07-562-017i SOLDER OR "SILFOSS." 15. PIPE INSULATION: CONDENSATE PIPING AND REFRIGERANT SUCTION PIPING SHALL BE INSULATED WITH %A" FIRE RATED FLEXIBLE FOAM INSULATION, FINISHED, WHERE EXPOSED WITH 2 COATS OF ACRYLIC LACQUER IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. strut strop hanger refrigerant liquid line secure w/ plast to insulation adjust this dimension -) in field as required insulation refrigerant suction END VIEW Jlut vltw Typical Refrigerant Piping Hanger Detail N.T.S. refrigerant liquid line - efrigerant hot gas line waddle saddle support J L -1/4" W. (min.) sheet metal - damper supply branch- duct -main duct AIR FLOW AIR FLOW �o so pivot costing (typ. *\-adjusting � rod condensing unit E pitch pan N steel plate bolted to roof 114" stainless steel turnbuckle (typ.) w/ wire rope clamp. Yr," stainless steel cable (typ. of 2) -bolt w /nut to secure unit to withstand winds up to 150 mph • spring isolators or isomode pod at each corner of unit (size as per manufacturer's recommendations) steel angle 4 x 4 x 1/4 R weld to support column & channel 3" dia. support column / ^° built -up roof deck & insulation (refer to Architect's drawings) beam or other support structure Air Cooled Split A/C Unit Schedule HVAC General Notes: support from _ SEE PLAN 22. ALL OUTSIDE EQUIPMENT SHALL BE SECURED TO WITHSTAND 150 M.P.H. WINDS. 6. ALL AIR CONDITIONING SUPPLY DUCTWORK SHALL BE EXTERNALLY structure RHEEM AIR v INSULATED WITH MINIMUM 1 -1/2" THICK, %ALB DENSITY (R-6) FIBERGLASS - -air handling unit 'Titus' 3-FL BLANKET COVERED WITH FLAMEPROOF REINFORCED ALUMINUM FOIL 23. ALL FAN DRIVES SHALL BE ADJUSTED TO DELIVER THE SPECIFIED FACED PAPER OR VAPOR SEALED. (mount as high 1. THE WORK TO BE DONE UNDER THIS HEADING INCLUDES THE 16. FLAME AND SMOKE RATING= ALL INSULATION PRODUCTS USED INSIDE External Static Pressure In. of H2O AIR DUCTS 15' -0" FROM UNIT CONNECTIONS WITH 1" THICK 3 LB DENSITY SELECTOR SWITCHES ON SUBBASE. MOUNT ON WALL WHERE SHOWN as possible) 1 / 3 / 3.4 FURNISHING OF ALL LABOR, MATERIALS, EQUIPMENT, PERMITS, THE BUILDING SHALL HAVE A MAXIMUM FLAME SPREAD RATING OF 25 Electrical Service Available KEY LOCK PLASTIC GUARDS. 8. PROVIDE ALTERNATE BID FOR ALL AIR CONDITIONING SUPPLY AND RETURN -- spring type vibration isolator (typ: at each - FEES, INSPECTIONS, TESTS, INSURANCE, ETC. REQUIRED FOR DUCTWORK TO BE CONSTRUCTED OF 1 -1/2" THICK (R -6) STANDARD DUTY AND A MAXIMUM SMOKE GENERATION OF 50 IN ACCORDANCE WITH %" threaded rod (typ.) or as FIBERGLASS BOARD WITH REINFORCED FLAMEPROOF ALUMINUM FOIL FACED mounting point) THE COMPLETION OF THE HVAC SYSTEM SHOWN ON DRAWINGS 46,500 TESTS OUTLINED IN N.F.P.A. 255. recommended by mfgr. BE FABRICATED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND Total Sensible Capacity BTU /HR. 24 HRS. AFTER TESTING EVACUATE SYSTEM TO 28" OF MERCURY -- refrigerant pipes - AND /OR LISTED BELOW. 17. VERIFY ALL VOLTAGES WITH ELECTRICAL CONTRACTOR BEFORE nut & washer (typ.) Q PUMP OFF. BREAK VACUUM WITH OPERATING REFRIGERANT. 9. - -- condensate drain w/ trap (see plumb. drwgs. or hvoc drwgs) 2. