13-441-047HVAC GENERAL NOTES 1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY FOR THE INSTALLATION QF HVAC SYSTEM IN ACCORDANCE WITH THESE DRAWINGS. 2. THE WORK INCLUDES PROVIDING THE HVAC SYSTEMS, INCLUDING DUCTWORK, DIFFUSERS AND GRILLES, INSULATION, CONTROLS AND EQ UIPMENT NECESSARY FOR A COMPLETE FUNCTIONING SYSTEM. HVAC SYSTEM INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING: SUPPLY, RETURN AND EXHAUST DUCTWORK SYSTEMS WITH GRILLES, DIFFUSERS FILTERS AND DAMPERS. 3. TEMPERATURE CONTROL SYSTEM INCLUDING LOW VOLTAGE WIRING AND CONDUIT, TRANSDUCERS, ACTUATORS, CONTROLLER. 4. WARRANTY: PROVIDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR AFTER SUBSTANTIAL COMPLETION OR OWNER ACCEPTANCE OF THE COMPLETED PROJECT. 5. DRAWINGS FOR HVAC WORK ARE DIAGRAMMATIC, SHOWING THE GENERAL EQUIPMENT LOCATION, TYPE, LAYOUT AND REQUIRED. THE DRAWINGS SHALL NOT Q BE SCALED FOR EXACT MEASUREMENTS. REFER TO MANUFACTURER'S STANDARD INSTALLATION DRAWINGS FOR EQUIPMENT CONNECTIONS AND INSTALLATION REQUIREMENTS AS REQUIRED. FURNISH AND INSTALL ALL DUCTWORK, CONNECTIONS, ACCESSORIES, OFFSETS AND MATERIALS NECESSARY TO FACILITATE THE SYSTEM FUNCTIONING AS INDICATED BY THE DESIGN AND THE EQUIPMENT INDICATED. 6. CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES, ESPECIALLY WITH THE LOCATION OF STRUCTURAL MEMBERS, PIPING, SPRINKLERS, CONDUITS AND LIGHTING OUTLETS AND /OR FIXTURES. 7. ALL MATERIAL AND EQUIPMENTS SHALL BE NEW OF U.S. MANUFACTURER AND OF GOOD QUALITY OF RESPECTIVE KIND AND GRADE, AND MUST BE FURNISHED SO AS TO PREVENT ANY DELAY IN THE PROGRESS OF THE WORK. ALL WORK THROUGHOUT SHALL BE PERFORMED IN A WORKMANLIKE MANNER BY SUFFICIENT NUMBER OF SKILLED PERSONNEL. 8. FLEX DUCT: PROVIDE FACTORY ASSEMBLED CLASS 1 AIR DUCT (UL 181) WITH 1 -1/2" THICK 1 PCF FIBERGLASS INSULATION R -6 AND REINFORCED OUTER PROTECTIVE COVER /VAPOR BARRIER. FLEX DUCT SHALL MEET NFPA 90A WITH FLAME SPREAD L UNDER 25, SMOKE DEVELOPED UNDER 50, AND SHALL BE RATED FOR 2" W.G. PRESSURE AND 0 TO 250 DEGREES FAHRENHEIT, PROVIDE METAL ADJUSTABLE CLAMPING DEVICES, SCREW OPERATED. USE TWIST -LOCK CONICAL TAP COLLARS AT CONNECTIONS INTO SHEET METAL DUCTWORK. FLEXIBLE DUCTWORK MAY BE USED FOR BRANCHES TO DIFFUSERS AS INDICATED ON DRAWINGS. DO NOT EXCEED EIGHT (8) FEET IN LENGTH FOR ANY FLEX DUCT. ACCEPT MANUFACTURER FLEX MASTER 8M AND THERMOFLEX MKE. 9. BALANCING DAMPERS: FABRICATED OF SAME MATERIAL AS DUCT, TWO METAL GAUGES HEAVIER THAN DUCT. MOUNT ON 3/8" SQUARE ROD WITH SAW SLOT POSITION INDICATOR. PIVOT AND BEARING, LOCKING POSITION REGULATOR. 10. ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE FROM DEFECTS AND WITH MANUFACTURER'S WARRANTY. 11. PROVIDE DOUBLE THICKNESS TURNING VANES AT ELBOWS AND EXTRACTOR DAMPERS AT ALL DUCT BRANCHES AND TAKE -OFFS. 12. ALL EXHAUST DUCTWORK SHALL BE OF GALVANIZED SHEET METAL FABRICATED IN ACCORDANCE WITH SMACNA STANDARD FOR PRESSURE CLASS ACCORDING TO EACH SYSTEM. EXHAUST AIR DUCTWORK SHALL BE UNINSULATED. 13. FLEXIBLE CONNECTOR: WHERE REQUIRED PROVIDE U.L. LABELED NEOPRENE COATED FIBERGLASS FABRIC DUCT CONNECTORS. 14. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL OF ALL EQUIPMENT, MATERIALS AND LAYOUTS PRIOR TO INSTALLATION. 15. CONTRACTOR SHALL PRINT -UP INSTRUCTIONS FOR OWNER'S OPERATION OF SYSTEMS. L PAY ALL INSPECTION FEES. ALL COSTS OF PERMITS AND 16. THE CONTRACTOR SH A L ALL OTHER COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK UPON FINAL ACCEPTANCE A CERTIFICATE FROM THE LOCAL INSPECTION AUTHORITY SHALL BE FURNISHED TO THE OWNER. 17. THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH THE LOCATION OF EXISTING EQUIPMENT, DUCTWORK, PIPING, CONDUITS, ETC., AND /OR ANY CONDITION THAT MAY AFFECT HIS WORK. 18. ALL AIR CONDITIONING DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET METAL INSULATED WITH 2 INCH THICK AND 1.0 PCF GLASS FIBER FLEXIBLE BLANKET INSULATION WITH ALUMINUM FOIL REINFORCED WITH GLASS FIBER EASING (FSKL) JOHN - MANVILLE MICROLITE (R -6 INSTALLED) OR APPROVED EQUIVALENT, DUCT SIZES SHOWN ARE NET FREE AREA. PROVIDE DOUBLE THICKNESS TURNING VANES AND EXTRACTORS AT ALL ELBOWS AND TAKE -OFFS. 19. ALL CONCEALED SUPPLY AND RETURN AIR DUCTS SHALL BE EXTERNALLY INSULATED WITH DUCT WRAP AS INDICATED IN GENERAL NOTES. 20. REFRIGERANT PIPING SHALL BE COPPER TUBING WITH WROUGHT COPPER, SOLDER JOINT TYPE FITTINGS. USE 95/5 SOLDER. REFRIGERANT PIPING SHALL BE SIZED IN ACCORDANCE WITH LQUIVALET PIPE LENGTH FOR PRESSURE DROP EQUIVALENT TO ONE DEGREE FARENHEIT, 1" FOAMED PLASTIC INSULATION SHALL BE PROVIDED FOR SUCTION LINES, WITH APPROVED PROTECTIVE FINISH WHEN EXPOSED TO WEATHER AND WHEN INSTALLED IN RETURN AIR PLENUMS. FILTERIDRYER AND SIGHGLASS SHALL BE PROVIDED AT LIQUID LINES. 