RESIDENTIAL UNITS FEEDER SCHEDULE
BLDG.
UNIT NO.
sC NEL
WIRE
CONDUIT
A
A3 -1
R1
3 #2
1 114"
I
A3 -2
R1
3 #2
1 1/47
A3 -3
R1
3 #2
1 1/47
A3 -4
R1
3 #2
1 114"
A3 -5
R1
3 #2
1 1/4"
A3 -6
R1
3#1
1 1/4"
A3 -7
R1
3 #1
1 114"
A3 -8
R1
3 #1
1 114"
A3 -9
R2
3-1/0
1 114
A4 -1
R1
3 #2
1 114"
A4 -2
R1
3 #2
1 1/4"
A4 -3
R1
3 #2
1 1/4"
A4 -4
R1
3 #2
1 1/4"
A4 -5
R 1
3 #2
1 114
A4 -5
R1
3 #2
1 114"
A4 -6
R1
3 #1
1 114"
A4 -7
R1
3 -1/0
1 1/2"
A4 -8
R1
3 -1/0
1 1/2"
A4 -9
R2
3-1/0
1 1/27
HOUSE
A
id 6 G
B
B3 -1
R1
3 #1
1 114"
B3 -2
R1
3 #2
1 114"
B3 -3
R1
3 #2
1 114"
83 -4
R1
3 #2
1 1/47
83 -5
R 1
3 #2
1 1/47
B3 -6
R1
3 #2
1 1/4"
B3 -7
R1
3 #2
1 1/4"
B3 -8
R 1
3 #2
1 114
B3 -9
R 1
3 #2
1 1 14"
B3 -10
R1
3#2
1 1/4"
B3 -11
R2
3 #1
1 114"
84 -1
R2
3 #1
1 1/4"
B4 -2
R1
3 #1
1 1/4"
B4 -3
R1
3 #2
1 114
B4 -4
R1
3 #2
1 1/47
84 -5
R1
3 #2
1 1/4"
B4 -6
R1
3 #2
1 114"
B4 -7
R1
3 #2
1 114"
B4 -8
R1
3 #2
1 114"
B4 -9
R1
3 1
1 114
84 -10
R1
3 #1
1 1/4"
B4 -11
R2
3 #1
1 1/4"
HOUSE
B
4 -300
MCM
2 1/2"
1
4 5 6 7 1 8 10 1 11 1 12 13 14 15 16 17 18
O REFER TO BLDGS. A AND B ONE -LINE DIAGRAM, SHEET E7.01 FOR RATING AND SIZES OF EQUIPMENT,
CONDUCTORS, CONDUITS AND OTHER ADDITIONAL INFORMATION NOT SHOWN ON THIS DRAWING.
OCONTRACTOR SHALL COORDINATE WITH F.P.& L. CO. ALL PENETRATIONS INTO THE VAULT, FINAL
LOCATIONS OF CONDUIT STUBS, CONDUCTOR LENGTHS AND TERMINATIONS PRIOR TO COMMENCING
THIS WORK.
O PASSENGER ELEVATOR MAIN, 3P., 200A., ENCLOSED CIRCUIT BREAKER WITH SHUNT -TRIP DEVICE.
OSHUNT -TRIP SIGNAL WIRING TO HEAT DETECTORS LOCATED IN ELEVATOR EQUIPMENT ROOM AND
IN THE ELEVATOR SHAFT.
O 3 -3/0 & 1 - #6 (G) IN 2 7C. TO ELEV. EQUIPMENT ROOM.
O314 "X 10', COPPER -CLAD GROUND ROD. CONNECT TO GROUNDED SERVICE CONDUCTOR (NEUTRAL)
IN SERVICE MAIN. BOND TO REINFORCING STEEL IN BUILDING FOUNDATION, TO THE COLD WATER PIPE
AND TO THE SECOND GROUND ROD WITH 1 -2/0 AWG. IN 3/4 "C. ALL CONNECTIONS ON GROUND RODS
SHALL BE EXOTHERMICALLY WELDED.
7O BOND TO REINFORCING STEEL IN BLDG. FOUNDATION AND TO THE COLD WATER PIPE.
O8 1 #6 IN 3/4 "C. GROUNDING CONDUCTOR CONNECT TRANSFORMER SECONDARY NEUTRAL AND TTRANSFORMER
GROUNDING LUG TO GROUND ROD.
OCOMBINATION, ONE -UNIT, STEPDOWN TRANSFORMER AND PANELBOARD IN INTEGRATED ENCLOSURE.
480V. PRIMARY WITH CIRCUIT BREAKER, 5 KVA., SINGLE PHASE, 240/120V. SEC., TRANSFORMER
WITH 2P, 30A., SECONDARY MAIN AND SIX, ONE -POLE, 20A. BRANCH CIRCUIT BREAKERS. REFER TO SCHEDULE.
10 EMERGENCY POWER FEEDER. REFER TO PANEL SCHEDULES.
MAIN ELECT. ROOM
BUILDING "A"
ELEVATOR
FEEDER 01
MAIN
q 0 �
_)f
v .1
PANEL II PANEL
"y" "Pr,
RESIDENTIAL UNIT
PANEL
"R1"
OR
"R2"
RESIDENTIAL
PANEL
"R1"
OR
"R2"
RESIDENTIAL UNIT FEEDER.
