07-1196-001
I c:. r r _ FIRE ALARM INSTALLATION & OPERATION NOTES: FIRE ALARM SEQUENCE OF OPERATION: ACTUATION OF ANY MANUAL PULL STATION, SMOKE DETECTOR, HEAT DETECTOR OR WATER FLOW SWITCH SHALL CAUSE THE FOLLOWING OPERATIONS TO OCCUR; 1. LIGHT THE ASSOCIATED INDICATORS CORRESPONDING TO ACTIVE SIGNAL CIRCUITS. 2. A GENERAL ALARM SHALL BE ANNUNCCATED UPON ACTIVATION OF ANY PULL STATION, FLOW SWITCH, DETECTION DEVICE. A TROUBLE SIGNAL SHALL BE ANNUNCIATED UPON FAILURE OR REMOVAL OF A DETECTION OR MAUL DEVICE, A SUPERVISORY SIGNAL SHALL ANNUNCIATE ANY TAMPER, HVAC, OR DUCT DETECTOR ACTIVATION. 3. DUCT TYPE SMOKE DETECTORS SHALL, IN ADDITION TO ABOVE FUNCTIONS SHUT DOWN THE VENTILATION SYSTEM OR CLOSE ASSOCIATED CONTROL DAMPERS AS APPROPRIATE. 4. IN BUILDING WITH SPRINKLER SYSTEM, ACTIVATION OF ANY SUCH SYSTEM, LOW PRESSURE SWITCH OR VALVE TAMPER SWITCH SHALL CAUSE A SYSTEM SUPERVISORY ALARM INDICATION. 5. ANNUNCIATION OF THE ACTIVE DEVICE AT THE FIRE ALARM CONTROL PANEL AND ANY ANNUNCIATORS, IN MONITORED BUILDING, SEND A SIGNAL TO THE U.L. MONITORING CENTER FOR ALARM, TROUBLE, WATERFLOW AND SUPERVISORY CONDITIONS. FIRE ALARM SPEC IF]CA_TIONS: -ALL EQUIPMENT TO BE U.L. LISTED FOR FIRE SERVICE AND SHALL BE COMPATIBLE WITH THE SYSTEM BEING USED, SYSTEM IS TO BE POWER LIMITED. - SYSTEM TO BE REMOTE MONITORED AS PER NFPA -72. -FIRE ALARM PANEL SHALL BE LISTED FOR CENTRAL STATION SERVICE PER NFPA 72, 2002, SECT. 5 -2, UNLESS OTERWISE SPECIFIED. -THE FIRE ALARM PANEL MUST HAVE AN EARTH GROUND CONNECTION AS REQUIRED BY THE SYSTEM MANUFACTURER AND ARTICLE 760 OF THE NATIONAL ELECTRICAL CODE. MINIMUM WIRE SIZE IS 12 AWG FOR GROUND CONNECTION. (NOTE: PANEL NEUTRAL OR CODUIT FROUND IS NOT ACCEPTABLE). -ALL STROBE LIGHTS SHALL ACTIVE UPON INITIATION OF THE GENERAL ALARM AND SHALL BE SYNCHRONIZED IN OPEN AREAS. ALL AUDIBLE SIGNALS SHALL HAVE THREE PULSE TEMPORAL PATTERN AND SOUND LEVEL SHALL BE AT LEASE 15 DBA ABOVE AMBIENT SOUND LEVEL AND • HAVING A DURATION OF AT LEASE- 60_ ONDS-M ASURED 5 FT ABOVE P -AREA . THE CONTRACTOR IS REQUIRED TO CERTIFY THE DBA LEVEL WITH AN APPOVED DBA METTER PRIOR TO THE CERTIFICATE OF OCCUPANCY. _ -FIRE ALARM CIRCUITS AND_bEVICES SHALL'BE CLASS "B' -HVAC DUCT SMOKE DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM CONTROL PANEL AND SHALL ACTIVATE AN ALARM OR TROUBLE SIGNAL; AS REQUIRED. r -ALL WIRING AND CONDUIT TO CONFORM TO N.F.P.A. AND N.E.C. 760. - CONNECTIONS TO LIGHTS AND POWER SERVICE SHALL BE ON A DEDICATED BRANCH CIRCUIT. THE CIRCUIT AND CONNECTIONS SHALL BE MECHANICALLY PROTECTED. THE CIRCUIT DISCONNECTING MEANS SHALL HAVE A RED MARKING AND BE ACCESABLE ONLY TO AUTHORIZED PERSONNEL AND