21. CONSTRUCTION FILTER: PROVIDE TWO SETS OF TEMPORARY 2 INCH THICK FIBERGLASS THROW AWAY FILTERS DURING CONSTRUCTION AND START UP. CONSTRUCTION FILTERS TO BE 35% EFFICIENT. CONSTRUCTION FILTERS PROVIDED FOR ALL FILTER APPLICATION, REPLACE FILTER REGULARLY BUT NOT TO EXCEED 7 DAYS DURING CONSTRUCTION. FINAL FILTERS: SHALL CONSIST OF A SINGLE 2 INCH THICK, DISPOSABLE, PLEATED PARTICULATE FILTER, ASHRAE 52.1 -92 RATED AT 40 -45% PERCENT ATMOSPHERIC DUST SPOT EFFICIENCY (ADS), LOCATED IN FILTER BOX OF EACH COIL. 22. RETURN AIR DUCTS LOCATED ABOVE UNCONDITIONED SPACES SHALL BE INSULATED THE SAME AS THE SUPPLY AIR DUCTS. 23. DUCT FINISHES AND SEALERS SHALL HAVE A SMOKE DEVELOPED RATING OF LESS THAN 50 AND A FLAME SPREAD OF 25 OR LESS. 24. DURING CONSTRUCTION, ALL SUPPLY AND RETURN DUCTWORK OPENINGS SHALL BE FITTED WITH BLANKET TYPE, DISPOSABLE 1" THICK SYNTHETIC MEDIA IN ORDER TO PREVENT CONSTRUCTION DEBRIS FROM ENTERING AND ACCUMULATING INSIDE THE DUCT SURFACES. UPON COMPLETION, CONTRACTOR SHALL CLEAN ALL DUST AND DEBRIS IN AREAS WHERE WORK WAS CONDUCTED. 25. CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE THE TEST & BALANCE FOR THE HVAC SYSTEM AS PER ASSOCIATED AIR BALANCE COUNCIL STANDARDS (DONE BY CERTIFIED TEST & BALANCE CONTRACTOR OR ENGINEER). 26. PROVIDE FIRE STOPPING ALL AROUND DUCTS CROSS 1 HOUR RATED WALL. 27. EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE CONDITIONS OF THE LISTING, THE MANUFACTURER'S INSTALLATION INSTRUCTIONS ON FBC -2010 CHAPTER 3 GENERAL REGULATIONS - SECTION 304 INSTALLATION # 304.1 GENERAL. MANUFACTURER'S INSTALLATION SHALL BE AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTION. 28. THE SMOKE DUCT DETECTOR SHALL CONNECTED TO THE FIRE ALARM SYSTEM. AIR CONDITIONING LEGEND SYMBOL DESCRIPTION AC AIR CONDITIONING UNIT (DX TYPE) BD BACKDRAFT DAMPER COND. CONDENSATE CU CONDENSING UNIT CFM CUBIC FEET PER MINUTE EF EXHAUST FAN EA EACH E/A EXHAUST AIR FD FIRE DAMPER FLA FULL LOAD AMPS FPM FEET PER MINUTE FPS FEET PER SECOND H HUMIDISTAT HP HORSEPOWER HR HOUR IN. INCH KW KILOWATT LBS. POUNDS MAX. MAXIMUM VD MANUAL VOLUME DAMPER (OPPOSED BLADE TYPE) NO. NUMBER O/A OUTSIDE AIR R/A REVOLUTIONS PER MINUTE RPM, RETURN AIR REF. REFRIGERANT S/A SUPPLY AIR SD SMOKE DAMPER TEMP. TEMPERATURE T THERMOSTAT V VELOCITY VAV VARIABLE VOLUME BOX VFD VELOCITY FREQUENCY DRIVE. HVAC DESIGN REOUIRES: YES NO DUCT SMOKE DETECTOR - VAV BOX SIZE DUCT MTD. SMOKE-- DETECTOR W /REMOTE & FEST SWITCH (PROVIDE ACCESS DOOR. 12x12 rain) FIRE DAMPERS) X 24X12 SMOKE DAMPER(S) X -_ EXISTING EQUIPMENT OR DUCT TO BE REMOVED. FIRE RATED ENCLOSURE _ _ _ X_ FIRE RATED ROOF /FLOOR CEILING ASSEMBLY 9 X FIRE STOPPING X THERMOSTAT / HUMIDISTAT SMOKE CONTROL 14 X AIR DISTRIBUTION LEGEND DUCT: FIRST FIGURE IS SIDE SHOWN INLET) SHALL BE AS FOLLOWS: I'AIN Al b 1- 1. Si