13-441-053SCREW; SCRCVV0 MA I pC ` OMITTED IF HANGER LOOPS STRAP HANGERS SHEET METAL RUNNER TOP AND BOTTOM SECURED TO DUCT WITH SHEET METAL SCREWS SHEET METAL DOUBLE THICKNESS QUARTER ROUND TURNING VANES UNLESS FOOT OF TRAP IS PLACED UNDER A BOTTOM REINFORCEMENT FORLOAD TRAPEZE HANGERS TYPICAL FABRICATED SHEET METAL ELBOW SHEET METAL DOUBLE THICKNESS TURNING VANES WITH FLANGED FASTENERS TOP AND BOTTOM SHEET METAL RUNNER FASTENED TC DUCT WITH SHEET METAL SCREWS DUCT TURNING VANE DETAIL N.T.S. HINGE FLIP TOP ESCUTCHEONS CALK ALL AROUND (TYP ) MIN. 24 GA VANES WEATHER CAP 22 GA. GALV. SHEET METAL i LIQUID E SUCTION LINES - I II II DRAW II II 75 OVERHANG II DOWNTURN I I i KCURB SECURE CURB TO ROOF USING I I I 10' NOMINAL FASTENERS AT 8' O.C. BEFORE (I (I FLASHING HEIGHT APPLYING ROOFING AND INSULATION (IF REQUIRED) (I I I I EXISTING ROOFING EXISTING ROOF � I I ( II II II II II INSULATE VOID TO PREVENT CONDENSATION. V II TYPICAL REFRIGERANT PIPING PENETRATION THRU EXISTING ROOF N.T.S. JER �2 OPPOSED BLADE BALANCING DAMPER WITH CONCEALD LINKAGE, GALVANIZED AS MANUFACTURED BY RUSKIN uMD -35 NOTE: SINGLE BLADE MD -35 DAMPER MAYBE USED ON DUCTS II" HIGH AND UNDER. VENTFAB x644 FOR �� HANDLE WITH LOCKING NUT INSULATED DUCTS VENTFAB x641 FOR SHEET METAL SCREW NON - INSULATED DUCTS. FASTENEGS DUCT BALANCING DAMPER DETAIL N.T.S. 12" ABOVE COOLING COIL L AS CLOSE TX VALVE AS POSSIBLE OR CAPILLARY TUBE FOR 5 TR CAPACITY AND LESS - FILTER DRYER SIGHT GLASS SOLENOID VALVE IF REQUIRED BY MANUFACTURER S - PER L CIRCUIT _ NOT' (') WHETHER OR NOT PIPE SIZES ARE INDICATED, THE MANUFACTURER SHALL SUBMIT FOR APPROVAL SIZES HE RECOMMENDS TO ASSURE PERFECT FUNCTIONING OF EQUIPMENT SUBMITTED. S CONDENSING UNIT PAINT LIQUID LINES EXPOSED TO OUTDOORS WITH TWO COATS OF ALUMINUM REFLECTIVE PAINT NOTE: PROVIDE DOUBLE RISER AT SUCTION LINE IF RECOMMENDED BY MANUFACTURER. REFRIGERANT LINES SCHEMATIC N.T.S. DISCONNECT SWITCH UL. LISTED ELECTRIC CONDUIT - GUIDE NEOPRENE GASKET (FURNISHED WITH CURB) ACOUSTICAL INSULATION -� (FURNISHED WITH CURB) 1/8" STAINLESS STEEL CABLE W/ TURNBUCKLE (SEE NOTE x2) 3/8' GALVANIZED STEEL, SELF TAPPING EYEBOLT (TOTAL OF 4) SECURE FAN TO CURB WITH NO. 14 S/S SCREWS, 8' O.C. ALL AROUND PREFABRICATED FAN CURB (18" MIN. HEIGHT) CANT STRIP (BY ROOFER) ROOFING Z .