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST ORDERING ANY EQUIPMENT. angle clip (typ.) EDITION OF THE FLORIDA BUILDING CODE AND ALL LOCAL CODES. 18. SUBMIT SHOP DRAWINGS OF ALL MATERIALS AND EQUIPMENT FOR B. BALANCE AIR SYSTEM TO DELIVER QUANTITIES AT EACH OUTLET - RECOMMENDATIONS. " WITHIN 51 USING A.A.B.C. PROCEDURES AND TESTS. SUBMIT APPROVAL PRIOR TO FABRICATION INCLUDINGI /A E UC OU " SCALE DUCT LAYOUT. L . AIR BALANCE TEST RESULTS FOR APPROVAL PRIOR TO FINAL Electric Heat Capacity KW @ 208 V 3. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS INSPECTION AND ACCEPTANCE. PROVIDE MANUAL BALANCING VOLUME 10. steel angle ceiling - auxilary drain pan. - AND SHALL COORDINATE WORK WITH ALL OTHER TRADES AT THE 19. ALL EQUIPMENT AND MATERIALS SHALL BE GUARANTEED FORA secure drain pan with angle clips. CONTRACTOR SHALL COORDINATE LOCATION OF ALL GRILLES WITH THE JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF DUCTWORK DUCTS PENETRATING FIRE BARRIERS. DAMPERS SHALL BE CONSTRUCTED PERIOD OF ONE YEAR. COMPRESSOR SHALL CARRY 5 YEAR FACTORY LIGHTS AND THE ELECTRICAL CONTRACTOR. - AND EQUIPMENT. Type of Fan GUARANTEE. Horizontal A/C Unit Mountin g Detail (AHU-1) U.L. 555. FIRE DAMPERS SHALL BE 100/ FREE AREA WITH BLADE OUT - 4. ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID OF AIR STREAM AND U.L. LISTED ACCESS PANELS SHALL BE PROVIDED N.T.S. AIR FLOW AND SERVICE. INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION AND IN 20. VIBRATION ISOLATION ALL EQUIPMENT AS PER MANUFACTURER'S 1 STRICT COMPLIANCE WITH ALL APPLICABLE CODES AND STANDARDS. 28. RECOMMENDATION OR AS SCHEDULED ON DRAWINGS. Notes: 1. Auxiliary drain pans shall be min 2" deep and shall l0e not less than 3" FIRE DAMPERS IN FIRE RATED CEILINGS AHALL BE RADIANT CEILING DAMPERS Compressor F.L.A. (Ea.) AND INSTALLED WITH 11/2" THICK, %ALB DENSITY (R -6) FIBERGLASS COVERED WITH A larger than the unit dimensions in width and length. Pan shall be constructed 5. ALL AIR CONDITIONING SUPPLY DUCTWORK SHALL BE CONSTRUCTED OF 21. AIR DISTRIBUTION, AIR HANDLING UNIT, CONDENSING UNIT AND FANS of not less than 0.0276 inch thick galvanized sheet metal. MESH. CONNECTION TO DUCT MAINS SHALL BE MADE WITH FITTINGS PROVIDED WITH ZINC COATED GALVANIZED SHEET METAL CONSTRUCTED IN ACCORDANCE FIRE RATED CEILINGS. GRILLES SHALL BE STEEL SHALL BE AS SCHEDULED ON THE DRAWINGS OR APPROVED EQUAL. 2. Provide a float switch in aux. drain pan to control overflow by automatically shutting down the air handling unit. SOLDER OR "SILFOSS." 15. PIPE INSULATION: CONDENSATE PIPING AND REFRIGERANT SUCTION PIPING SHALL BE INSULATED WITH %A" FIRE RATED FLEXIBLE FOAM INSULATION, FINISHED, WHERE EXPOSED WITH 2 COATS OF ACRYLIC LACQUER IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. strut strop hanger refrigerant liquid line secure w/ plast to insulation adjust this dimension -) in field as required insulation refrigerant suction END VIEW Jlut vltw Typical Refrigerant Piping Hanger Detail N.T.S. refrigerant liquid line - efrigerant hot gas line waddle saddle support J L -1/4" W. (min.) sheet metal - damper supply branch- duct -main duct AIR FLOW AIR FLOW �o