i8r;V4G VAV BOX SIZE DUCT MTD. SMOKE-- DETECTOR W /REMOTE & FEST SWITCH (PROVIDE ACCESS DOOR. 12x12 rain) ©AD SD FC ����p I I /VVVYI U.C. 60 24X12 8 *0 - m� /m /1 L21 EXISTING EQUIPMENT OR DUCT TO BE REMOVED. FLEXIBLE DU(,T; FLEXIBLE CONNECT -ION (FC) DUCT SECTION: SUPPLY & 8 RETURN OR EXHAUST 9 UNDERCUT DOOR OT OW ALL ELBOW MUST BE PROVIDED WITH TURNING VANES WHETHER THERMOSTAT / HUMIDISTAT OR SHOWN ON DWGS. 14 MOTORIZED DAMPER - TYP. 45* TAP -OFF WITH VOLUME DAMPER 1; 4 nun }" X 22 C },, aa" VARIABLE AIR VOL UME BOX WITH ELECTRIC HEA TER T1,'vO 11:1 I,:, VD VAV VOLUME DAMPER ? ri' VD !; 4 rnr1; TRANSITION RECTANGULAR TO ROUND - Sri ili 1t3 +.) • SPLITTER DAMPER 1 .t 18 qE, '+ i {" 1" X 2i1 gsr DEMOLITION TO THIS POINT 1" h ..F qA t 1' .. 2, rl + 1 1 CO2 MONITOR DEVICE Fc-6-21 � F5 POINT OF CONNECTION BETWEEN NEW AND EXISTING WORK. FIRE DAMPER ( MUST BE USE ACCESS DOOR) COMBINATION FIRE / SMOKE DAMPER ( MUST BE USE ACCESS DOOR) NOTES 1. 45R TAP -OFFS, SPLITTERS AT EACH TAP -OFF AND TEE, AND ACCESS DOORS SHALL BEE USED WHERE REQUIRED, WHETHER OR NOT INDICATED IN THE DRAWINGS. 2. IN AREAS WHERE NON - REMOVABLE CIELINGS ARE USED, PROVIDE 45 TAP -OFFS OF THE FIXED TYPE, WITH WIDTH PROPORTION TO BRANCH CFM. CODES AND STANDARDS APPLICABLE CODES AND ORDINANCES, N STANDARDS SHALL INCLUDE ALL STATE LAWS LOCAL UTILITY COMPANY REGULATIONS AND THE APPLICABLE REQUIREMENTS OF THE FOLLOWING ACCEPTED CODES AND STANDARDS. WITHOUT LIMITING THE NUMBER AS FOLLOWS. 1. FLORIDA BUILDING CODE - 2010 EDITION. 2. GUIDELINES FOR DESIGN AND CONSTRUCTION ON HEALTH DEPARTMENT CARE FACILITIES 2010 EDITION. 3. NATIONAL ELECTRICAL CODE (NEC 2008). 4. ENVIRONMENTAL PROTECTION AGENCY (EPA). 5. DEPT. OF ENVIRONMENTAL REGULATION MANAGEMENT (DERM). 6. LOCAL ORDINANCES, REGULATIONS OF THE BUILDING DEPTS. AND FIRE DEPTS. 7. NATIONAL ELECTRICAL SAFETY CODE 2002- 8. OCCUPATIONAL SAFETY AND HEALTH STANDARD. 9. RECOMMENDATIONS OF NFPA, IN GENERAL AND IN PARTICULAR: A. LIFE SAFETY, NFPA 101 (2009) B. HVAC, NFPA 90A, B (2009) C. HVAC, NFPA 96 (2004) D. HOSPITALS, NFPA 99 (2005) E. SMOKE CONTROL, NFPA 92A (2000), 92B (2005) F. STANDARD FOR INSTALLATION OF EXHAUST SYSTEMS, NFPA 91 (2004) G. STANDARD FOR INSTALLATION OF SPRINKLERS SYSTEM, NFPA 13 (2007) 10. RECOMMENDATIONS OF ASHRAE (2001), INCLUDING ASHRAE 90 -75. 11. FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION (2012). 