07-1196-041r
4.
SPST N.O.
RELAY
I
a
208V -3 0
- - - - -,
7,5
HP
FAN SECTION
FROM LOAD SIDE OF EXH
FAN MAGNETIC MOTOR"
STARTER
--- _-- _-------- _-- ..-- - - - - -�
EXHAUST FAN
TE: CONTRACTOR TO VERIFY ROUTING REQUIREMENTS OF
E & LOW VOLTAGE WIRING FOR EF -1
L1
INTERLOCK CIRCUIT STARTS
BLOWER MOTORS FOR FC -1 THRU 3
TO PROVIDE 1007 MECHANICAL
INTERLOCK FOR EXHAUST AND
MAKE -UP AIR
SPST N.O.
208V -3 0 RELAY SPST N.C. RELAY
MOUNT SYSTEM MANAGER COIL M. BY E.C.
INSIDE MUA -1 CONTROL E
C
PANEL & SET COOLING TO C. B. T_ i Lo --------------------- Q
7E' F 507 RH &HEATING D.S.
TO 6 ' F -------- R --- - - - - -�
-,- COI
-__ R ------------------- - - - - -- - ----------- -
TO SMOKE DETECTOR
CIRCUIT, SEE DIAGRAM N
TYPICAL
208V -1 0
D".
COIL 120V -1 0
DPST N.Q. RELAY
BY E.C.
�l
D.S.
(1/2-
P
EXHAUST FAN/MUA\
\ij
120V -1 0
HP- 1 /FC -1
BAR
H P -3 FC--3
L
KITCHEN
EF -2
0
DISHWASHER HOOD
120V -1 0
HP- 2 /FC -2
DINING
EF -3
RESTROOMS
NOTE: CONTRACTOR TO VERIFY ROUTING REQUIREMENTS Of ALL
LOW VOLTAGE HIRING BETWEEN OUTDOOR AND INDOOR UNITS
1605 GENE AUTRY WAY
ANAHEIM, CA. 92805
TEL: 714 -634 -1771 IMA
FAX: 714- 634 -8880
E MAIL: systems@georgethaII.com CONTROL PANELS
A/C LOGIC AND CONTROL PANEL
KS
Izu -1 0
BY E.C.
TO HOOD ARE SUPPRESSION
SYSTEM INTERLOCK SWITCH
-__ - -.............. --------- - - - - --
FILTER SECTION
- ____-- .- .- _--- .- _- ___ -_ -_ -�
EF
SMOKE DETECTORS FU
INSTALLED BY THE ME,
CONTRACTOR, WIRED B
ELECTRICAL CONTRACT(
(TYP OF 3)
TO HOOD ARE SUPRESSION
SYSTEM INTERLOCK BY E.C.
(ACTIVATION OF "ANSUL" SYSTEM
SHUTS DOWN MUA -1, MUA -2
& FC -1 THRU 3
TO L'S ARE ALARM CONTROL
PANEL, (FIRE /LIFE SAFETY)
TO BUILDING FIRE ALARM
CONTROL PANEL
SMOKE DETECTOR WIRING DIAGRAM
SEE ELECTRICAL DRAWINGS
0.
(2) -116, IN CONDUIT FROM
r YV
P�TO REMOTE SENSORS
D.S. CC►]4
�
208V -3 0
20EV -3 0
d C.B.
a
E C.B.
E D .S.
\lj
77-77
_
•
•
20EV -3 0
it
208V -3 0
E C.B.
E C.B.
D.S.
E D.S.
3
3
<600>
MUA -1
(5) - 116, IN CONDUIT FROM
5000
REMOTE SENSORS
5000
� Q
MUA -2
(10) -116, IN CONDUIT FROM
1600
PQTD REMOTE SENSORS
1600
�
208V -1 0
D".
COIL 120V -1 0
DPST N.Q. RELAY
BY E.C.
�l
D.S.
(1/2-
P
EXHAUST FAN/MUA\
\ij
120V -1 0
HP- 1 /FC -1
BAR
H P -3 FC--3
L
KITCHEN
EF -2
0
DISHWASHER HOOD
120V -1 0
HP- 2 /FC -2
DINING
EF -3
RESTROOMS
NOTE: CONTRACTOR TO VERIFY ROUTING REQUIREMENTS Of ALL
LOW VOLTAGE HIRING BETWEEN OUTDOOR AND INDOOR UNITS
1605 GENE AUTRY WAY
ANAHEIM, CA. 92805
TEL: 714 -634 -1771 IMA
FAX: 714- 634 -8880
E MAIL: systems@georgethaII.com CONTROL PANELS
A/C LOGIC AND CONTROL PANEL
KS
Izu -1 0
BY E.C.
