Loading...
13-441-052Ventil2tionSizing Summary for AHU # 1 Project Name: 23018 Larkin Community Hospital 04! 15/20113 Prepared by: Louis J. Aguirre & Associates P.A. 02:15PM 1. Summary Ventilation Sizing Method ASHRAE Std 62.1-2007 t-)t--,igrl Condition Minimum flow (heating) Occupant Diversity 1.000 Uncoriected Ventilzilion Airflow Rate 909 CFPvl System Ventilation Efficiency 0,800 Design Ventilation Airflow Rate 1136 CFM 2. Space Ventilation Analysis Table Supply Air Ventilation Sizing Summary for AHU # I Project Name: 23018 Larkin Community Hospital 0J /15,,2013 Prepared by: LOUIS J. Aguirre 9 Associates P.A, 02:15PM Ventilation Sizing Summary for AHU * 1 Proj-act Name: 230111 Larkin Community Hospital 04x15;2013 Prepared by: Louis 3 Aguirre & Associates P.A. 02:15PM 6.1 J Doctor's Off 1 Minimum Floor Required Time Required Air Required Uncorrected Space 6501111 Off 9110 2 Supply Air Area Outdoor Air Avorageal Outdoor Air Distribution Outdoor Air Outiloor Air Ventilation Zone Name I $pace Name Mult. (CFM) (w) (CFM/ft') Occupancy (CFMIperson) Effectiveness (CFM) (CFM) Efficiency Zone I 2 20 103.4 0.06 2.0 5.00 U0 20 0,800 600 Waiting Area 1 96 444.0 OrOG 10.0 SrOo 96 20 0,800 040 601/660 Check Out 2 13 86.0 0.06 1.0 5.00 0.80 13 664 Work Area 0800 602/661 Work Area 2 46 107.3 0.06 5r0 500 0.80 46 1 0.860 603 F HC Toilet 1 0 5111.6 0.00 0.0 0.00 0 21 0.11100 0.20 604 Clean Supply 1 5 32,6 0112 0.0 0.00 040 5 S09 0,800 605 Soiled Holding 1 6 42.3 0.12 0.0 000 040 6 0 06 0.800 606/611 Office 1/5 21 11 65.4 0.06 1.0 5.00 0.90 11 'J 0*00 607 Office 2 11 12 74.5 0.06 1.0 5.00 0.80 12 0800 608/609 Off 314 21 11 67,0 0.06 1.0 5.00 0.90 11 1300 610J616 Work Area 2 22 123.7 0.06 2.0 5.00 0.80 22 0.800 612 Office 6 11 10 565 0.06 500 0.80 10 0800 1.0 613!615 Corridor 1 18 239.2 006 00 000 0,110 12 0800 614 Research Off. 7 1 11 67.4 0.06 1.0 5.00 0.80 11 0800 617161 S R Off 5/6 2 14 98.0 0.06 1.0 5.00 0,80 14 0.300 119 llebeat-ch 011, 4 1 15 12U 0.06 1.0 5.00 0.90 15 0.400 620 Research Off. 3 1 18 159.0 006 1.0 5.00 0.30 Is 0.800 621 Research Off. 2 1� --11 60-.0 0.06 0,40 11 0800 1.0 ---5,00 622 Research Off, 1 1 15 110.0 0.06 1.0 500 0-1110 is 0.800 624 Exam RM 1 20 102.0 0.06 2.0 5.00 0.80 20 0900 625/628 Exam RM 2 20 0.06 2.0 5.00 - 0.80 20 - ---- 0800 6261623 Exam RM 2 21 114A. O.UEi 2.0 5,00 0-80 - - - -21 0.800 627 Corridor 1 26 345.0 0.06 0.0 0.00 0,30 26 0.800 629 Ortho Exam RM 1 25 161.3 0.06 0,06 2.0 5.00 0,90 25 i 0800 0,800 630/662 DictiView, RM 21 10 $6.0 1.0 500 040 10 631 X-Ray 1 0 318.0 0.00 1.0 00 0.1110 0 0600 631A X-Ray/Control RM 17 583 0.06 2.0 5.00 0.80 17 0.800 63 2 Corridor 633 X-Ray 1 0 3210 228.1 0.06 0.00 0.0 1-0 0.00 0.00 0.80 0.80 24 0 0800 0.800 633A X-Ray?Conttol RM 1 16 52.4 0.06 -,--2.0 5.00 0.20 16 -mm 0.800 634 Storage 631',,1636 Ofl'718 1 2 13 21 3 9:1.0 0.12 0.06 0.0 1.0 OM 5.00 0.1110 -U.60 13 0800 0 801) 637 Doctor's Off. 1 27 187,0 0,06 2,0 5r00 0.86 27 --- 631 Doctor's Off --- ---- 1 15 120.0 0.01 1.0 5.00 0,40 Is 2 0.400 639 IT/Data Room 1 2 33L0 0 06 0,0 000 0.80 2 0800 640/644/645/647 Corr 1 45 599.3 006 2.0 000 0,11110 45 0.800 641 Conference RM 1 47 211.2 0.06 5.0 500 0.80 47 0 800 642. Janitor 1 4 27.0 012 0.0 0.00 0.90 011100 643 Staff Toilet 1 0 68.0 0.00 0.0 0,00 0,80 0 0,800 646 Staff Lounge. 