12. SMACNA (2005) -TYPE OF DIFFUSER A1GW DIRECTION OF FLOW 6 X 11 5 O SIZE OF DIFFUSER AMOUNT OF CFM AIR OUTLET TAG N.T.S. GENERAL NOTE: AS PART OF THIS CONTRACT, THE SUB - CONTRACTOR AND THE CONTRACTOR ARE RESPONSIBLE FOR COORDINATION AND VERIFICATION THAT ALL EQUIPMENT, SHOWN IN THE ARCHITECTURAL DRAWINGS PARTICULARLY, BUT NOT LIMITED TO SHEET EQUIPMENT PLAN, INCLUDE ALL SERVICE /UTILITY REQUIRED TO OPERATE THE EQUIPMENT SHOWN. ANY DISCREPANCIES ARE TO BE POINTED OUT DURING THE BIDDING PROCESS. DISCREPANCIES NOT POINTED OUT DURING THE BIDDING PROCESS WILL BE RESOLVED BY THE CONTRACTOR AS PER THE ARCHITECT DETAILS AT NO ADDITIONAL COST TO THE OWNER. VAV BOXES SIZES SIZES OF ROUND METAL DUCTS CONNECTING TO VAV BOXES (PRIOR TO TRANSITION ING TO REQUIRED FLEX DUCT AT BOX INLET) SHALL BE AS FOLLOWS: I'AIN Al b 1- 1. Si i8r;V4G VAV BOX SIZE ROUND METAL.DUCT-SIZE 4 60 5 8 *0 6 8 "0 7 10 "0 8 10,0 9 ITO 10 12'0 12 14 "0 14 16 "0 16 18 "0 RECTANGULAR DUCT HANGERS MINIMUM SIZE °'• ,'� :. �: _ -: ' t'-_ -` 92 VAX1,1U[d H>`,LF OF PA.R AT 10 FT. SPAGf,IG PAS: AT 3 F1 SI.�.c,1NG I'AIN Al b 1- 1. Si i8r;V4G Pj%liZ Al 4 1 1. t.l'AC'.I iGI . y` DUCT PH_gI TTFR STRAP NARFRC)r) STRAP Vti'€ "r2f W)F) ;,TRAP I�'4PI"POD iItLAF 1/ ;lilf�+yf7 I_I IINlI [rl _,. ' 7 III ICJ ga +.i :[ rl ll fl 11),�a L' I?EOUIRED t? c�t�. r''iul_I I' n C)F' 1 11'Jf 12 r,<. P2 = iii„ 1" X 22 ga ,,' III 1" X 22 Get 1; 4 nun }" X 22 C },, aa" 1„ ;,:1''tX1 T1,'vO 11:1 I,:, 1 „} t„ _ 1)., + 1 1 rnlr ? ri' iC) I r1j !; 4 rnr1; {ll 1(iiij - Sri ili 1t3 +.) • F'.'1 72 1 .t 18 qE, '+ i {" 1" X 2i1 gsr 1 1" 1" h ..F qA t 1' .. 2, rl + 1 1 t'2 '_t. ------ ._. - - -- � 1 n 1(:. ya. , „ 1 .{ 18 ilia j ii" 2.1 y�+ _ }'.' 1 ?I�" 1 1;'" i. ]ii <a._i 1,,�„ 1 h lc.l :� 17 i n rl i 1" X 1i sja 0 X L,.I T';','. -, 2' 1 1 rr n 4" 1.2' T,;',; , ?J1J' r'v ",a ? 1; 0 rrlm -- r r r F 1c 1.6 i= lr� NOT DESIGNED w �F..- E �4 L [= 2LI H _(, -I-1c" M I _,_, L IoH f_t _'r, L w _. H ''1!1.• f i- I •1_' F1 _ 1 STP1.F'- ,f'.rmE. ,''LVv,'j1C7. STEEL. RIO , °,PEiItK,:m,TEL1 :iK,I ::,L',i. 1 + ;fi" 1 i;2" X 16 y,; 1 -.. 1 ir"_': 1r'!1,, 1 2" 1» X Iii q't :5 i;" 1" X W 11,' I P2 =, 192" NOI GUEh1 1 ''" 1 1!2' X 1c;y:a 1."2" 1" X 16 ya :E1 1 1 :: lr; {; I 3 u rat ._ 1:1:3.. II ?'rL. (�, €_ /0:ALYSIS FIEG -1-I 1, ^1:1175 STFtAFrS A.RE tAP,(l7lf•!Ci")!; E Shit;_LEiA ;i_LI<i, @r1 „.L:,i'f: ALLriVe�>!.[iLt- L +�,�1) F -..-4 1 :'4 7.a AP 11; lil ?;' ;3�, - �€ V.w) _ 1; f�i� l)I t; •„ C t I" X - 1,( i ")1 I' 1" X 2l a :)td) i,RS f1� t7 1G1," iii) I i' X':( ;y<a I`N�) 1.4 "1:I.10L1 1 "X`)i1y..l �2i11L:' 1 :''r i 1 ' �i'" h 1 U vita - [ V'VCi S::i" L1JFr I =?i31: i '-i ,r ally i" X 1� u:, 0. 