13-441-000I
COUNTY
FIRE ENGINEERING & WATER SUPPLY BUREAU
11805 SW 26 STREET, SUITE 150, MIAMI, FL. 33175
TELEPHONE (786) 315 -2771 EMAIL:
www. m iam idade. .,ov /mdfr
FIRE REVIEW DISAPPROVAL COMMENTS
DATE: 5/21/13 FD TRACKING NUMBER: M2013007588 REVIEWED BY: RICK GONZALEZ
NAME OF PROJECT: LARKIN COMMUNITY HOSPITAL 6T" FLOOR OFFICE RENOVATIONS
ADDRESS: 7000 SW 62 AVE 6T" FLOOR S. MIAMI, FL.
PROVIDE RESPONSE SHEET ADDRESSING EACH OF THE COMMENTS AND INDICATE THE SHEET
IN WHICH CORRECTION IS FOUND — IF NOT PROVIDED ORIGINAL FULL REVIEW FEE WILL BE
ASSESSED AGAIN
1. PROVIDE ORIGINAL APPROVED PLANS BY THE FIRE DEPARTMENT TO VERIFY COMPLIANCE WITH
ALL EXISTING CONDITIONS
2. STORAGE ROOMS #634, #647, AND #668 TO BE PROVIDED WITH A 1 HOUR FIRE RATED ENCLOSURE AND
45 MINUTE FIRE RATED DOORS WITH CLOSERS — SCT. 36.3.2
3. CLEAN SUPPLY ROOM #604 AND SOILED HOLDINGS ROOM #605 DOORS TO BE A MINIM,jk� F 45
MINUTE FIRE RATED WITH A CLOSER — SCT. 36.3.2 — (DOOR SCHEDULE ONLY SHOWS ' PE DOORS
WITH NO RATING IN MINUTES)
4. PROVIDE EXIT SIGNS AND EMERGENCY LIGHTS THROUGHOUT
5. INDICATE IF THERE IS AN EXISTING FIRE SPRINKLER AND / OR FIRE ALARM SYSTEM — IF SO PROVIDE
PLANS SHOWING THE LOCATION OF ALL NEW AND EXISTING HEADS AND DEVICES
6. ADDITIONAL COMMENTS MAY FOLLOW ONCE ALL INFORMATION IS PROVIDED
* ALL CODE REFERENCES MENTIONED IN THESE COMMENTS ARE FROM FFPC/NFPA, FLORIDA FIRE
PREVENTION CODE AND NFPA 101 LIFE SAFETY CODE, UNLESS OTHERWISE NOTED..
• PROVIDE NEW SHEETS WITH ALL CORRECTIONS AND CHANGES HIGHLIGHTED OR CLOUDED.
• RETURN VOIDED SHEETS WITH FIRE DEPT. STAMPS FOR COMPARISON, OR FULL REVIEW FEE WILL BE
ASSESSED
• COORDINATE ALL CORRECTIONS & CHANGES THROUGHOUT THE ENTIRE SET OF PLANS.
* PROVIDE ALL INFORMATION ON THE PLANS
* DROP OFF FOR REWORK
Department of Regulatory and Economic Resources
Miami -Dade County
Plan Review Summary
Process Number: M2013007588
FINAL CORE REVIEW DATE: 5/8/2013 OVERALL STATUS: Overall Disapproval
PROJECT DETAILS: CONTACT DETAILS:
FOLIO: 09 -4025- 000 -0591 NAME: JORGE FERNANDEZ
ADDRESS: 7000 SW 62 AVE, SOUTH MIAMI, F EMAIL:
PERMIT TYPE DESC.: INTERIOR RENOVATION PHONE #: 3057254522
DISAPPROVAL CODES:
Disapproval Code 01. 0294 - Requires Air Section approval for Asbestos. Contact the West Dade office at 11805
Coral Way
TASK REVIEWED BY STATUS DATE STATUS
Initial Core Review Jose Fnas 05/07/2013 Reviewed
Comments- INTERIOR RENOVATIONS FOR PROPOSED 10,949 SF MEDICAL CENTER REPLACING OFFICE
SPACE AT EXISTING OFFICE BUILDING /
Allocation letter 2013 - ALLOCATION -01417 on file / Approval granted for 10,949 sf medical center /
ASBES Review Anthony Hung 05/08/2013 Disapproved
Comments: A -1 Demolition interior partitions, existing floor finish, and ceiling tiles on sixth floor > 160 sf surface area
suspect ACMs. Submit an asbestos survey.
An asbestos survey from a Florida - licensed asbestos consultant, Florida Statutes 469.001 -015, is required when the
'surface area' being impacted by the proposed work is equal to or greater than 160 sq ft of suspect Asbestos
Containing Materials (ACM). An asbestos affidavit can be submitted for a conditional approval. The affidavit is an
agreement to perform an asbestos survey prior to the commencement of work, thus allowing your plan approval
process to continue. The asbestos survey should be available on site for the asbestos inspector. Regulated under
National Emission Standards for Hazardous Air Pollutants (NESHAP) 40 CFR 61, subpart M, section 145(a).
Asbestos Reviewer 786.315.2800, Appointments 786.315.2844 Mon -Fri 8am -12pm.
http: / /www.miamidade.gov/ development /pollution /asbestos.asp
INDUST Review Manny Diaz - Villamil 05/08/2013 Approved
Comments: Interior renovation on 6th floor Larking Community Hospital 7000 Building Office, as per plans. Images
taken by the x -ray equipment will be digitally processed, stored and viewed, as per plans. No wet x -ray film
processing as part of this project, as per plans.
Final Core Review Jose Fnas 05/08/2013 Overall Disapproval
Comments: Please do not hesitate to email me with any question(s) you may have regarding the review comments
for this project. While I may not respond immediately to your email — because I may be assisting another customer a�
the time I receive your email — I will reply within 24 hours of receiving your email unless I am out of the office. M/•
email address and that of my direct supervisor are as follows:
My Email- friasj @miamidade.gov
My Supervisor's Email GuerrCh @miamidade.gov
PLAN CONDITIONS:
NO CONDITIONS
PLAN REVIEW FEES (FEES ARE SUBJECT TO CHANGE PENDING FINAL APPROVAL):
FEE CODE DESCRIPTION USER DATE UNIT TOTAL
D034 FastTrack Fee ADMIN 05/02/2013 1 $80.00
D034R FastTrack Fee ADMIN 05/02/2013 1 ($80.00)
Total $0.00
FOR MORE INFORMATION PLEASE CONTACT:
YOUR DERM CORE REVIEWER. friasj @miamidade.gov
DERM PERMITTING AND INPECTION CENTER, 11805 SW 26 ST, 786 - 315 -2800
DERM OVERTOWN TRANSIT CENTER, 701 NW 1 CT, 305 - 372 -6899
Coastal: dermcr @miamidade.gov
EQCB: egcb @miamidade.gov
Specialty Engineering Reviews (industrial, storage tanks, industrial waste pretreatment, asbestos, paving
& drainage, trees): dermengreviews @miamidade.gov
Tree Permit applications: dermtreeprogram @ miamidade.gov
Water Control: dermwatercontrol @ miamidade.gov
Wetlands: dermwetlands @miamidade.gov
r
U