1 75 303.0 006 9.0 5,00 0.80 79 0.300 6.18 Doctor's Off. - .- ----- - - ---- -- 19 173,41 0,06 1.0 -- . - - .. - - - 5.00 -- - -- OMI . - -r ­-­'. 19 0 801 Ventilation Sizing Summary for AHU * 1 Proj-act Name: 230111 Larkin Community Hospital 04x15;2013 Prepared by: Louis 3 Aguirre & Associates P.A. 02:15PM 6.1 J Doctor's Off 1 14 98.1 0.06 1.0 500 0.80 14 0.100 0.800 6501111 Off 9110 2 13 94.0 0,06 1,13 5.00 0.80 Outdoor Air Outdoor Air 0.800 652 Exam RM 1 21 109.0 0.06 20 500 0.80 21 (CFM) 0.11100 653/655 Exam RM 2 20 103.4 0.06 2.0 5.00 U0 20 0,800 - 654 Corridor 1 20 21539 0 06 0.0 0 00 0.8Q 20 0.900 0.1100 656 Exam RIA 1 20 103.2 0.06 2.0 5.00 0.80 20 664 Work Area 0,800 657 Oitho Ex. RM 1 23 142,3 0.06 2.0 5.00 0,80 23 1 0800 658 Exam RM 1 21 107.2 0.06 2.0 5.001 0.0 21 19 6-110-0 Totals (i- n cl- . pace Multipliers) 2.0 1136 19 0.800 1 11 S09 0400 • N- 01. NO. CA 924 1QUIS-J. LAGUIRRE & ASSOCIATES P.A. CONSULT114G ENGINEERS 'JT50 sowWcADFLAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TF(FMONI�;, 05) 670--0141 FAX:' (3(n) 670 -0144 �,Www.jjaaptcom, Ventilation Sizing Summary for AHU # 1 (1) Project Name: 23018 Larkin Community Hospital 041152013 Prepared by- Louis J Aguirre & Associates P.A. 02, 1 5Plvl 1. Sun-ifnary Ventilation Sizing Method ASHRAE Std 62.1-2007 Design Condilion Minimum flow (heating) Occupant Diversity 1.000 Uncorrected Ventilation Airflow Rate 901 CFM System Ventilation Efficiency 0.100 Design Ventilation Airflow Rate 1126 CFM 4',nnpn Nlnnt;Infinn Anmiwcic Tnhln Supply Air Revisions- A A A A- A V) 0 Z 0 U Z �Zp < C5 0 4J I GPM f U 4111 0 as I (A < > PERMIT SET DRAWN J-IB- Minimum Floor Required Time Required Air Required Uncorrected Space Supply Air Area Outdoor Air Averaged Outdoor Air Distribution Outdoor Air Outdoor Air Voritilati*n Zone Name I Space Name MUIL (CFM) (ft') (CFM/ft') Occupancy (CFM]person) Effectiveness (CFM) (CFM) Efficiency, Zone I 659 ki HC Toilet 1 0 39.2 0,00 0.0 000 0,80 01 0.900 663 Rehabilitation 1-610 11104.4 O.Uti 190 2000 0.80 10 0.800 664 Work Area 1 40 203.4 0 06 4.0 6.00 080 40; 0.800 665/666 FIM I I I C Toilet 1 0 43,2 ----- -- --- 0L00 0.0 0.00 l 0.80 ---Orb-0 01 0800 Ca67 Support Area 1 19 80.5 0.06 2.0 5.00 19 0.800 664 Storage 1 11 744 0.12 00 00() O 80 IV 0400 669 Sub -Wait. 1 771 276.0 0 06 9.0 5,00 0.80 771, 0.800 Future Office 1 3691 3080.0 0.06 22.0 500 080 369' 0.800 Totals (incl. Space Multipliers) l 1126 ------ - 901 0.400 Revisions- A A A A- A V) 0 Z 0 U Z �Zp < C5 0 4J I GPM f U 4111 0 as I (A < > PERMIT SET DRAWN J-IB- CHECKED: E.5. DATE: 04-I9 -2013 SCALE: A5 SHOLLN SEAL (,,l, 4Z ME04AN CA4L Y 7E.�DQ,A, SuAQr- 1E I Sheet No. I •6.01 IJOB # 201301 1