-- ROOF INSULATION WIRING BACKDRAFT DAMPER BY OTHERS WASHER - - - - - - - 3/8" DIA. THRU BOLTS, 18" O.C. FLEXIBLE MAXIMUM ALL AROUND. LOCATE CONNECTION AS CLOSE AS POSSIBLE TO VERTICAL MEMBER. `�- -- EXHAUST DUCT SEE ARCH. DRAWINGS FOR ROOF CURB ROOF FAN MOUNTING DETAIL N.T.S. NOTE: I. POWER LINES SHOULD BE BROUGHT UP IN ONE CORNER OF CURB AND FED THROUGH THE CLEARANCE HOLE PROVIDED IN THE LOUVER DAMPER, IN TURN, THE POWER LEAD SHOULD THEN BE FED THROUGH THE ROOF VENTILATOR CONDUIT GUIDE OR GROMMENTS. PROVIDE A GENEROUS LOOP OR SLACK IN THE POWER SUPPLY LINE WITHIN THE MOTOR COMPARTMENT TO ALLOW FOR MOTOR DEFLECTION AND FOR BELT TENSION ADJUSTMENT. 2. FANS SHALL BE SECURED WITH CROSS - CONNECTED CABLES OVER THEM, REGARDLESS OF HEIGHT. SCREWS FOR ALL CURB MOUNTED EQUIPMENT SHALL BE SIZE NO, 14 WITH GASKETED WASHERS. 3, SEE ARCH, DRAWINGS FOR ROOF CURB 4. INSTALLATION MUST MEET MINIMUM OF 150 MPH WIND LOADING, MINIMUM REQUIREMENTS ARE HEREBY INDICATED, HOWEVER BASED ON ACTUAL EQUIPMENT INSTALLED EPA (EFFECTIVE PROJECTED AREA) ADDITIONAL SECURING SHALL BE PROVIDED UPPER ATTACHMENT PER SMACNA -- - FLEXIBLE DUCT- 8' -0" MAX. 2' -0" MIN. LENGTH --.` MAXIMUM D/8 OFFSET ALLOWED IN LAST D INCHES TO DEVICE WHERE D IS THE INTERNAL FLEX DIAMETER - visa r•• u r • Y . .vi u•i• r v HORIZONTAL DUCT SHALL BE SUPPORTED AT INTERVALS NOT GREATER THAN 5 FT DUCT SAG BETWEEN SUPPORT SHALL NO EXCEED 1/2" PER FOOT OF LENGTH • 4 0 45- TAKEOFF OR ROUND BELLMOUTH COLLAR MOUNT IN SIDE OF DUCT ADJUSTABLE CLAMP — Al CLOSE OPENING 45 DEGREE ENTRY - 45 HVAC DUCT CONSTRUCTION STANDARDS ALL DUCTWORK MUST COMPLY WITH SMACNA HVAC DUCT CONSTRUCTION STANDARD AS FOLLOWS- LOW PRESSURE DUCTWORK 2 "W.G. W.(4" MIN) TAPP -OFF WITH VOLUME DAMPER N.T.S. I I /2'XI 1 /2' (MIN) ANGLE IRON FRAME INSULATION DUCT OPERATOR /ACTUATOR BREAKAWAY POINT FUSIBLE ROD ACCESS DOOR 14 "Xi4" MIN. ZONED AS REQUIRED WALL Al CLOSE OPENING 45 DEGREE ENTRY - 45 1 SADDLE u \� 22 GUAGE GALVINIZED STEEL NECK SIZE TO STRAP HANGER AS PER MATCH FLEX SMACNA FIG. 3 -10 (SEE NOTE x5) DUCT SIZE INDICATED - -- ADJUSTABLE CLAMP OR ROUND BELLMOUTH COLLAR DUCT SEALER CONNECTION TO MAIN INSULATE TOP PANEL *Ova W V OF DIFFUSER OR GRILLE v i • • AIR DISTRIBUTION DEVICE CEILING (T -BAR SHOWN. - LAYIN SHOWN. GYP. BOARD SIMILAR) SURFACE MOUNT SIMILAR NOTES 1. FLEXIBLE DUCTS SHALL BE ONE PIECE AND SHALL NOT BE SPLICED TOGETHER . 2. EXTEND FLEXIBLE DUCT INSULATION TO DUCT /DIFFUSER PANEL INSULATION AND SEAL WITH MASTIC. 3. FLEXIBLE AIR DUCT SHALL NOT EXCEED 8 FT. WHEN EXTENDED. ELBOW RADIUS SIZED FOR NO LESS THAN R / D = 1.0. 4. 24 INCH ORANGE SURVEY TAPE SHALL BE PROVIDED ON ALL DUCT QUADRANT LOCKING LEVERS DIRECTLY ABOVE THE ACCESS PANEL. 