06-1923-007FAN An m FIRE ALARM INSTALLATION & OPERATION NOTES: FIRE ALARM SEQUENCE OF OPERATION: ACTUATION OF ANY MANUAL PULL STATION, SMOKE DETECTOR, HEAT DETECTOR OR WATER FLOW SWITCH SHALL CAUSE THE FOLLOWING OPERATIONS TO OCCUR; 1. ACTIVATION OF ALL PROGRAMMED SIGNALCIRCUITS, ON FLOOR OF INCIDENCE AND FLOOR ABOVE AND BELOW. (IF MULTIPLE FLOORS & ALL COMMON AREAS) 2. LIGHT THE ASSOCIATED INDICATORS CORRESPONDING TOACTIVE SIGNAL CIRCUITS. 3. A GENERAL ALARM SHALL BE ANNUNICATED UPON ACTIVATION OF ANY PULL STATION, FLOW SWITCH, DETECTION DEVICE. ATROUBLE SIGNAL SHALL BE ANNUICATED UPON FAILURE OR REMOVAL OFA DETECTION OR MAUL DEVICE. A SUPERVISORY SIGNAL SHALL ANNUICATE ANY TAMPER, HVAC, OR DUCT DETECTOR ACTIVATION. 4. IF MULTIPLE FLOORS, EACH ELEVATOR LOBBY, HOISTEWAY, AND MACHINE ROOM SMOKE DETECTOR SHALL INITIATE AN ALARM CONDITION ON THE BUILDING AND RETURN ALL ELEVATORS TO THE PRIMARY OR ALTERNATE FLOOR OF EGRESS IN COMPLIANCE WITH ANSI ASME Al 7.1. ACCORDANCE WITH ANSI /ASME A17.1. 5. IN BUILDING WITH SPRINKLER SYSTEM, ACTIVATION OF ANY SUCH SYSTEM, LOW PRESSURE SWITCH OR VALVE TAMPER SWITCH SHALL CAUSE A SYSTEM SUPERVISORY ALARM INDICATION. 6. ANNUCIATION OF THE ACTIVE DEVICE AT THE FIRE ALARM CONTROL PANEL AND ANY ANNUCIATORS, IN MONITORED BUILDING, SEND A SIGNAL TO THE U.L. CENTRAL STATION FOR ALARM, TROUBLE, WATERFLOW AND SUPERVISORY CONDITIONS. FIRE ALARM SPECIFICATIONS: -ALL EQUIPMENT TO BE U.L. LISTED FOR FIRE SERVICE AND SHALL BE COMPATIBLE WITH THE SYSTEM BEING USED. SYSTEM IS TO BE POWER LIMITED. - SYSTEM TO BE CERTIFIED CENTRAL STATION AS PER NFPA -72. -FIRE ALARM PANEL SHALL BE LISTED FOR CENTRAL STATION SERVICE PER NFPA 72, 2002, UNLESS OTERWISE SPECIFIED. -THE FIRE ALARM PANEL MUST HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY THE SYSTEM MANUFACTURER AND ARTICLE 760 OF THE NATIONAL ELECTRICAL CODE. MINIMUM WIRE SIZE IS 8AWG FOR GROUND CONNECTION. (NOTE: PANEL NEUTRAL OR CODUIT FROUND IS NOT ACCEPTABLE). -ALL STROBE LIGHTS SHALL ACTIVE UPON INITIATION OFTHE GENERAL ALARM AND SHALL BE SYNCHRONIZED IN OPEN AREAS. ALL AUDIBLE SIGNALS SHALL HAVE THREE PULSE TEMPORAL PATTERN AND SOUND LEVEL SHALL BE AT LEASE 15 DBA ABOVE AMBIENT SOUND LEVEL AND HAVING A DURATION OF AT LEASE 60 SECONDS MEASURED 5 FT ABOVE THE FLOOR IN OCCUPIED AREAS. THE CONTRACTOR IS REQUIRED TO CERTIFY THE DBA LEVEL WITH AN APPOVED DBA METTER PRIOR TO THE CERTIFICATE OF OCCUPANCY. -FIRE ALARM CIRCUITS AND DEVICES SHALL BE CLASS "B ". cloudriS Jm w. -ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. AND N.E.C. 760. 