TO HOOD ARE SUPPRESSION
SYSTEM INTERLOCK SWITCH
-__ - -.............. --------- - - - - --
FILTER SECTION
- ____-- .- .- _--- .- _- ___ -_ -_ -�
EF
SMOKE DETECTORS FU
INSTALLED BY THE ME,
CONTRACTOR, WIRED B
ELECTRICAL CONTRACT(
(TYP OF 3)
TO HOOD ARE SUPRESSION
SYSTEM INTERLOCK BY E.C.
(ACTIVATION OF "ANSUL" SYSTEM
SHUTS DOWN MUA -1, MUA -2
& FC -1 THRU 3
TO L'S ARE ALARM CONTROL
PANEL, (FIRE /LIFE SAFETY)
TO BUILDING FIRE ALARM
CONTROL PANEL
SMOKE DETECTOR WIRING DIAGRAM
SEE ELECTRICAL DRAWINGS
0.
0,
r YV
•V•
D.S. CC►]4
C4��
OUTSIDE AIR
EXHAUST
w2
120V -1 0
120V -1 0 COIL
SPST N.O. RELAY
BY E.C.
E
D.S.
U p
EXHAUST FAN/-E-F\
120V-1 0 \��
120V -1 0 'COIL
SPST N.Q. RELAY
BY E.C.
E
D.S.
U p
EXHAUST FAN/-E-F\
3
GENERAL NOTES
1) ALL WORK AND EQUIPMENT SHAM COMPLY WITH THE LATEST
APPLICABLE CODE.
2) ALL FIELD CONDITIONS AND JOBSITE DIMENSIONS ARE TO
BE VERIFIED PRIOR TO THE COMMENCEMENT OF ANY WORK.
3) ALL WORK SHALL BE COORDINATED WITH OTHER TRADES.
4) THE LOCATION OF ALL ROOF PENETRATIONS SHALL BE
COORDINATED WITH THE ARCHITECTURAL AND STRUCTURAL
DRAWINGS.
5) THE LOCATION OF ALL CEILING AIR DISTRIBUTION DEVICES
SHALL BE COORDINATED WITH THE ARCHITECTS REFLECTED
CEILING PLAN AND LIGHTING PLAN.
i Al�C'N RACTOR
1 PROVIDE ALL LEVEL EQUIPMENT CURBS, RUNNERS AND
PLATFORMS TO INCLUDE SHEET METAL CAPS OR LEVELING OF
FACTORY CURBS.
2) PROVIDE ALL REQUIRED ROOFING, PATCHING, CUTTING,
HEADING, RATED SHAFTS, ACCESS DOORS, FURRING,
FLASHING AND PAINTING.
3) SIZE AND LOCATION OF ALL HVAC RELATED ROOF, WALL AND
CEILING PENETRATIONS TO BE COORDINATED WITH THE
MECHANICAL CONTRACTOR
1) PROVIDE ALL REQUIRED DRAINS, GAS, WATER & CONDENSATE
PIPING COMPLETE WITH APPLICABLE TRAPS & VALVES.
ELECTRICAL CCRTWOOR
1) SYMBOL
. LINE VOLTAGE WIRING, IN CONDUIT BY E.C.
---- - - - - -- - LOW VOLTAGE WIRING, IN CONDUIT BY E.C.
nE - ITEMS FURNISHED AND INSTALLED BY E.C.
E - ITEMS FURNISHED & WIRED BY E.C. AND
M INSTALLED BY MECHANICAL CONTRACTOR
ITEMS FURNISHED AND INSTALLED BY THE
PWMBIN SAL CONTRACTOR
LINE VOLTAGE CONDUIT AND
LINE VOLTAGE WIRING INCLUDING FINAL CONNECTIONS
3) FURNISH & INSTALL ALL LOW VOLTAGE CONDUIT AND
LOW VOLTAGE WIRING INCLUDING FINAL CONNECTIONS
(LOW VOLTAGE DEFINED AS 24 VOLT CONTROL WIRING)
4) FURNISH & INSTALL ALL FUSES, CIRCUIT BREAKERS AND
DISCONNECT SWITCHES
5) CONTACTORS, IN NAELLVOOLLLTAGE SNTA SS, STARTERS SWITCHES.