2' ll_ .a [a ` ♦ x 6 i !AJ IES � 101 :;b1r b Z;4,E `/'"+5�E t�/"\�I I✓'liJ {J €i1 1{�S'[f�,.J, I 1" X 11.a ua - f Ir,'., :s'' 5.21" - 2000 1?',,, 3 1" - " ;r)t')01i: 1 DII: E 4,. l:) €'i 07111 -k TIIAIS OA6r,5 A R F 111 ICI JES, 2 1Altl- Et,LLC+�.'�i FURL'i-sGTwEicii1 1 It3 ;f1111i6tiLAIsX41 IU6t hI ANI. ;ti )[ft.r:s_ ;<M[Vi1CO3 1•1 I AU; II;A-.€'1it.:l''�'H6� A. 13 -i1 (lUt>[U2t'J�LLt.)tJ:; �.. - STk/�F� nr�E G><,w�. /A€u�l� UrEEL 4 ALL0V,&\b:_E LOADS FOR P,2 t SSuIv€ETRAT ui,t�TS ARE 1i, GA. f i ;v f<: IfV'. EX -J'i THAT ."v1iFS4 ki's, , ;oi' ;i Dij\' I D Lf':u!'., ;a t. V ; I OVER 60" TFa/�f i R2 Ivi7 X1,iUt.1 V, 1.25 wi. 12, tit. 8 ya VVIRF w, TFF1 OF r ACI<',1': €iI I FD FiRli,i IT BA. I {: f;it Ci.4i -`v A?',L'_ Fr) TY'f'f MINIMUM HANGER SIZES FOR ROUND DUCTS ['d b .T t',1 ". %'1P,11 1[:1 IRE 2" W.G. STATIC PO$. OR 1,111 r1[�- E.u7rT.• SF„cll1� r1�.t ;1r -rri ?f :> „1Ef 1u L.Ii J FI_IF' L-11_T t:.�.'_'L NI -1 I_I IINlI [rl _,. ' 7 III I_I P'IL .'_ �.1 f'l ll (I +.i :[ rl ll fl •'. : L1 >'� 1111 -- -* L' I?EOUIRED 12 r''iul_I I' n C)F' 1 11'Jf t rill unll ,,' III r_d''1L4 / rinn 1; 4 nun _` nl n aa" 12' T1,'vO 11:1 I,:, 1 „} t„ _ 1)., + 1 1 rnlr ? ri' T''','' 3 51 rilrr !; 4 rnr1; L :? - Sri 12' T�vl ! , d; B- 2t - t -.,- 'J� II I Illill I I'. I1,''rl_1 E I II111 - :+ J .l if II - .=t LI I II If TV's, 4"_ 7,. _ G3� 1«�, ------ ._. - - -- T'''ti ", .;,, I' -ru" 12, l_ y) D-_'U 1'e ",'_ I'. „;r+ I' 1•: ,,:I 17 i n rl i _..' rn l_ ct.; T'd';1:1 + ': nil i T';','. -, 2' 1 1 rr n 4" 1.2' T,;',; , ?J1J' r'v ",a ? 1; 0 rrlm -- r r r F 1c 1.6 i= lr� NOT DESIGNED '•11 iTE =, E 2_ E - ' F 'l1 ..H I ;.: [- I C' V E �4 L [= 2LI H _(, -I-1c" M I _,_, L IoH f_t _'r, L w _. H ''1!1.• f i- I •1_' F1 _ 1 STP1.F'- ,f'.rmE. ,''LVv,'j1C7. STEEL. RIO , °,PEiItK,:m,TEL1 :iK,I ::,L',i. 110El,:1TE> =L. Vvf:'E13LPL ;011, `,Idl'.,I',LF3_. DRN =HT 5s . :7.C:., C,R G.- .L\1At1 CET, `TFTI PI_L AREA,I TFT1,1 -`,TI'';.E, 2 1 LE.-`,LL +_ +'u''. FI_Ih; l.:II I'JF1'ITI'_'I'la.L 'r''dt'.LL THII- 1,111=: ,:_, i'IL, J.11111 r :r'i ti, I'_ I LI_I'_ 4E Lf .,,'-F U',:.1.1� -.1 1�,_if i t4_HI. N HE= , ;ikJ'LII II i' .I_,E 1,E'EIfI I,�LLtt,, ALL -U._r ti,L,t.p_IJ, ._L'E:: :� I +_,E+L- ','',1(NIPI IHEN�:L .'