07-562-019General EIEDctrical Notes
1.
ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL
13.
ALL CONDUCTORS SHALL BE COPPER.
CON
DUIT
ELECTRICAL CODE, FLORIDA BUILDING CODE AND OTHER
REMARKS
CKT.
NO.
CKT.
NO.
APPLICABLE CODES AND STANDARDS.
14.
ALL MATERIALS SHALL BE U.L. APPROVED.
2.
THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD
15.
NEW TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER
JOB IS COMPLETED REFLECTING ALL CHANGES AND ADDITIONS.
2
CONDITIONS BY VISITING THE SITE PRIOR TO COMMENCING/
Ya"
8
EXISTING AHU (_)
BIDDING WORK.
16.
ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
3.
THE CONTRACTOR SHALL SATISFACTORLY REPAIR/ REPLACE
17.
CONTRACTOR SHALL SEAL FLOOR CPENINGS WITH A FIRE SEAL SIMILAR
31120
EQUIPMENT OR PART OF STRUCTURE DAMAGED AS A RESULT OF HIS
2
TO 'OZ' FLAMESEAL.
1
WORK. SURFACES AND FINISHED AREAS SHALL BE RESTORED TO
12
EXISTING CKT
MATCH ADJACENT AREAS.
18.
ALL NON- POWER RELATED WIRING IN CEILING AIR CONDITIONING
12
1/2"
20
PLENUM RUNNING WITHOUT CONDUIT SHALL BE TEFLON COATED
4.
APPROVAL SHALL BE OBTAINED FROM THE ENGINEER PRIOR TO
CLASSIFIED FOR USE IN PLENUMS.
CUTTING OR DRILLING ANY STRUCTURAL SUPPORT MEMBER.
19.
ALL EMPTY CONDUIT TO BE PROVIDED WITH NYLON PULL STRINGS.
5.
ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS
EXISTING CKT
12
1/2"
RUN CONCEALED IN FINISHED AREAS EXCEPT AS SPECIFICALLY
20.
FUSES SHALL BE DUAL ELEMENT, TIME DELAY UNLESS OTHERWISE NOTED.
SHOWN /NOTED OTHERWISE.
6.
ALL ELECTRICAL EQUIPMENT SHALL BE REMOVED FROM STRUCTURE
21.
CONTRACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN
TO BE REMOVED. ACCESSIBLE RACEWAYS, WIRES, BOXES,
ORDER TO FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL
POWER CONTROL CIRCUITS WIRING AND RACEWAYS AS SHOWN ON THE
10
SWITCHES AND OTHER ELECTRICAL ITEMS ASSOCIATED WITH THIS
AIR CONDITIONING DRAWINGS OR SPECIFICATIONS. IF AIR CONDITIONING
WORK SHALL BE REMOVED IF NOT REQUIRED FOR NEW EQUIPMENT
TO CONTINUE IN SERVICE.
DRAWINGS REFER TO MANUFACTURER'S WIRING DIAGRAMS, THE CONTRACTOR
SHALL VERIFY WITH SAID MANUFACTURER ALL REQUIREMENTS AND INCLUDE ALL
7.
WIRE SHALL BE REMOVED BACK TO SOURCE FROM INACCESSIBLE
EXISTING CKT
RELATED WORK IN HIS CONTRACT.
1/2"
RACEWAYS NOT REUSED. INSTALL BLANK PLATES IN FLUSH
1
1,000
1,000
OUTLETS NOT REUSED. PLATE COLOR SHALL MATCH ADJACENT
SURFACE AS NEAR AS POSSIBLE IN FINISHED AREAS.
22.
ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE
CEILING SYSTEM MANUFACTURER RE COME NDATIONS AND LOCAL CODE
REQUIREMENTS.
8.
MODIFY AND REROUTE EXISTING WIRING AS REQUIRED TO
ACCOMPLISH INDICATED WORK AND CONTINUE SERVICE TO LOADS
23.
RISEN ARE DIAGRAMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED
BEYOND AREA IN WHICH WORK IS DONE.
FOR THE INSTALLATION.
9.
INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL
COMPONENTS FOR AIR CONDITIONING SYSTEMS AS SHOWN /NOTED
24.
THIS DRAWING IS A GUIDE FOR THE INSTALLATION OF ELECTRICAL SERVICE.
ON THESE DRAWINGS AND PER OTHER APPLICABLE DRAWINGS/
THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING
16
INSTRUCTIONS. SEE AIR CONDITIONING DRAWINGS.
SYSTEM.
10.
ALL MATERIAL REMOVED SHALL BE DISPOSED OF AS DIRECTED
25.
ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT OTHERWISE INDICATED_
BY OWNER.
700
500
26.
ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES.
11.
ALL WIRING INDICATED AS EXISTING IS BASED ON ORIGINAL
CONTRACT DRAWINGS AND IS TO BE VERIFIED BY CONTRACTOR AT
27.
EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD.
18
JOB SITE.
28.
ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
12.
WIRE SIZE SHALL BE # 12 THHN /THWN UNLES OTHERWISE NOTED IN PLANS.
1,200
500
CONDUCTOR 6 AND LARGER SHALL BE THW.
\ \1 F.1 �'r;
ELECTRIC
CHECK NA111 OT WATER I i',': \'i FR
EQIPMENT,
U
U1I'yIENT TO Oii`I "; \Ir!
AND OTHER E Q
CORRECT IRE SI ZES P,N1?
PROTECTION.
20
OVERCURRENT
.AD UA F VCAIIIAC- l'i' "SUBJECT TO
BE PROVIDET)
SUT3.IECTT0 EI.ECFRICA1 FIELD INSPECTION"
INSPECI'Inr!
EXIST
PNL
„c,►
3rd Floor
existing 4 *1/0 - 2" C
to a 3P - 150A BKR
Partial Electrical Riser Diagram
N.T.S.
a
VOLTAGE 120/208V, 30, 4W
TYPE _ EXISTING PANEL "C" BUS 150A
MAIN M.L.O. LOAD 33.8 KVA / 360V = 93.9 A
LOAD
POLE
TRIP
CON
DUIT
IRE
REMARKS
CKT.
NO.
CKT.
NO.
REMARKS
WIRE
CON
DUIT
' TRIP
POLE
LOAD
4,160
2
40
Ya"
8
EXISTING AHU (_)
EXISTING CU (_)
10
Ya"
30
2
31120
3
2
1,000
1
20
1/2"
12
EXISTING CKT
5
6
EXISTING CKT
12
1/2"
20
1
720
1,0
00
,00
7
8
EXISTING CKT
12
1/2"
20
2
2,000
9
10
700
11
12
EXISTING CKT
12
1/2"
20
1
1,000
1,000
13
14
700
1,200
15
16
700
500
17
18
1,200
500
19
20
1,200
2,000
2
20
%2"
12
EXISTING CKT
21
22
1,000
23
24
700
800
1
20
%2"
12
NEW LIGHTS
25
26
NEW ROOF REC
12
1/2"
20
1
200
10,707
2
70
11 /4"
4
NEW AHU {_)
27
28
NEW CU {_)
6
1"
45
2
4,430
29
30
NOTES: (_) NON. CONCURRENT LOADS.
FB7ROCKHOUSE
BROCKT-IOUSE ASSOCIATES PA
1570 MAI7RUCJA AVF_NIJE PI-11
i CORAL CiA13Lh'S, 1,'L. 33146
305 666 2333 ■ FAX 666 2332
J
1! �1
ARGHTECTURE
PROJECT
A Renovation
For-The:
THE CENTER FOR
ARTHRITIS AND
RHEUMATIC DISEASES
6150 Sunset Drive
South Miami, FI 33143
305 661 2299
SEAL
• �. r
�kA.liv Q : ua
Q ,r
• .``�1' -•IAN• .• � r'i 1
I INNOVATIVE
E ENGINEERING
GROUP, INC.
SUDHIR K. GUPTHA
P-E. # 29189
5532 N.W. 72 AVE. MIAMI, FLORIDA 33166
305- 888 -9626
SHEET TITLE
ELECTRICAL
SCHEDULES, NOTES,
& DETAILS
SHEET TITLE REFERENCE
03027- elecdet.dgn
ALL CONCEPTS. DESIGNS. ARRANGEMENTS. DRAWINGS AND
SPECIFICATIONS ARE OWNED BY, AND ARE THE PROPERTY OF
THIS OFFICE AND WERE CREATED, EVOLVED AND DEVELOPED
FOR USE ON, AND IN CONJUNCTION WITH. THE SPECIFIED
PROJECT. NONE OF SUCH IDEAS. DESIGNS. ARRANSE:ENTS
OR PLANS SHALL BE USED BY OR DISCLOSED TO ANY PERSON.
FIRW OR CORPORATION FOR ANY PURPOSE WHATSOEVER
WITHOUT THE WRITTEN PERIIISSIM OF:
BROCKHOUSE ASSOCIATES, PA.
REVISION
DESIGNED BY
S.A.
DRAWN BY
B.A.
APPROVED BY
L. C.
DATE
-x._05
SCALE AS NOTED
PROJECT NO. 03027
SIIFET NO.
r-
Fs2