3 - CONNECTIONS TO LIGHTS AND POWER SERVICE SHALL BE ON A EST -2 DEDICATED BRANCH CIRCUIT. THE CIRCUIT AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. THE CIRCUIT DISCONNECTING MEANS FR/-S--1 SHALL HAVE A RED MARKING AND BE ACCESABLE ONLY TO AUTHORIZED BPS10A PERSONNEL AND BE PER N.F.P.A. 72,2002 1 -THE FIRE ALARM PANEL IS PROVIDED WITH STANDBY BATTERY PER FIRE ALARM POWER SUPPLY N.F.P.A. 72 WITH 24 HOURS OF STANDBYAND 15 MINUTES OF ALARM (AS EST REQUIRED). SHOULD LOSS OF NORMAL 120VAC POWER OCCUR, FIRE ® ALARM PANEL WILL AUTOMATICALLY TRANSFER TO BATTERY. RACCR EST -A'CERTIFICATE OF COMPLETION'WILL BE PREPARED ANDA COPY S PROVIDED TO THE OWNER AND THE CITY FIRE RESCUE DEPARTMENT. G4RF -37VM -OWNER MANUALS, INSTALLATION INSTRUCTIONS, OPERATION 3� INSTRUCTIONS AND RECORD DRAWINGS SHALL BE AT THE SITE ON SPEAKER/STROBE WEATHERPROOF COMPLETION OF JOB AND FINAL ACCEPTANCE. EST INSTALLATION NOTES: L -ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED N.E.C. f ELECTRICAL TUBING AND SHALL BE SEALED WITH U.L. APPROVE FIRE EST STOP MATERIAL. QT\ 3 -COLOR CODING MAY NOT APPLY TO EXISTING WIRE. SIGA -278 (WIRE TO BE LABELED ACCORDINGLY.) 2 a WP PULL STATION WEATHERPROOF - CONDUIT SHALL BE A MINIMUM OF 1 /2" AND 40% FILL MAXIMUM. EST -SMOKE DETECTOR SHALL NOT BE LOCATED IN DIRECT STREAM OF Q SUPPLY AIR OUTLETS. CONTROL MODULE -TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE CONTROL 33 COMMUNICATOR. �T - ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC. SIGA -CT1 VERIFY EXACT LOCATIONS OF DEVICES AND WIRE ROUTING PRIOR TO 177 STARTING WORK. r A j MOUNTING REQUIREMENTS: EST - MANUAL PULL STATIONS TO BE INSTALLED AT 48" A.F.F. nH -MOUNT FIRE ALARM SYSTEM STROBES & HORN /STROBES AT 80" A.F.F. SIGA -HRS FROM BOTTOM OF DEVICE OR 6" BELOW CEILING. 4 (WHICH EVER IS LOWER) DUCT DETECTOR -SMOKE DETECTORS TO BE INSTALLED AS PER N.F.P.A. 72. WALL EST MOUNTED SMOKE DETECTORS SHALL BE MOUNTED 4" MINIMUM FROM RT CEILING WITH 12" MAXIMUM FROM CEILING. SIGA -TRM FIRE ALARM LEGEND cloudriS Jm w. 1 © FIRE ALARM CONTROL PANEL WITH (2 -LCX) SLC EXPANDER & (AA -50) AMPLIFIERS EST -2 EST 11 FR/-S--1 FIRE ALARM POWER SUPPLY BPS10A EST 1 �M,71 FIRE ALARM POWER SUPPLY BPS6A EST 1 ® REMOTE CABINET WITH SIGA -APS & SIGA -AA50 RACCR EST 170 S SPEAKER /STROBE G4RF -37VM EST 3 WP S SPEAKER/STROBE WEATHERPROOF 757 -8A -T EST 299 L STROBE ONLY G1RF -VM EST 18 FF PULL STATION SIGA -278 EST 2 a WP PULL STATION WEATHERPROOF 103-60 EST 14 C CONTROL MODULE SIGA -CC1S EST 