so pivot costing (typ. *\-adjusting � rod condensing unit E pitch pan N steel plate bolted to roof 114" stainless steel turnbuckle (typ.) w/ wire rope clamp. Yr," stainless steel cable (typ. of 2) -bolt w /nut to secure unit to withstand winds up to 150 mph • spring isolators or isomode pod at each corner of unit (size as per manufacturer's recommendations) steel angle 4 x 4 x 1/4 R weld to support column & channel 3" dia. support column / ^° built -up roof deck & insulation (refer to Architect's drawings) beam or other support structure Air Cooled Split A/C Unit Schedule WITH LATEST A.S.H.R.A.E. GUIDE AND S.M.A.C.N.A. RECOMMENDATIONS. AHU -1 O.A. Provided Area Served SEE PLAN 22. ALL OUTSIDE EQUIPMENT SHALL BE SECURED TO WITHSTAND 150 M.P.H. WINDS. 6. ALL AIR CONDITIONING SUPPLY DUCTWORK SHALL BE EXTERNALLY Design Manufacturer RHEEM AIR v INSULATED WITH MINIMUM 1 -1/2" THICK, %ALB DENSITY (R-6) FIBERGLASS RBEH2IJ 'Titus' 3-FL BLANKET COVERED WITH FLAMEPROOF REINFORCED ALUMINUM FOIL 23. ALL FAN DRIVES SHALL BE ADJUSTED TO DELIVER THE SPECIFIED FACED PAPER OR VAPOR SEALED. CFM AGAINST THE ACTUAL STATIC PRESSURE OF THE INSTALLATION. 7. SOUNDLINE SHEET METAL RETURN AIR PLENUMS AND SUPPLY AND RETURN 24. THERMOSTAT SHALL BE PROGRAMMABLE LOW VOLTAGE HEAT COOL WITH FAN AND External Static Pressure In. of H2O AIR DUCTS 15' -0" FROM UNIT CONNECTIONS WITH 1" THICK 3 LB DENSITY SELECTOR SWITCHES ON SUBBASE. MOUNT ON WALL WHERE SHOWN FIBERGLASS DUCTLINER WITH BLACK COATING. INSTALL AS PER 1 / 3 / 3.4 ON PLANS, HEIGHTTO BE PER HANDICAP CODE REQUIREMENTS. PROVIDE MANUFACTURER'S RECOMMENDATIONS. Electrical Service Available KEY LOCK PLASTIC GUARDS. 8. PROVIDE ALTERNATE BID FOR ALL AIR CONDITIONING SUPPLY AND RETURN 25. TESTING= - DUCTWORK TO BE CONSTRUCTED OF 1 -1/2" THICK (R -6) STANDARD DUTY Z roofing FIBERGLASS BOARD WITH REINFORCED FLAMEPROOF ALUMINUM FOIL FACED A. PRESSURE TEST ALL REFRIGERANT HIGH SIDE PIPING TO 275 PSIG. COVERING IN ACCORDANCE WITH N.F.P.A. BULLETIN 90 -A. DUCTWORK SHALL 46,500 HOLD FOR 24 HRS. LOW SIDE TO BE TESTED AT 150 PSIG. HOLD FOR z BE FABRICATED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND Total Sensible Capacity BTU /HR. 24 HRS. AFTER TESTING EVACUATE SYSTEM TO 28" OF MERCURY BULLETINS. OWNER'S OPTION TO ACCEPT. GAUGE PRESSURE WITH VACUUM PUMP. HOLD FOR 24 HRS. WITH 80 / 67 Q PUMP OFF. BREAK VACUUM WITH OPERATING REFRIGERANT. 9. ALL OUTSIDE AIR AND EXHAUST DUCTWORK SHALL BE CONSTRUCTED OF ZINC COATED GALVANIZED SHEET METAL CONSTRUCTED IN TA - 1 Q ACCORDANCE WITH THE LATEST A.S.H.R.A.E. GUIDE AND S.M.A.C.N.A. Quantity & Size B. BALANCE AIR SYSTEM TO DELIVER QUANTITIES AT EACH OUTLET RECOMMENDATIONS. U_ WITHIN 51 USING A.A.B.C. PROCEDURES AND TESTS. SUBMIT AIR BALANCE TEST RESULTS FOR APPROVAL PRIOR TO FINAL Electric Heat Capacity KW @ 208 V t0 INSPECTION AND ACCEPTANCE. PROVIDE MANUAL BALANCING VOLUME 10. ALL DUCT SIZES SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. 1 DAMPERS AT EACH BRANCH DUCT TAKE -OFF FOR THIS PURPOSE. 