REFER TO FEEDER
SCHEDULE (TYPICAL)
11 ELEVATOR EQUIPMENT FUSIBLE DISCONNECT SWITCH, 3P., 100A., 480VAC. FUSES AS PER ELEVATOR
EQUIPMENT REQUIREMENTS PROVIDE AUXILIARY, ELECTRICAL INTERLOCK, CONTACTS TO MONITOR SWITCH
POSITION. CONNECT INTERLOCK CONTACTS TO ELEVATOR CONTROLLER.
12 3/4 7C. WITH CONTROL WIRING FROM SWITCH INTERLOCK CONTACTS TO ELEVATOR CONTROLLER. CONNECT,
AS PER ELEVATOR EQUIPMENT INSTRUCTIONS TO DISABLE ELEVATOR CONTROLLER BATTERY POWER AND
STOP THE ELEVATOR CAB IN POSITION.
13 POWER FEED TO ELEVATOR EQUIPMENT, 3 #3 IN 1 "C.
14 PASSENGER ELEVATOR MAIN, 3P, 150A., ENCLOSED CIRCUIT BREAKER WITH SHUNT -TRIP DEVICE.
BUILDING °A° RESIDENTIAL gUILDING "A°
ELECTRICAL ROOM RESIDENTIAL
ESIDENTIAL UNIT ELEV. CU TW REAK R (TYP.) ROOM EQUIP.
-HOUSE
KWHR
METER
El
125A.
CIRCUIT
Mims
HOUSE
PANEL
PANEL
I
El
AA
Mims
�
Mims
Mimi&
miss
Mims
MEMO
MOEN
-HOUSE
KWHR
METER
WITH
125A.
CIRCUIT
BREAKER
HOUSE
PANEL
PANEL
"EHp'
AA
FOURTH FLOOR
SECOND FLOOR
�8°X 8"X REQ. LENGTH
1 -2/0 IN 3/4%. SPARE WIREWAY
rC7
n rr 6 T
GROUND FLOOR
- -2" SPARE
CONDUIT � �
i I 4W. Y, StKVIC:E I 1 1" SPARE �
REFER TO ONE -LINE � � i � � 5 J.. I I J I CONDUIT
_ -_
i DIAGRAMS. SHEET E701 I _ I � i '- --5 � � � � � ------ - - - - -- (1�}� � -� -- �
FOR SERVICE L 10 � -I
CONDUCTORS AND � � �,_,� I
CONDUITS � r---- - - - - -- I - - -- I- iJ
L - .0
BUILDINGS "A" & "B" RESIDENTIAL SERVICES ELECTRICAL RISER DIAGRAM
N.T.S.
2 3 4 5 6
7 8 9 10 11 12 13 14 15 16 17
RESIDENTIAL SERVICES -LOAD CALCULATIONS
(NEC. ART. 220, 220 -32)
BUILDING "A"
16 APTS. AT 16.57 KVA. EACH= 265.12
2 APTS. AT 17.4 KVA. EACH= 34.74
TOTAL APT. LOAD: 299.86 KVA.
AS PER TABLE 220 -32 DEMAND FACTOR: 0.38
295 KVA. X 0.38= 114.95 KVA., 317 AMPS AT
208V., 30
HOUSE LOAD, PANEL "A ": 24.22 KVA., 116.4 AMPS., AT
208V., 10
APT.. DEMAND AMPS: 317
HOUSE PANEL AMPS: 116
TOTAL SERVICE AMPS: 433
SERVICE LATERAL PROVIDED: 2 SETS OF 4 -300 KCM IN 2 1/2 "C. EACH 2.3% VOLTAGE DROP
BUILDING "B"
17 APTS. AT 16.57 KVA. EACH= 281.7
5 APATS. AT 17.4 KVA. EACH= 87
368.7
DEMAND FACTOR: 0.36
368.7 KVA.X 0.36= 132.73
HOUSE LOAD, PANEL "B": 60
192.73 KVA, 535 AMPS., AT
208V., 30
SERVICE LATERAL PROVIDED: 2 SETS OF 4 -500 KCM IN 3 "C., EACH. 2.54% VOLTAGE DROP
A
►J1 lvlUl
INATIONAL CITY CENTER
P.O. BOX 7033
INDIANAPOLIS, IN 46207
(317) 636-1600
If
K
F
THE :]
CCOMRAS
COMPANY
1111 Lincoln Road Mall
Suite 510
Miami Beach, FL. 33139
(305) 532 -0433
•
11C�)1 III l�(;
I": •\ l I N2 I ZI
ARCMECIVRE- ENGINEERING
PLANNING- INTERIOR DESIGN
5960 S.W. 57TH AVE.
MIAMI, FLORIDA
33143
(305) 666 -5474
E FAX (305) 666 -4994
A.A.C. 000404
ANGEL E. LORENZO, P.E.
FL. ELECTRICAL ENGINEER
REG. NO. 31137
ISSUE DATE
°o
c REVISION DATE
=� PRICING D 07-% C.
9 -12 -96
C;
B
:a
CADD FILE NAME
E- 805 -RT
DRAWING TITLE
ONE LINE DIAGRAMS
SHEET NUMBER
A
E8.05
OF