Loading...
06-1923-003MIAMI DADE FIIRE RESCUE FIRE ALARM PRE- SUBIMITTAL CHECKLIST Designer to fill in and answer all items and provide Iocation1comments as appropriate. 32 YES NO N/A The FACP—an-d—aII s b panels in unoccupied rooms are protected with a smoke n detector. 34 It"a complete automatically activated system, there is at least 1 pull sta lion each floor or 2 for large buildings. I a�ITy ectrvate sys em, t��ravel dise of �eaeh a pull s{atimn �s ess / ✓ _ -- __ 35 than 200' and near all exits. All automatic initiating devices are shown and are located in accordance with 36 NFPA 72, the manufacturer's s ecifications,and accepted engineering ractices. _ All visible devices are placed per the tables in NFPA 72 and each strobe has it's 37 candela rating listed on the floor plan and riser. _ 38 All corridor spaced strobes are placed a maximum of 100' apart and wiithin 15' from ends of the corridor. V _- 39 _ All spaces meet the audible characteristics of NFPA 72 and NFPA 101. _ Walls, partition, racks, shelves and equipment which may block devices are shown 40 with their height indicated. Duct detectors or relays for duct detectors are shown on the floor plara and riser 41 for all systems over 2000 cfm. ,��� The fire pump is monitored for run, phase reversal & phase loss to _✓ a _ 42 continuously manned location, or the supervised fire alarms stern. 43 Elevator recall is connected to the fire alarm system. _ All interconnected fire alarm control panels are arranged to function ais a single 44 system and monitored for integrity er NFPA 72. All relays for automatic extinguishing systems are shown on the floor (plan and 45 riser. hood, sprinkler, FM200, etc.) —__ - -. The class and/or style is shown for all initiating device circuits, signal line circuit 46 and notification appliance circuits. The maximum number of each device type is provided for each IDC based on device load or each SLC, based on class and style, per NFPA 72 and t:he 47 manufacturer's specifications. The capacity of each power supply and circuits complete with individival device 48 current is specified for each fire alarm control panel and NAC panel The total footage to the last device including voltage drop calculations are 49 provided for each notification appliance circuit for each power supply. 50 The wattage tap is indicated for all speakers. _ 51 The wattage capacity and load is provided for each amplifier._ All load and draw calculations correlate with the provided spec sheets and the 52 device draw or available power is highlighted on the specification sheets. This system is an Local Fire Alarm System or a Proprietary Supervising Station 53 Fire Alarm System and is stated as such on the plan. (24 hours secondary power)_._ This system will be certificated or placarded as a Central Station Service Fire 54 Alarm System and is stated as such on the plans. (24 hours secondary power) This system is an "Existing Remote Supervising Station Fire Alarm Syrstem" as _ 55 stated on the plan and will be provided with( 24 hours of secondary. power . V This system includes Emergency Voice Evacuation and is provided wilth 15 56 minutes of secondary alarm power. _ This system is being provided back up power by an emergency generator and will 57 provide 4 hours of standby power plus the appropriate secondary alairm power. Battery calculations, detailed in chart form, showing all information rcequired per 56 NFPA 72 4.4.1.5.3.1 are provided for each back-up power supply. — 59 ,/ Designed by Q,VI Phoneg5 fJ' 3 I-� 15 60 Si nature �Qyi� LCiV — 61 62 _ Instructions are available on request Refer to the instructions for a line by line 63 clarification of the above items. F /Apresubmittal Rev.02/02/06 Page 2