11. FIRE DAMPERS SHALL BE INSTALLED WHERE INDICATED FOR ALL 26. CONTRACTOR SHALL COORDINATE LOCATION OF ALL GRILLES WITH THE DUCTS PENETRATING FIRE BARRIERS. DAMPERS SHALL BE CONSTRUCTED Unit Designation LIGHTS AND THE ELECTRICAL CONTRACTOR. AND INSTALLED TO CONFORM TO REQUIREMENTS OF N.F.P.A. 90 -A AND Type of Fan PROP. U.L. 555. FIRE DAMPERS SHALL BE 100/ FREE AREA WITH BLADE OUT 27. ALL EQUIPMENT SHALL BE INSTALLED MAINTAINING RECOMMENDED CLEARANCES FOR OF AIR STREAM AND U.L. LISTED ACCESS PANELS SHALL BE PROVIDED Ambient Air Temp. DB AIR FLOW AND SERVICE. FOR REPLACEMENT OF FUSIBLE LINKS. No. of Compressors 1 o 28. FLEXIBLE DUCTWORK SHALL BE ROUND DUCTWORK REINFORCED WITH A WIRE HELIX 12. FIRE DAMPERS IN FIRE RATED CEILINGS AHALL BE RADIANT CEILING DAMPERS Compressor F.L.A. (Ea.) AND INSTALLED WITH 11/2" THICK, %ALB DENSITY (R -6) FIBERGLASS COVERED WITH A INSTALLED IN ACCORDANCE WITH U.L., N.F.P.A. AND ALL LOCAL CODE Electrical Service Available VAPOR BARRIER OF ALUMINUM METALIZED POLYESTER FILM LAMINATED TO GLASS REQUIREMENTS. PROVIDE FIRE DAMPERS IN ALL DUCT PENETRATIONS OF Operating Weight LBS. MESH. CONNECTION TO DUCT MAINS SHALL BE MADE WITH FITTINGS PROVIDED WITH FIRE RATED CEILINGS. GRILLES SHALL BE STEEL Design Manufacturer Model No. TWIST RINGS, BUTTERFLY DAMPERS, QUADRANT OPERATORS, EXTRACTOR AND INSULATION U SEER GUARD. DUCTWORK SHALL BE CLASS 1, U.L. 181, 'WIREMOLD' TYPE WK OR APPROVED EQUAL. 13. PROVIDE ACCESS PANELS IN WALLS AND CIELINGS FOR ALL Ref. Line Size, SUCT /LIQ. O.D. 11 „ : „ A / /a DAMPERS, CONTROL DEVICES, ETC. ACCESS PANELS SHALL BE 29. PROVIDE TURNING VANES IN ELBOWS GREATER THAN 45 DEGREES. MILCOR FLUSH TYPE. 14. ALL REFRIGERANT PIPING SHALL BE TYPE "L" COPPER, TOGETHER WITH 30. CONDENSATE DRAIN PIPING SHALL BE COPPER OR PVC SCH. 40. PVC SHALL NOT WROUGHT COPPER SOLDER FITTINGS JOINTS SHALL BE MADE WITH SILVER BE USED IN RETURN AIR PLENUM. SOLDER OR "SILFOSS." 15. PIPE INSULATION: CONDENSATE PIPING AND REFRIGERANT SUCTION PIPING SHALL BE INSULATED WITH %A" FIRE RATED FLEXIBLE FOAM INSULATION, FINISHED, WHERE EXPOSED WITH 2 COATS OF ACRYLIC LACQUER IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. strut strop hanger refrigerant liquid line secure w/ plast to insulation adjust this dimension -) in field as required insulation refrigerant suction END VIEW Jlut vltw Typical Refrigerant Piping Hanger Detail N.T.S. refrigerant liquid line - efrigerant hot gas line waddle saddle support J L -1/4" W. (min.) sheet metal - damper supply branch- duct -main duct AIR FLOW AIR FLOW �o so pivot costing (typ. *\-adjusting � rod condensing unit E pitch pan N steel plate bolted to roof 114" stainless steel turnbuckle (typ.) w/ wire rope clamp. Yr," stainless steel cable (typ. of 2) -bolt w /nut to secure unit to withstand winds up to 150 mph • spring isolators or isomode pod at each corner of unit (size as per manufacturer's recommendations) steel angle 4 x 4 x 1/4 R weld to support column & channel 3" dia. support column / ^° built -up roof deck & insulation (refer to Architect's drawings) beam or other support structure Air Cooled Split A/C Unit Schedule Unit Designation AHU -1 O.A. Provided Area Served SEE PLAN 140 CFM Operating Weight LBS. 130 0. B. D. Design