BE PER N.F.P,A. 721 - 5.2.5.2 -THE FIRE ALARM PANEL IS PROVIDED WITH STANDBY BATTERY PER N.F.P.A. 72 WITH 24 HOURS OF STANDBY AND 5 MINUTES OF ALARM (AS REQUIRED). SHOULD LOSS OF NORMAL 120VAC POWER OCCUR, FIRE ALARM PANEL WILL AUTOMATICALLY TRANSFER TO BATTERY. - A'CERTIFICATE OF COMPLETION' WILL BE PREPARED AND A COPY PROVIDED TO THE OWNER AND THE CITY FIRE RESCUE DEPARTMENT. -OWNER MANUALS, INSTALLATION INSTRUCTIONS, OPERATION INSTRUCTIONS AND RECORD DRAWINGS SHALL BE AT THE SITE ON COMPLETION OF JOB AND FINAL ACCEPTANCE. INSTALLATION NOTES: -ALL FIRE STOP PENETRATIONS SHALL BE MADE WITH APPROVED N.E.C. ELECTRICAL TUBING AND SHALL BE SEALED WITH U.L. APPROVE FIRE STOP MATERIAL. -COLOR CODING MAY NOT APPLY TO EXISTING WIRE (WIRE TO BE LABELED ACCORDINGLY.) - CONDUIT SHALL BE A MINIMUM OF 3/4" AND 40% FILL MAXIMUM. -TWO TELEPHONE LINES SHALL BE PROVIDED TO THE FIRE CONTROL COMMUNICATOR. -ALL FLOW, TAMPER, PIV AND BACKFLOW WILL HAVE MONITOR MODULES; FIRE PROTECTION SPRINKLER PUMP MONITORING. (3 POINTS) (A).FIRE PUMP RUN (B).FIRE PUMP FAIL (C).FIRE PUMP PHASE REVERSAL. -ALL DUCT DETECTORS WILL HAVE CONTROL MODULES OR RELAYS LOCATED WITHIN 3FT OF AHU FOR SHUTDOWN. REMOTE TEST SWITCH (CONNECTED TO EACH DETECTOR). LOCATIONS TO BE VARIFIED IN FIELD WITH MECHANICAL CONTRACTOR. - ROUTING OF THE FIRE ALARM SYSTEM CONDUIT IS DIAGRAMMATIC. VERIFY EXACT LOCATIONS OF DEVICES AND WIRE ROUTING PRIOR TO STARTING WORK. MOUNTING REQUIREMENTS: - MANUAL PULL STATIONS TO BE INSTALLED AT 48" A.F.F. -MOUNT FIRE ALARM SYSTEM STROBES, HORN AND SPEAKER / STROBES AT 80" A.F.F. FROM BOTTOM OF DEVICE OR 6" BELOW CEILING. (WHICH EVER IS LOWER) 1 -SMOKE DETECTOR SHALL NOT BE LOCATED WITHIN T OF SUPPLY AIR OUTLETS. -SMOKE DETECTORS TO BE INSTALLED AS PER N.F.P.A, 72. WALL MOUNTED SMOKE DETECTORS SHALL BE MOUNTED 4" MINIMUM FROM r CEILING WITH 12" MAXIMUM FROM CEILING. - i FIRE ALARM LEGEND COUNT SYMBOL DEVICE TYPE MODEL MANUFACTURE 1 HIS FIRE ALARM CONTROL PANEL OSi EDWARDS SYSTEM 1 P15 REMOTE POWER SUPPLY BPS6A EDWARDS SYSTEM 5 NO HORN/STROBE G1RF -HDVM EDWARDS SYSTEM 4� STROBE ONLY G1RF VM EDWARDS SYSTEM 1 ©STROBE ONLY WEATHERPROOF CS405 -AA T EDWARDS SYSTEM 3 FF MANUAL PULL STATION SIGA -273 EDWARDS SYSTEM 1 Fm] SIGNAL INPUT MODULE SIGA -CT1 EDWARDS SYSTEM 1 7 A/H PROVIDED SYNCHRONIZATION MODULE SIGA -CCIIS EDWARDS SYSTEM 1 O SMOKE DETECTOR SIGA -PS EDWARDS SYSTEM Is TOTAL DEVICES SCOPE OF WORK INSTALL NEW EST (QS1) FIRE ALARM CONTROL PANEL, (SPSGA) REMOTE POWER SUPPLY, INITIATING AND NOTIFICATION DEVICES AS SHOWN ON FLOOR PLAN AND RISER DIAGRAM. DEVICE NUMBER CURRENT PER DEVICE ISTA NDBY ALARM 13PS6A 75 mA 175 mA NOTIFICATION DEVICES x HIS 5 161 