06-1923-0133 BATTERY CALCULATIONFOR 4TH FL(DOR CABINET -STANDBY SIGA -AA50 1 X 0.00100 = 0.00100 SIGA -AP S 1 X 0.07000 = 0.07000 SUM COLUMN FOR STANDBY LOAD = 0.071 ALARM SIGA -AA50 1 X 3.00000 - 3.00000 SIGA -APS 1 X 0.07000 0.07000 SUM COLUMN FOR LOAD IN ALARM = 1 3.070 TOTAL STANDBY LOAD ° "NUMS�� of p1%CES REQUIRED STANDBY TIME IN HOURS CURRENT (AMPS) - (24 OR 60 Hm) 0.071 X 24 = 1.70 ALARM LOAD REQUIRED ALARM TIME IN HOURS CURRENT (AMPS) 1 (15 MINUTES = 0.250) 3.070 X 0.250 = 0.77 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOUR BATTERY 2.47 MULTIPLY BY THE DERATING FACTOR OF 1.2 TOTAL AMPERE HOUR REQUIRED = 2.97 7.2 A/H PROVIDED F1I&? AUX%til SY:i'IEM 'r013 IN STALLED IN ACCORDANC E, WfI I I NPPA`r 10, 101 - n 111r,213 c .n'• NTIAIN1I- JI)ADE COUNTY FIItE DFP�VXFtk4EI '17 FIfl A!_sjlM.__._ /_.... -. r!ta" 51.,r''PN=S//3,,{CN 1'1,kjr` MA ROOF - FIRE ALARM PLAN /V BATTERY CALCULATION - STANDBY Ql"V1C1 TYpE ° "NUMS�� of p1%CES X = .CURRENT - xvTAL cu�Rt:nl 0.186 X 24 = 4.47 ALARM LOAD REQUIRED ALARM TIME IN HOURS MAIN CIRCUIT BOARD 1 X 0.075 = 0.07500 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOUR BATTERY 5.68 MULTIPLY BY THE DERATING FACTOR OF 1.2 2 -LCX 1 X 0.02000 - 0.02000 ,SIGA -278 18 X 0.00025 = 0.00450 SIGA -PS 177 X 0.00045 = 0.07965 SIGA -HRS 1 X 0.00045 = 0.00045 SIGA -SD 4 X 0.00045 - 0.00180 SIGA -CR 3 X 0.00010 = 0.00030 SIGA -CT1 2 X 0.00025 = 0.00050 SIGA -AA50 1 X 0.00100 = 0.00100 SIGA -CC 1 S 14 X 0.00022 = 0.00312 SUM COLUMN FOR STANDBY LOAD 4 X 0.25500 = 0.186 ALARM MAIN CIRCUIT BOARD 1 X 0.110 - 0.11000 0.186 X 24 = 4.47 ALARM LOAD REQUIRED ALARM TIME IN HOURS 2 -LCX 1 X 0.13000 X 0.13000 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOUR BATTERY 5.68 MULTIPLY BY THE DERATING FACTOR OF 1.2 SIGA -278 18 X 0.00040 - 0.00720 SIGA -PS 177 X 0.00045 = 0.07965 SIGA -HRS 1 X 0.00045 = 0.00045 SIGA -SD 4 X 0.00045 = 0.00180 SIGA -CR 3 X 0.00010 = 0.00030 SIGA -CT1 2 X 0.00040 = 0,00080 SIGA -AA50 1 X 3.00000 = 3.00000 SIGA -CC 1 S 14 X j 0.00010 = 0.00140 G4RF -37VM 2 X 0.23900 = 0.47800 G1RF -VM 4 X 0.25500 = 1.02000 SUM COLUMN FOR LOAD IN ALARM = 4.830 TOTAL STANDBY LOAD REQUIRED STANDBY TIME IN HOURS CURRENT (AMPS) (24 OR 60 Hrs.) 0.186 X 24 = 4.47 ALARM LOAD REQUIRED ALARM TIME IN HOURS CURRENT (AMPS) (15 MINUTES = 0.250) 4.8301 X 0.250 = 1.21 ADD STANDBY AND ALARM LOAD FOR REQUIRED AMPERE HOUR BATTERY 5.68 MULTIPLY BY THE DERATING FACTOR OF 1.2 TOTAL AMPERE HOUR REQUIRED = 6.81 12V10A) 11 A/H PROVIDED J J J " N ma JJ � • dC ( V, • y 0 LL W w Ln O Q ; 1=.s0M E� w w ( N ui a a w Li- c) L ui a REVIS ONS ACOMMENTS ADDRESSED BY ECENARRO 8/24106 2 COMMENTS ADDRESSED BY ECENARRO 9/11/06 0 3 COMMENTS ADDRESSED BY D.A.L. 9/20/06