5. MINIMUM 11/2* WIDE 22 GALVANIZED STRAP HANGER WITH HEMMED EDGES. (FBMC 2007 603.5.6.6) FLEXIBLE DUCT TAKEOFF DETAIL NTS Al CLOSE OPENING 45 DEGREE ENTRY - 45 HVAC DUCT CONSTRUCTION STANDARDS ALL DUCTWORK MUST COMPLY WITH SMACNA HVAC DUCT CONSTRUCTION STANDARD AS FOLLOWS- LOW PRESSURE DUCTWORK 2 "W.G. W.(4" MIN) TAPP -OFF WITH VOLUME DAMPER N.T.S. I I /2'XI 1 /2' (MIN) ANGLE IRON FRAME INSULATION DUCT OPERATOR /ACTUATOR BREAKAWAY POINT FUSIBLE ROD ACCESS DOOR 14 "Xi4" MIN. ZONED AS REQUIRED WALL Al CLOSE OPENING 45 DEGREE ENTRY - 45 1 VOLUME DAMPER W/ LOCKING QUADRANT S 2" STANDOFF FULLY HINGED E GASKETED ACCESSDOOR FOR DAMPERS IN NON - ACCESSIBLE CEILINGS TAPP -OFF WITH VOLUME DAMPER N.T.S. 1/4' CLEARANCE PER FOOT ALL AROUND SLEEVE - DUCT NEGATOR SPRING - 6' (MAX) BOTH SIDE AIR FLOW CAULKING FULL PERIMETER OF DAMPER (TYPICAL BOTH SIDES) COMBINATION FIRE /SMOKE DAMPER DETAIL N.T.S. NOTES: I. DAMPER "RUSKIN.' FSD 60 WITH 165•F FUSIBLE LINK OR APPROVED EQUIVALENT. 2. INSTALLATION OF THE DAMPER SHALL BE IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND UL555S, yFROJ. aVo. m CA 924 • OWri V • �AOUIS�J. "AGUIRRE & ASSOCIATES R.A. GONSULTING ENGINEERS 9150 SO4ffl bADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELEPII%4 (4305) 670 -0141 'FAX:• (3�5) 670 -0144 :www4jaapce.come Revisions: Z� IA d d< �21_~ C L. 0 x w c c2)0 ~g�4 �J C C5 C7 z -� s. O Q4,0 w� o (a V > Lw PERMIT SEA" DRAWN: r i • u u • u i - i U W • • V U V y DUCT SEALER AT 45- TAKEOFF iiU OR ROUND BELLMOUTH COLLAR CONNECTION TO MAIN • v*• *Ova W V v v i • • • r • SUPPY AIR DUCT y•itl i Y•i G6 • VOLUME DAMPER W/ LOCKING QUADRANT S 2" STANDOFF FULLY HINGED E GASKETED ACCESSDOOR FOR DAMPERS IN NON - ACCESSIBLE CEILINGS TAPP -OFF WITH VOLUME DAMPER N.T.S. 1/4' CLEARANCE PER FOOT ALL AROUND SLEEVE - DUCT NEGATOR SPRING - 6' (MAX) BOTH SIDE AIR FLOW CAULKING FULL PERIMETER OF DAMPER (TYPICAL BOTH SIDES) COMBINATION FIRE /SMOKE DAMPER DETAIL N.T.S. NOTES: I. DAMPER "RUSKIN.' FSD 60 WITH 165•F FUSIBLE LINK OR APPROVED EQUIVALENT. 2. INSTALLATION OF THE DAMPER SHALL BE IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND UL555S, yFROJ. aVo. m CA 924 • OWri V • �AOUIS�J. "AGUIRRE & ASSOCIATES R.A. GONSULTING ENGINEERS 9150 SO4ffl bADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELEPII%4 (4305) 670 -0141 'FAX:• (3�5) 670 -0144 :www4jaapce.come Revisions: Z� IA d d< �21_~ C L. 0 x w c c2)0 ~g�4 �J C C5 C7 z -� s. O Q4,0 w� o (a V > Lw PERMIT SEA" DRAWN: CHECKED: -- DATE: 04 - I9 - 2 m 13 SCALE: AS SHOWN SEAL .0 < !A c jANIC,AtL+ £ ' gU0D0 A, �IICENIa� x:647 G4 Sheet No. JOB � 2PJ13ml