mA 0 mA 805 mA STR75 4 152 mA 1.1.5 0 mA 608 mA STR110 WP 1 248 mA 0 mA 248 mA TOT. CURR. RATINGS ALL DEV. line A,B,C 75 mA 1836 mA TOTAL CURR. CONVERTED TO AMPS 0.001 0.075 A 1.836 A NUMBER OF STANDBY HOURS (24 for NFPA) 24 Hr Multiply lines E & F Total standby AH 1.8 AH ALARM SOUNDING PERIOD /HOURS 5 MIN= _0833 HRS M�05 0.0833 Hr MULTIPLY LINES E & H 0.152939 AH ADD LINES G i 1 1.952939 AH 7 A/H PROVIDED MULTIPLY LINE J BY 1.20 (20% EXTRA FOR DESIRED PERFORMANCE (1.2 Derating Factor) 2.343527 AH F1Rr%T A PA"%E r t FIRE PENETRATION DETAIL 1. PRE -RATED CONCRETE FLOORS OR BLOCK WALLS = MIN. 4 -112" THICKNESS. 2. MAX. AREA OF OPENING = 293 SQ. IN., WITH A MAX. DIMENSION OF 24 ". METALLIC PIPE - A) STEEL PIPE - i" DIAM. (OR SMALLER) SCH_ 40 (OR HEAVIER) STEEL PIPE. B) CONDUIT - 4" DIAM. (OR SMALLER) EMT OR G" DIAM. (OR SMALLER) STEEL CONDUIT. C) IRON PIPE - S- DIAM. (OR SMALLER) CAST OR DUCTILE IRON PIPE. D) COPPER TUBING - 4" DIAM. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING. E) COPPER PIPE - 4" DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. NOTE: THE MAXIMUM NUMBER OF PIPES WITHIN OPENING IS 3. THE ANNUNLAR SPACE BETWEEN PIPES SHALL BE MIN. 1-1/2"AND A MIN. 1/2' BETWEEN PIPES AND EDGE OF OPENING. 3. FORMING MATERIAL (NOT SHOWN, OPTIONAL) - NOM. 1 "THICK POLYURETHANE BACKER. 4. FYRE - SHIELD -MIN. 112" THICKNESS MASTIC APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF THE WALL ASSEMBLY. STROBE OR HORN /STROBE F Q 80" A.F.F. OR R O 6" BELOW CEILING F O (WHICHEVER IS LOWER) I PULL 48" A.F.F ADA HEIGHT REQUIRMENTS N.T.S. CEILING I= SMOKE DETECTOR MINIMUM DISTANCE A/C DEFUSER AND / OR Y AWAY FROM DUCT FLOUORECENT LIGHT SMOKE DETECTOR MOUNTING DETAIL NOTE: DO NOT INSTALL A SMOKE DETECTOR IN DIRECT AIRFLOW DUCT FIRE ALARM WIRE LEGEND WIRE SYMBOL WIRE TYPE ------- " -- ---- (A) INITIATING (16 -2 T.H.H.N. - FPLP OR FPLR) 1.2.5 (B) SIGNAL (2#e 14 T.H.H.N. - FPLP OR FPLR) FIRE ALARM RISER DIAGRAM SHANTILAL C. PATEL (954) 327 -9475 f7, P.E. 0028551�r�rrrrr�s, 1.2.3 1.2.4 1.2.5 1.2.1 1.22 75cd 75cd 75cd 75cd 75cd EOL J 0.737A DATE: SCALE: 1.1.4 1.1.5 1/8 1.1.1 1.1.2 1.1.3 75cd 75cd D. 75cd 75cd 110cd OF I �J 0.874A WP P/S FACP 0A) D01 M02 M�05 BPS6A jM0033 JM0044 — (QS1) M01 L�jl 1#12 1 11112 �_ _ THHN _ 1A ___ _ I T """ DEDICATED PHONE LINES ■ �41 � .. �� q ■~A H N •. 2 r n M> In n [It ENtW VQ 2tJm 0 , one IoM 3ao d)5 117 -11Lm law Iftft u LjVAN" Fl�ft_ cl)r►� A ■ X U M. . 'W of CL REVISIONS: LICENSED ENGINEER: SHANTILAL C. PATEL (954) 327 -9475 f7, P.E. 0028551�r�rrrrr�s, FIRE PRQV CTI(OPj r' ►r� ,'f j ♦ t Li ior / ♦„ i F- NUMBER: F -00334 DATE: SCALE: 10/26 07 1/8 DRAWN BY: CHECKED BY: D. B. P. OF I