�L.1LU'rI: SF' "d= p.IGA,Ii BID NOTE THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS OTHER THAN 1 -0 IDENTIFY MODIFICATIONS OR EXTENSIONS THERETO. VISIT THE SITE AND ASCERTAIN THE EXISTING CONDIT IONS, REVIEW CONSTRUCTION DETAILS OF THE EXISTING PORTION OF THE BUILDING DURING THE SITE INSPECTION. INCLUDE ALL WORK REQUIRED TO REMOVE OR MODIFY PORTIONS OF THE EXISTING INSTALLATION IN ORDER TO ACCOMMODATE THE NEW WORK. FAILURE TO COMPLY WITH THIS WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF THE EXISTING INSTALLATION OR INSTALLING ANY NEW OR TEMPORARY WORK. COORDINATION NOTE AS PART OF THIS CONTRACT, THE SUB - CONTRACTOR AND THE CONTRACTOR ARE RESPONSIBLE FOR COORDINATION AND VERIFICATION THAT ALL EQUIPMENT, SHOWN IN THE ARCHITECTURAL DRAWINGS PARTICULARLY, BUT NOT LIMITED TO THE ARCHITECTURAL EQUIPMENT PLAN, INCLUDE ALL SERVICEIUTILITY REQUIRED TO OPERATE THE EQUIPMENT SHOWN. ANY DISCREPANCIES ARE TO BE POINTED OUT DURING THE BIDDING PROCESS. DISCREPANCIES NOT POINTED OUT DURING THE BIDDING PROCESS WILL BE RESOLVED BY THE CONTRACTOR AS PER THE ARCHITECT DETAILS AT NO ADDITIONAL COST TO THE OWNER. COORDINATION DRAWINGS 1. THE CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS TO ARCH. /ENG AND OWNER'S PROJECT MANAGER FOR APPROVAL PRIOR TO ANY FABRICATION AND INSTALLATION. 2, CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEW DUCTWORK, CONDUITS, LCT. WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL. AND ELECTRICAL SYSTEMS OF THE BUILDING. VERIFY ALL SPACE CONDITIONS AND DIMENSIONS AT JOBSITE PRIOR TO FABRICATION AND INSTALLATION OF EQUIPMENT AND MATERIALS. ANY CONFLICTS SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT /ENGINEER PRIOR TO BEGINNING OF CONSTRUCTION. F;,R6J. ,140. 43018w Q : w CA 4 w R w w u c •.• • rr +f t RuRR • w e LLOUIS J. AGLYHE & ASSOCIATES P.A. u U 'u CO SULTING ENGINEERS Q15e,w MTIa ;), DWLAND BLVD. SUITE: 900 MIAMI, FLORIDA 33156 TFLEPEIONF: (305) 670 --0141 " " 1 FAX,"'- (J� X10 -0144 w• wwVs,.Ijaapa.c0rT, ZL L -A C7 '� �< w 0. f a wx d z >j J; O 4A Q� d 1r S. I O cd I A z z0 r...� ...a < > Oz on W PERMIT SET DRAWN: i.e. CHECKED.•5. DATE; 04 -19 -2013 SCALE: A5 5HOLUN SEAL =� EDI,JARDO A' SUAREZ, P.E. LINSE •x 67x9' � Sheet No. ►1 IJOB # 21D13oi l RECTANGULAR DUCT REINFORCEMENT 2" W.G. STATIC PO$. OR 1,111 11C'1 [<A-1t 1_Ii- _E9':1EPd I r"'E t_IIF'FLI f E1dF + ?f :> „1Ef IT 1_OLt FI_IF' L-11_T t:.�.'_'L NI -1 1;:k1 drwlr. :Et,1Et 11 ' I' ;L.C:[1, - r_,pl r I 7' r11 1'.. _. L' I?EOUIRED I'll , 12 :'4 ;h B -?r) E' I: 6 wC r; 2I. E ail E- i E� 6 I.: 14 22 a_{ ,- - H-2 4 2-1 b I L :? t' 2t> r; E �; k' r`, B- 2t - t -.,- :il Q -t i : r; i= _' = 24 24 I.yl ri 711' 1r. tea. 1C; :A l_ y) D-_'U - -22 LI-2_ 1- 24 LI �4 1_ _IS L, e'' I -` _i_� l_ ct.; r,_:} F 1c 1.6 i= lr� NOT DESIGNED E -2 _i F -_u -1:. I-11; _ E 2_ E - ' F 'l1 ..H I ;.: [- I C' V E �4 L [= 2LI H _(, -I-1c" M I _,_, L IoH f_t _'r, L w _. H ''1!1.