2 �T SINGLE INPUT MODULE SIGA -CT1 EST 177 Z IS � MO KE DETECTOR SIGA -PS EST 1 nH HEAT DETECTOR SIGA -HRS EST 4 _ DUCT DETECTOR SIGA -SD EST 4 RT REMOTE TEST STATION SIGA -TRM EST 3 t_J CONTROL RELAY MODULE SIGA -CR EST 720 TOTAL DEVICES Q TOTAL SQUARE FOOTAGE IS 117,680 96 DETECTORS AND 94 MODULES PER SLC FIRE ALAI,,-I ,5 YS 1 E�41 TO 3E INSF - INACCORJ_)AI\CI:WfIII NPPA 7'_); ?x;101. J 1' Nlfl?.iNll -I)r .0E C011iN'!Y FICA: DSPiUt'lA IN'I' F!i{K �1JY Pi> J�Q (IJ,1 �}3 ;g;i1 Ex F. CEILING f{ SMOKE DETECTOR MINIMUM DISTANCE A/C DEFUSER AND /OR ))) 3' AWAY FROM DUCT FLOUORECENT LIGHT SMOKE DETECTOR MOUNTING DETAIL NOTE: DO NOT INSTALL A SMOKE DETECTOR IN DIRECT AIRFLOW DUCT FIRE ALARM WIRE LEGEND A = INITIATING 16-2 T.H.H.N. - F.P.L.P OR F.P.L.R. B = SIGNAL 2# 14 T.H.H.N. - F.P.LP OR F.P.L.R. C = SPEAKER18 -2 T.H.H.N. - F.P.L.P OR F.P.L.R. 2ND FLOOR - FIRE ALARM PLAN 80" A.F.F. OR 6" BELOW CEILING (WHICHEVER IS LOWER) STROBE OR HORN/STROBE F O a O E 0 PULL 48" A.F.F ADA HEIGHT REQUIRMENTS N.T.S. INSTALL NEW EST 2 FIRE ALARM CONTROL PANEL, BPS10A AND BPS6A POWER SUPPLIES, INITIATING AND SIGNALING DEVICES AS SHOWN ON PLANS AND RISER DIAGRAM. NOTE: THIS ►S NOT A SPRINKLED BUILD{NG 1 • v Y � ; a f ) a r c _ • u • D J • 7 ! • 1 Js � f _ ) FIRE PENETRATION DETAIL U\'ss I f, � :cam WL1051 1. PRE -RATED CONCRETE FLOORS OR BLOCK WALLS = MIN. 4-1/2" THICKNESS. 2. MAX. AREA OF OPENING = 288 SQ. IN., WITH A MAX. DIMENSION OF 24 ". METALLIC PIPE - A) STEEL PIPE - 8" DIAM. (OR SMALLER) SCH. 40 (OR HEAVIER) STEEL PIPE. B) CONDUIT - 4" DIAM. (OR SMALLER) EMT OR 6" DIAM. (OR SMALLER) STEEL CONDUIT. C) IRON PIPE - 8" DIAM. (OR SMALLER) CASTOR DUCTILE IRON PIPE. D) COPPER TUBING - 4" DIAM. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING. E) COPPER PIPE - 4" DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. NOTE: THE MAXIMUM NUMBER OF PIPES WITHIN OPENING IS 3. THE ANNUNLAR SPACE BETWEEN PIPES SHALL BE MIN. 1- 12 " AND A MIN. 1/2" BETWEEN PIPES AND EDGE OF OPENING. 3. FORMING MATERIAL (NOT SHOWN, OPTIONAL) - NOM. 1" THICK POLYURETHANE BACKER 4. FYRE- SHIELD - MIN. 1/2" THICKNESS MASTIC APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF THE WALL ASSEMBLY, foes ' � a U`WM 5 W � U W � Q J W � N C) o 0 0 REVISIONS: ACOMMENTS ADDRESSED BY ECENARRO 8/24/06 ACOMMENTS ADDRESSED BY ECENARRO 9/11/06 3 COMMENTS ADDRESSED BY D.A.L. 9/20/06 REGESTERED ENGINEER. SHANTILAL C. PATEL 954 - 962 -3765 P.E. 0028551 , FIRE PRQ jgg,T1, i F- NUMBER!, 71 V% F- 00214' 07/16/06 1 1/8 CENARRq D. N. 2 OF 10