6) THE WIRING DIAGRAMS ARE SCHEMATIC, INTENDED TO SHOW
SEQUENCE AND METHOD OF OPERATION. ALL ELECTRICAL
WORK TO COMPLY WITH ALL LOCAL AND STATE CODES.
7) THE FINAL. CONNECTIONS TO EQUIPMENT TO BE RAN IN FLEXIBLE
CONDUIT (SEALTTIE OR EQUAL).
E) THERMOSTATS TO BE MOUNTED 0 + 48" AFF, REMOTE SENSORS
TO BE MOUNTED 0 + 78" AFF, U.N.O., (VERTICAL BOX)
9) ALL LOW VOLTAGE WIRING TO BE 114 GA. STRANDED, U.N.O.
BUILDING AIR BALANCE & PRESSURIZATION DATA
y••♦ •
r YV
•V•
l •
OUTSIDE AIR
EXHAUST
FC -1
I�I�.II.II�R11A►./.
4000
y
L V
*00 • • •
_
•
•
J • • L • Y
2200
<1800>
FC -3
KITCHEN
3000
2400
<600>
MUA -1
FC -1, 2 & 3
5000
0
5000
MUA -2
TYPE I HOODS
1600
0
1600
EF -1
MAIN HOOD
••,•
•Y••,
•••
•fi[.
DISH HOOD
Y•••
•
♦
-
-600
MIX a
0:006
60669
0 006
BUILDING AIR BALANCE & PRESSURIZATION DATA
AIR FLOW CHART
ffllT-
AW9, SEW
.PLY
OUTSIDE AIR
EXHAUST
FC -1
BAR
4000
1500
<2500>
FC -2
DINING
4000
2200
<1800>
FC -3
KITCHEN
3000
2400
<600>
MUA -1
FC -1, 2 & 3
5000
0
5000
MUA -2
TYPE I HOODS
1600
0
1600
EF -1
MAIN HOOD
-3982
EF -2
DISH HOOD
-1041
EF 3
RESTROOMS
-600
TOTALS
19600
6100
6600
-5623
6600 CFM OSA -5623 EXH = 977 CFM POSSITNE
NOTE: MUA -1 PROVIDES 5000 CFM OF PRE - CONDITIONED OUTSIDE AIR
TO OL FMC-1
OLFC -1 I AND BRACK SE QUANTITIES INDICATED IN THE OUTSIDE AIR
CUM�
NOTE:
FC -1 THRU 3 SHALL BE EQUIPPED WITH APPROVED TYPE SMOKE
DETECTORS INSTALLED IN THE UNITS RETURN AIR PLENUM. MUA -1
SHALL HAVE A SMOKE DETECTOR FACTORY INSTALLED IN THE UNITS
SUPPLY AIR PLENUM.
UPON DETECTION OF SMOKE FROM ANY SINGLE DETECTOR, A SIGNAL.
SHALL BE SENT TO LL'S FIRE / LIFE SAFETY WHEREBY AN ADDITIONAL
SIGNAL SHALL BE RETURNED TO THE A/C LOGIC AND CONTROL PANEL
SHUTTING DOWN ALL INDOOR SUPPLY AIR FANS. ALL DETECTORS
FOR FC -1 THRU 3 & MUA -1 SHALL BE FURNISHED AND INSTALLED,
(AS APPLICABLE), BY THE MECHANICAL CONTRACTOR. ALL DETECTORS
SHALL BE WIRED BY THE ELECTRICAL CONTRACTOR.
CITY OF SOt;TH MIAMI
BUILDMG DEFT,
MECHANICAL SECTION
APPROVED BY:
q �
/,TE: 1 • L�� �,,
CRO ENGINE - E NG
GROUP, INC.
18652 Florida Strut, Suite 150
Huntington Beach, CA 92648
F (714)847-7100
F (714 )841 -6000
� rl t. jai
n,
RA 5U5hI CORPORATION
5COTT5DALE, AZ
0 1 2 -22 -OG
0 REV15ION5
O
d
z
O
❑ 06. 15.07
15t LANDLORD 5UBMITTAL
❑ 08.21 .07
15t CITY SUBMITTAL
❑ 02.07.08
2nd CITY 5UBMITTAL
❑ DATE
5829 5W 73RD 5T
SOUTH MIAMI, FL
ISM ! .0
MECHANICAL
SCHEDULES �
DIAGRAMS
r