Manufacturer RHEEM AIR v Model Number RBEH2IJ 'Titus' 3-FL Total Air CFM 1600 Vent Air CFM 140 External Static Pressure In. of H2O 0.45 Fan Motor Hp (Non - Overload) /F.L.A. 1 / 3 / 3.4 Electrical Service Available 208 -1 -60 Smoke Detectors - Z C� Grand Total Capacity BTU /HR. 46,500 z J Total Sensible Capacity BTU /HR. 32,400 Z Entering Air Temp. DB /WB 80 / 67 Q Type & Thickness TA - 1 Q F- LUCY Quantity & Size 1 -21 x 19.75 U_ Electric Heat Capacity KW @ 208 V t0 W No. of Heating Steps 1 Unit Designation CU - 1 Z Type of Fan PROP. No. of Fans And HP (Ea.) 1 -2.0 FLA Z Ambient Air Temp. DB 95 V) No. of Compressors 1 o Capacity Reduction (Percent) 100 -0 0 Compressor F.L.A. (Ea.) 19.3 U 0 Electrical Service Available 208 -1 -60 J Operating Weight LBS. 260 O O Design Manufacturer Model No. RAMB048JA U SEER 12.0 W Q Ref. Line Size, SUCT /LIQ. O.D. 11 „ : „ A / /a ' NOTES, 1. - Provide Programmable Thermostat With Sub -Base, AHU Mounted Circuit Breaker, Sight Glass, Filter Drier. 2. - Coordinate Ref. Line Sizes With Mfgr. Provide All Accessories Recommended A/C Equipment On Roof: Mounting Detail By Mfgr. N.T.S. sheet metal damper return or exhaust branch duct Duct Branch Take Off Detail For Low Pressure Ductwork N.I.S. Outside Air Calculation Per'ASHRAE' STD. 62 Max. Anticipated Occupancy Outside Air Required O.A. Provided 7 7pers. X 20 CFM 140 CFM SUPPLY AIR = 140 CFM 0. B. D. _ Air Distribution Schedule Symbol Name Type Accessories Manufacturer & Model No. O SUPPLY AIR CLG. DIFF. 0. B. D. 'Titus' 250 -AA ORETURN AIR v WALL / CLG. GRILLE - - - - -- 'Titus' 3-FL NOTES: 1. - COORDINATE COLOR FINISH WITH ARCHITECT 2. - ALL GRILLES SHALL BE OF ALUMINUM CONSTRUCTION 3.- APPROVED EQUAL MANUFACTURERS ARE ACCEPTABLE Condensate Trap Detail N.T.S. TO COND. DRAINAGE SYSTEM effective trap seal metal round fitting quadrant operator to be outside insulation provide insulation guard where necessary insulated flex duct seal joint with duct sealer & tape diffuser low velocity supply air duct (see plan view) air flow Flexible Duct Connection Detail N.T.S. FBRC)CKHO�;S7�7E BROCKHOUSE ASSOCIA'I'ES PA 1570 MADRUGA AVENUE PI-11 CORAL GABLES, FL. 33146 305 666 2333 ■ FAX 666 2332 AR 0.• ARGHTECTURE - INTERIOR DESIGN PROJECT A Renovation For The: THE CENTER FOR ARTHRITIS AND RHEUMATIC DISEASES 6150 Sunset Drive South Miami, FI 33143 305 661 2299 SEAL ' � : ,,Ur . =� +i ..� moo^-• INNIJVATIVI ENGINEERING GROUP, INC. SUDHIR K. GUPTHA P.E. # 29189 5532 N.W. 72 AVE. MIAMI, FLORIDA 33166 305- 888 -9626 SITEET TITLE HVAC NOTES & DETAILS SHEET TITLE REFERENCE 03027- hvacdet.dgn ALL CONCEPTS. DESIGNS. ARRANGEMENTS. DRAWINGS AND SPECIFICATIONS ARE OWNED BY, AND ARE THE PROPERTY OF THIS OFFICE AND WERE CREATED, EVOLVED AND DEVELOPED FOR USE ON, AND IN CONJUNCTION WITH, THE SPECIFIED PROJECT. NONE OF SUCH IDEAS, DESIGNS, ARRANGEWNTS OR PLANS SHALL BE USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORPORATION FOR ANY PURPOSE WHATSOEVER WITHOUT THE WRITTEN PERMISSION OF: BROCKHOUSE ASSOCIATES, PA. REVISION DESIGNED BY B.A. DRAWN BY B.A. APPROVED BY L.C. DATr: 1 -2A_05 SCALE PROJECT NO. 03027 SHEET N0, A Ivi 4