Loading...
13-441-000I COUNTY FIRE ENGINEERING & WATER SUPPLY BUREAU 11805 SW 26 STREET, SUITE 150, MIAMI, FL. 33175 TELEPHONE (786) 315 -2771 EMAIL: www. m iam idade. .,ov /mdfr FIRE REVIEW DISAPPROVAL COMMENTS DATE: 5/21/13 FD TRACKING NUMBER: M2013007588 REVIEWED BY: RICK GONZALEZ NAME OF PROJECT: LARKIN COMMUNITY HOSPITAL 6T" FLOOR OFFICE RENOVATIONS ADDRESS: 7000 SW 62 AVE 6T" FLOOR S. MIAMI, FL. PROVIDE RESPONSE SHEET ADDRESSING EACH OF THE COMMENTS AND INDICATE THE SHEET IN WHICH CORRECTION IS FOUND — IF NOT PROVIDED ORIGINAL FULL REVIEW FEE WILL BE ASSESSED AGAIN 1. PROVIDE ORIGINAL APPROVED PLANS BY THE FIRE DEPARTMENT TO VERIFY COMPLIANCE WITH ALL EXISTING CONDITIONS 2. STORAGE ROOMS #634, #647, AND #668 TO BE PROVIDED WITH A 1 HOUR FIRE RATED ENCLOSURE AND 45 MINUTE FIRE RATED DOORS WITH CLOSERS — SCT. 36.3.2 3. CLEAN SUPPLY ROOM #604 AND SOILED HOLDINGS ROOM #605 DOORS TO BE A MINIM,jk� F 45 MINUTE FIRE RATED WITH A CLOSER — SCT. 36.3.2 — (DOOR SCHEDULE ONLY SHOWS ' PE DOORS WITH NO RATING IN MINUTES) 4. PROVIDE EXIT SIGNS AND EMERGENCY LIGHTS THROUGHOUT 5. INDICATE IF THERE IS AN EXISTING FIRE SPRINKLER AND / OR FIRE ALARM SYSTEM — IF SO PROVIDE PLANS SHOWING THE LOCATION OF ALL NEW AND EXISTING HEADS AND DEVICES 6. ADDITIONAL COMMENTS MAY FOLLOW ONCE ALL INFORMATION IS PROVIDED * ALL CODE REFERENCES MENTIONED IN THESE COMMENTS ARE FROM FFPC/NFPA, FLORIDA FIRE PREVENTION CODE AND NFPA 101 LIFE SAFETY CODE, UNLESS OTHERWISE NOTED.. • PROVIDE NEW SHEETS WITH ALL CORRECTIONS AND CHANGES HIGHLIGHTED OR CLOUDED. • RETURN VOIDED SHEETS WITH FIRE DEPT. STAMPS FOR COMPARISON, OR FULL REVIEW FEE WILL BE ASSESSED • COORDINATE ALL CORRECTIONS & CHANGES THROUGHOUT THE ENTIRE SET OF PLANS. * PROVIDE ALL INFORMATION ON THE PLANS * DROP OFF FOR REWORK Department of Regulatory and Economic Resources Miami -Dade County Plan Review Summary Process Number: M2013007588 FINAL CORE REVIEW DATE: 5/8/2013 OVERALL STATUS: Overall Disapproval PROJECT DETAILS: CONTACT DETAILS: FOLIO: 09 -4025- 000 -0591 NAME: JORGE FERNANDEZ ADDRESS: 7000 SW 62 AVE, SOUTH MIAMI, F EMAIL: PERMIT TYPE DESC.: INTERIOR RENOVATION PHONE #: 3057254522 DISAPPROVAL CODES: Disapproval Code 01. 0294 - Requires Air Section approval for Asbestos. Contact the West Dade office at 11805 Coral Way TASK REVIEWED BY STATUS DATE STATUS Initial Core Review Jose Fnas 05/07/2013 Reviewed Comments- INTERIOR RENOVATIONS FOR PROPOSED 10,949 SF MEDICAL CENTER REPLACING OFFICE SPACE AT EXISTING OFFICE BUILDING / Allocation letter 2013 - ALLOCATION -01417 on file / Approval granted for 10,949 sf medical center / ASBES Review Anthony Hung 05/08/2013 Disapproved Comments: A -1 Demolition interior partitions, existing floor finish, and ceiling tiles on sixth floor > 160 sf surface area suspect ACMs. Submit an asbestos survey. An asbestos survey from a Florida - licensed asbestos consultant, Florida Statutes 469.001 -015, is required when the 'surface area' being impacted by the proposed work is equal to or greater than 160 sq ft of suspect Asbestos Containing Materials (ACM). An asbestos affidavit can be submitted for a conditional approval. The affidavit is an agreement to perform an asbestos survey prior to the commencement of work, thus allowing your plan approval process to continue. The asbestos survey should be available on site for the asbestos inspector. Regulated under National Emission Standards for Hazardous Air Pollutants (NESHAP) 40 CFR 61, subpart M, section 145(a). Asbestos Reviewer 786.315.2800, Appointments 786.315.2844 Mon -Fri 8am -12pm. http: / /www.miamidade.gov/ development /pollution /asbestos.asp INDUST Review Manny Diaz - Villamil 05/08/2013 Approved Comments: Interior renovation on 6th floor Larking Community Hospital 7000 Building Office, as per plans. Images taken by the x -ray equipment will be digitally processed, stored and viewed, as per plans. No wet x -ray film processing as part of this project, as per plans. Final Core Review Jose Fnas 05/08/2013 Overall Disapproval Comments: Please do not hesitate to email me with any question(s) you may have regarding the review comments for this project. While I may not respond immediately to your email — because I may be assisting another customer a� the time I receive your email — I will reply within 24 hours of receiving your email unless I am out of the office. M/• email address and that of my direct supervisor are as follows: My Email- friasj @miamidade.gov My Supervisor's Email GuerrCh @miamidade.gov PLAN CONDITIONS: NO CONDITIONS PLAN REVIEW FEES (FEES ARE SUBJECT TO CHANGE PENDING FINAL APPROVAL): FEE CODE DESCRIPTION USER DATE UNIT TOTAL D034 FastTrack Fee ADMIN 05/02/2013 1 $80.00 D034R FastTrack Fee ADMIN 05/02/2013 1 ($80.00) Total $0.00 FOR MORE INFORMATION PLEASE CONTACT: YOUR DERM CORE REVIEWER. friasj @miamidade.gov DERM PERMITTING AND INPECTION CENTER, 11805 SW 26 ST, 786 - 315 -2800 DERM OVERTOWN TRANSIT CENTER, 701 NW 1 CT, 305 - 372 -6899 Coastal: dermcr @miamidade.gov EQCB: egcb @miamidade.gov Specialty Engineering Reviews (industrial, storage tanks, industrial waste pretreatment, asbestos, paving & drainage, trees): dermengreviews @miamidade.gov Tree Permit applications: dermtreeprogram @ miamidade.gov Water Control: dermwatercontrol @ miamidade.gov Wetlands: dermwetlands @miamidade.gov r U