• f i- I •1_' F1 _ CI _'G I" :5 r." t ter: Li_ 2t LI- ill _ 1 -4 -E "4 F _4 ? F 4 E ?4 h� ° - 1,11' 1.� - -- [ 1 -. -. + -• -�w I L.':: F -..-4 1 :'4 7.a 111, ,, 1 :''r i L I� H F 1 u H BID NOTE THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS OTHER THAN 1 -0 IDENTIFY MODIFICATIONS OR EXTENSIONS THERETO. VISIT THE SITE AND ASCERTAIN THE EXISTING CONDIT IONS, REVIEW CONSTRUCTION DETAILS OF THE EXISTING PORTION OF THE BUILDING DURING THE SITE INSPECTION. INCLUDE ALL WORK REQUIRED TO REMOVE OR MODIFY PORTIONS OF THE EXISTING INSTALLATION IN ORDER TO ACCOMMODATE THE NEW WORK. FAILURE TO COMPLY WITH THIS WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF THE EXISTING INSTALLATION OR INSTALLING ANY NEW OR TEMPORARY WORK. COORDINATION NOTE AS PART OF THIS CONTRACT, THE SUB - CONTRACTOR AND THE CONTRACTOR ARE RESPONSIBLE FOR COORDINATION AND VERIFICATION THAT ALL EQUIPMENT, SHOWN IN THE ARCHITECTURAL DRAWINGS PARTICULARLY, BUT NOT LIMITED TO THE ARCHITECTURAL EQUIPMENT PLAN, INCLUDE ALL SERVICEIUTILITY REQUIRED TO OPERATE THE EQUIPMENT SHOWN. ANY DISCREPANCIES ARE TO BE POINTED OUT DURING THE BIDDING PROCESS. DISCREPANCIES NOT POINTED OUT DURING THE BIDDING PROCESS WILL BE RESOLVED BY THE CONTRACTOR AS PER THE ARCHITECT DETAILS AT NO ADDITIONAL COST TO THE OWNER. COORDINATION DRAWINGS 1. THE CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS TO ARCH. /ENG AND OWNER'S PROJECT MANAGER FOR APPROVAL PRIOR TO ANY FABRICATION AND INSTALLATION. 2, CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEW DUCTWORK, CONDUITS, LCT. WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL. AND ELECTRICAL SYSTEMS OF THE BUILDING. VERIFY ALL SPACE CONDITIONS AND DIMENSIONS AT JOBSITE PRIOR TO FABRICATION AND INSTALLATION OF EQUIPMENT AND MATERIALS. ANY CONFLICTS SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT /ENGINEER PRIOR TO BEGINNING OF CONSTRUCTION. F;,R6J. ,140. 43018w Q : w CA 4 w R w w u c •.• • rr +f t RuRR • w e LLOUIS J. AGLYHE & ASSOCIATES P.A. u U 'u CO SULTING ENGINEERS Q15e,w MTIa ;), DWLAND BLVD. SUITE: 900 MIAMI, FLORIDA 33156 TFLEPEIONF: (305) 670 --0141 " " 1 FAX,"'- (J� X10 -0144 w• wwVs,.Ijaapa.c0rT, ZL L -A C7 '� �< w 0. f a wx d z >j J; O 4A Q� d 1r S. I O cd I A z z0 r...� ...a < > Oz on W PERMIT SET DRAWN: i.e. CHECKED.•5. DATE; 04 -19 -2013 SCALE: A5 5HOLUN SEAL =� EDI,JARDO A' SUAREZ, P.E. LINSE •x 67x9' � Sheet No. ►1 IJOB # 21D13oi l