07-562-0221. FIRE ALARM SYSTEM SHALL BE U.L. LISTED NFPA 72 APPROVED.
2. UPON ACTIVATION OF FIRE ALARM SYSTEM BY MANUAL STATION,
THE FOLLOWING SHALL TAKE PLACE:
A ENERGIZE ALARM SIGNALING DEVICES
B SOUND AUDIBLE ALARMS AND FLASH VISUAL SIGNALS
C ALERT LOCAL FIRE DEPARTMENT OR PROPRIETARY SYSTEM
D CAUSE ZONE IN ALARM TO BE DISPLAY ON THE ANNUNCIATOR
3. ALL WIRING AND CONDUCT SIZE SHALL BE IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS AND
REQUIREMENTS OF NEC, LOCAL CODES AN6 NFPA IN NO CASE.
SHALL THE WIRING BE SMALLERTHAN • 16.
4. ALL CONDUCTORS SHALL BE COOPER AND SHALL BE SIZED FOR A
MAXIMUN LOSS OF IdB. MINIMUM WIRE SIZE SHALL BE AS REQUIRED
BY MANUFACTURER IN NO CASE. SHALL THE WIRING BE SMALLER THAN
• 16 F.P.L. CU IN. 3/4 CONDIUT.
5. QUANTITY OF WIRES PER DEVICES SHALL BE AS REQUIRED
BY MANUFACTURER.
6. RISER INTERCONNECTIONS ARE DIAGRAMMATIC ONLY.
7. SYSTEM TO BE POWER LIMITED.
arm Plan- 2nd Level
Existing Areas
:)f this Project Scope
8. VISUAL ALARMS PER ANSI A 117.1,4.26, AND A.D.A.
9. ACTIVATION OF SMOKE DETECTOR IN ANY ELEVATOR LOBBY OR ASSOCIATED
ELEVATOR MACHINE ROOM 0 tHER THAN AT THE DESIGNATED LEVEL, SHALL
Fire Alarm S y m b o I
Legend
CAUSE ALL CARS THAT SERVE THAT LOBBY TO RETURN NON -STOP TO THE
DESIGNATED LEVEL. THE OPERATION SHALL CONFORM TO THE REQUIREMENTS
OF RULE 211.3a OF ASME /MISIA17.1 -1987 AS ADOPTED BY CHAPTER
(E)
INDICATES EXIST. TO REMOVE
L
ADA STROBE NOTIFIER • S 1224 SERIES
4A -47 OF THE DEPARTMENT OF INSURANCE, STATE FIRE MARSHALL.
PHOTOELECTRIC SMOKE DETECTORS
(SEE FLOOR PLANS FOR CANDELA
REQUIREMENTS)
NO DEVICE, OTHER THAN PHASE ISWITCH (RULE 221.3a) OR THE DETECTOR
NOTIFIER • FSP - 851
IN THE LEVATOR LOBBY RO ASSOCIATED MACHINE ROOM SHALL INITIATE
PULL STATION NOTIFIER • - - NBG 12 LX
PHASE IOPERATION.
�_.
DUCT SMOKE DETECTOR NOTIFIER
IF THE SMOKE DETECTOR AT THE
THE DESIGNATED LEVEL IS ACTIVATED
FSD -751P WITH SAMPLING TUBES
ELEVATOR WARNING LIGHT "DO NOT USE"
THE CARS SHALL RETURN TO AN ALTERNATE LEVEL APPROVED BY
W
O
HEAT DETECTOR NOTIFIER • FST - 851
•
SPACE AGE SSU-0062
ENFORCING AUTHORITY, UNLESS THE PAHSE ISWITCH (RULE 221.3a)
IS IN THE ON POSITION.
(13710 LP — BASE)
H
ADA HORN /STROBE NOTIFIER • P1224•
FACP FIRE ALARM ADDRESSABLE PANEL
SERIES (SEE FLOOR PLANS FOR
10. SMOKE DETECTORS TO BE MOUNTED 3FTMINIMUM FROM ANY A/C DIFUSSER.
FACP
• AFP -200 PROVIDED WITH (2) LINE DIALER,
CANDELA REQUIREMENTS)
POWER SUPPLIES BATTERIES, ETC., AS
11. CONTRACTOR
DSSRALEDNSI A FLORIPROVIDINGER D ENGINE PERMIT DRAWINGS
REQIRED. PROVIDE "LCD' REMOTE
ANNUNCIATOR LCD 80".
4
Fzz1T-
�
- -
, r ..y
L :B i?l.
BROCKHOUSE�
BROCKHOUSE ASSOCIATES PA
1570 MADRUGA AVENUE PH 1
CORAL GABLES, FL. 33146
305 666 2333 ■ FAX 666 2332
AR 10682 AA 0002456
BRUCE BROCKHOUSE
ARCHITECTURE ■ INTERIOR DESIGN
PROJECT
A Renovation
For The:
THE CENTER FOR
ARTHRITIS AND
RHEUMATIC DISEASES
6150 Sunset Drive
South Miami, FI 33143
305 661 2299
SEAL
v
VV •�
K,
4- T�
FIRE ALARM PLAN
2ND LEVEL
SHEET TITLE
03027- faldgn
SHEET TITLE REFERENCE
9 5 L DESIGNS.
D
FOR USE ON, AND IN CONJUNCTION WITH, THE SPECIFIED
PROJECT. NONE OF SUCH IDEAS, DESIGNS. ARRANGEMENTS
OR PLANS SHALL BE USED BY OR DISCLOSED TO ANY PERSON.
FIRM OR CORPORATION FOR ANY PURPOSE WHATSOEVER
WITHOUT THE WRITTEN PERMISSION OF:
BROCKHOUSE ASSOCIATES, PA.
REVISION
DESIGNED BY
B.A.
DRAWN BY
B.A.
APPROVED BY
M.W.
DATE 5 -17 -05
SCALE 1/4"= 1 I -oil
PROJECT N0. 03027
SHEET N0.
FA.2