13-441-055F VAV BOX CONTROL DIAGRAM 74 F T 5 SP � CL� QR 7 VAV COOLING ONLY SEQUENCE OF OPERATIONS: RUN CONDITIONS - S_CHEDULED:THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES: OCCUPIED MODE: THE UNIT SHALL MAINTAIN A74`F (ADJ.) COOLING SETPOINT • UNOCCUPIED MODE: THE UNIT SHALL CLOSE TO ITS MINIMUM POSITION ZONE SETPOINT ADJUST /OPTIMAL START /UNOCC_UPIE_D_OVERRIDE:THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE ZONE SENSOR.THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START -UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM -UP OR COOL -DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF SCHEDULED OCCUPIED PERIOD.A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE. FLOW CONTROL:DURING OCCUPIED MODE,THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF THE FOLLOWING: • WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL THE ZONE IS SATISFIED. • WHEN THE ZONE TEMPERATURE IS LESS THAN THE COOLING SETPOINT, THE ZONE DAMPER SHALL MAINTAIN THE MINIMUM REQUIRED ZONE VENTILATION (ADJ.). DISCHARGE AIR TEM_P_ERATU_RE:THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE. ALARMS SHALL BE PROVIDED AS FOLLOWS: • HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.). • LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.). A n ` ('Go G • •PfYOJ. ��o. 2�C2� CA 924 �' p G U E G • LOUIS J. A�U1RRE A ASSOCIATES P.A. • • •° " CONSULTING ENGINEERS i� �•; '.� 1-21 '50 SOOT' I 'DADFLAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELFPHONP (305) 670 -0141 U uYY•W � r=AX: • (30-) 670 --0144 GYYu • • •• www.liaapa ",om • Y ••bG • •vfi• � BAs Respxansibiiity Matnx BAS INPUT /OUTPUT POINTS LIST Fu'1-11sr1 TAG POINT NAME AO Al AO DI DO NOTES: 1 Air flow sensor 16 x BAS BAS BAS NIA 2 Damper actuator x 16 16 VFDs BA.S 16 3 _ Electric heater stages Starters HOA Switches 16 16 WA x See equipmt data for of stages Y 4 Discharge air temperature x 5 Space air temperature sensor x See plans for location 6 Space air temp sensor setpoint x _ 7 Space air temp sensor override x _ A n ` ('Go G • •PfYOJ. ��o. 2�C2� CA 924 �' p G U E G • LOUIS J. A�U1RRE A ASSOCIATES P.A. • • •° " CONSULTING ENGINEERS i� �•; '.� 1-21 '50 SOOT' I 'DADFLAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELFPHONP (305) 670 -0141 U uYY•W � r=AX: • (30-) 670 --0144 GYYu • • •• www.liaapa ",om • Y ••bG • •vfi• � BAs Respxansibiiity Matnx Work BAS low voltage and communication wiring Fu'1-11sr1 Install BAS Low volt + it if gA -1be Line 13A.S BAS N/A Motorized damper actuators BAS 15 N/A 16 BAS Current sensors BAS BAS BAS NIA - Smoke detectors 16 16 16 16 VFDs BA.S 16 BAS 16 Starters HOA Switches 16 16 WA 16 GENERAL NOTES: SPACE SENSORS LOCATED AS PER PLANS. FIRE ALARM CONTACTS TO BE PROVIDED BY DIV.16 ELECTRICAL CONTRACTOR. WIRE FROM LOCAL FIRE ALARM CONTACTS TO THE MOTOR SHALL BE BY DIVISION 16 FOR FAN SHUTDOWN. CONTROLLERS MUST HAVE H -O -A SWITCHES MOTORIZED DAMPERS BY OTHERS. SD PROVIDED BY OTHERS AND INSTALLED BY F/A CONTRACTOR CONTROL CONTRACTOR MUST PROVIDE TO THE ENGINEER CALCULATION FOR VAV ACTUATOR SIZES TO BE APPROVED. BASIS OF DESIGN TAC/ANDOVER/ADVANGED CONTROLS CORP. 954- 491 -6660 IT ROOM SEQUENCE OF OPERATIONS.'