERTOP) NO. LRAD1919 WITH HEAVY DUTY SOUND GUARD UNDERCOATING, 6 -1/2 DEPTH, 3 HOLE 4" CENTERS FAUCET: CHICAGO ( *) MODEL NO. 786- GN2FCCP GOOSENECK SPOUT WITH LAMINAR FLOW CONTROL 1.5 GPM CAST BRASS, CHROME PLATED, ADA COMPLAINT. DRAIN: ELKAY ( *) MODEL NO. LK35B, CHROME FINISH 3 -1/2" INLET - 1 -1/2" OUTLET WITH CHICAGO ( ") MODEL NO. 8912, 1 -1i2" TAILPIECE. SINK SUPPLY: MCGUIRE ( *) MODEL NO. H171LK, 1/2" ANGLE VALVE WITH LOOSE KEY HANDLE, CHROME FINISH. PIPE GUARD: TRUEBO LAV GUARD ( *) NO. 102 E -Z SK -2 SINGLE COMP. SINK -ADA 1 112" 1/2" 112" ELKAY LUSTERTONE, ADA COMPLIANT MODEL (COUNTERTOP WITH EYEWASH) NO. LRAD1919 WITH HEAVY DUTY SOUND GUARD UNDERCOATING, 6 -1/2 DEPTH, 3 HOLE 4" CENTERS FAUCET: CHICAGO ( *) MODEL NO. 786- GN2FCCP GOOSENECK SPOUT WITH LAMINAR FLOW CONTROL 1.5 GPM CAST BRASS, CHROME PLATED, ADA COMPLAINT. EYEWASH CHICAGO MODEL 8004 -RHNF DECK MOUNTED RIGH HAND UNIT WITH PUSH PADDLE HANDLE. DRAIN. ELKAY ( *) MODEL NO. LK35B, CHROME FINISH 3 -1/2" INLET - 1 -1/2" OUTLET WITH CHICAGO ( *) MODEL NO. 8912,1-1/2" TAILPIECE. SINK SUPPLY: MCGUIRE ( *) MODEL NO. H171LK, 1/2" ANGLE VALVE WITH LOOSE KEY HANDLE, CHROME FINISH. PIPE GUARD: TRUEBO LAV GUARD ( *) NO. 102 E -Z MS -1 MOP SINK 3" 1/2 1/2 STERN WIL1IAh1 MODEL No.SBC- 1700 -BP -6" FRONT DROP, CORNER TYPE WITH STAINLESS STEEL CAP AND STAINLESS STEEL BACK PANELS, FAUCET: STERN WILLIAMS MODEL No. T -10 -VB P -TRAP: 3" P -TRAP GRID DRAIN: 3" STAINLESS STEEL STRAINER PLATE. MS -2 MOP SINK 3" 112 1/2 FIAT MODEL No. MSB 3624 MOLDED STONE MOP SERVICE SINK FAUCET: STERN WILLIAMS MODEL No. T- 10 -VB. P -TRAP: 3" P -TRAP. GRID DRAIN- 3" STAINLESS STEEL STRAINER PLATE. EWC -1 ELECTRIC WATER COOLER - ADA 1 1/4" 1/2" - ELKAY MODEL #1ERPBM28K, NO LEAD (BI LEVEL - RECESSED) TWO -LEVEL SWIRLFLO WALL MOUNT WATER COOLER BARRIER FREE ACCESS F= INISH: SATIN STAINLESS STEEL CHILLER LOCATED BEHIND LOW FOUNTAIN FDA FLOOR DRAIN W/ TRAP PRIMER 4" FLOOR DRAIN: JR SMITH ( *) NO. 2005 -NB, 6" ADJUSTABLE SQUARE TOP NICKEL BRONZE -- _ -� -� FINISH WITH 1 /2" TRAP PRIMER CONNECTION. WATER HEATER SCHEDULE WATER WATTAGE VOLTAGE EFFICIENCY MARK CAPACITY HEATING TEMP MANUFACTURER MODEL NO. REMARKS SOURCE COLD HOT (UPPER /LOWER) (V /PH /HZ) SETTING (EF RATING) EWH -1 40 GAL ELEC 3/4" 3/4" 3000/3000 208/3/60 140 DEG LOCHINVAR LSX040HH -SIM 0.92 GIELING HUNG UNIT ON HOLDRIT (SIMULTANEOUS) MODEL # 50SVVHP PLATFORM. NOTE: 1. ELECTRIC WATER HEATER MEETS AHSRAE 90.1 MANDATORY REQUIREMENTS 2. ALL HAND WASHING SINKS AND LAVATORIES HAVE BEEN SPECIFIED WITH A WAT-1 S USG -B (ASSE 1070) MIXING VALVE SET AT 110 DEC, Revisions: a a a a a E �M �0. V1 d I-+ ..1 ci t O � � 1 O to 0 z � h � L.rLI Z Z p Z GA LLJ V) P ERMT SET DRAWN: J.B. CHECKED: DATE: 04 -15 -2013 SCALE: A5 SHOLiJN SEAL. SO MECI iANICF,L; r EDUARDO A. SUAPEZ, F.F. LICENSE M 64759 Sheet No. I i" V.V V IJOB # 201301 I