. DURING OCCUPIED MODE: -AHU -4 SHALL BE LNABLFD AN RA BRANCH MOTORIZED DAMPER SHALL BE OPEN. -RA/SA MOTORIZED DAMPERS SHALL BE OPEN -AC -2 SHALL BE CONTROLLED BY ITS OWN THERMOSTAT. AC-2 THERMOSTAT SET POINT SHALL BE SET AT 3 °F (ADJ) HIGHER THAN THE NORMAL ROOM AIR TEMPERATURE SET POINT DURING UNOCCUPIED MODE: -AHU -4 SHALL BE DISABLE, AND THE RA BRANCH MOTORIZED DAMPER SHALL BE CLOSED -RA/SA MOTORIZED DAMPERS SHALL BE CLOSED -AC -2 SHALL BE CONTROLI...ED BY ITS OWN THERMOSTAT. AC -2 THERMOSTAT SLT POINT SHALL BE SET AT THE NORMAL ROOM AIR TEMPERATURE SET POINT. - DURING THIS MODEM, THE SYSTEM SHALL MONITOR THE SPACE AIR TEMPERATURE ALARMS SHALL BE PROVIDED AS FOLLOWS: - RA DAMPER FAILURE: COMMANDED OPEN /CLOSE, BUT THE STATUS IS CLOSF /OPEN. Y VAV COOLING AND HEATING SEQUENCE OF OPERATIONS: RUN CONDITIONS - SC_H_EDULED:THE UNIT SHALL RUN ACCORDING TO A USER DEFINABLE TIME SCHEDULE IN THE FOLLOWING MODES: OCCUPIED MODE: THE UNIT SHALL MAINTAIN A 74 °F (ADJ.) COOLING SETPOINT A 70 -F (ADJ.) HEATING SETPOINT. UNOCCUPIED MODE: THE UNIT SHALL CLOSE TO ITS MINIMUM POSITION. ZONESETPOLNT ADJUST /OPTIMAL START /UNOCCUPIED OVERRIDE:THE OCCUPANT SHALL BE ABLE TO ADJUST THE ZONE TEMPERATURE HEATING AND COOLING SETPOINTS AT THE ZONE SENSOR.THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START -UP. THIS ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM -UP OR COOL -DOWN PERIOD WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF SCHEDULED OCCUPIED PERIOD.A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE SCHEDULE AND PLACE THE UNIT INTO AN OCCUPIED MODE FOR AN ADJUSTABLE PERIOD OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL AUTOMATICALLY RETURN TO THE SCHEDULE. FLOW CONTROL: DURING OCCUPIED MODE THE UNIT SHALL MAINTAIN ZONE TEMPERATURE SETPOINTS BY CONTROLLING THE AIRFLOW THROUGH ONE OF THE FOLLOWING: WHEN ZONE TEMPERATURE IS GREATER THAN ITS COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED AIRFLOW (ADJ.) AND THE MAXIMUM COOLING AIRFLOW (ADJ.) UNTIL_ THE ZONE IS SATISFIED. WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE HEATING SETPOINT, THE ZONE DAMPER SHALL MAINTAIN THE MINIMUM REQUIRED ZONE VENTILATION (ADJ.). WHEN ZONE TEMPERATURE IS LESS THAN ITS HEATING SETPOINT, THE CONTROLLER SHALL ENABLE HEATING TO MAINTAIN THE ZONE TEMPERATURE AT ITS HEATING SETPOINT. ELECTRIC REHEATING STAGES:THE CONTROLLER SHALL MEASURE THE ZONE TEMPERATURE AND STAGE THE REHEATING TO MAINTAIN ITS SETPOINT. TO PREVENT SHORT CYCLING, THERE SHALL BE A USER DEFINABLE (ADJ.) DELAY BETWEEN STAGES, AND EACH STAGE SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME. THE REHEATING SHALL BE ENABLED WHENEVER: AND THE ZONE TEMPERATURE IS BELOW SETPOINT. AND SUFFICIENT AIRFLOW IS PROVIDED. DISCHARGE AIR TEMPERAT_URE:THE CONTROLLER SHALL MONITOR THE DISCHARGE AIR TEMPERATURE. ALARMS SHALL BE PROVIDED AS FOLLOWS: HIGH ZONE TEMP: IF THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.). LOW ZONE TEMP: IF THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT BY A USER DEFINABLE AMOUNT (ADJ.). Revisions: D D D G n U� "02 w W O w (� z a U �U w O ccf � V) ►..-a 0 Z o V PE I T SET DRAWN: MR All EAB (D5 -10 -12 AS SHOUJN a U �U w O ccf � V) ►..-a 0 Z o V PE I T SET DRAWN: MR CHECKED: DATE: SCALE: EAB (D5 -10 -12 AS SHOUJN SE -i tWkV �iy ••�yW ••r�y�° u '•,MECHANICL•' Vu 6LIOENSE Sheet No. M7.02 JOB # 201209