12-86 70F7-181M
L
d J
d
I
LOCATED
IN THE
ELECTRICAL ROOM
l:l
7
r
1
n
3 � 4 5
FIB ROPTIC — ETHERNET 10 MBAUD FIBER OPTIC — ETHERNET 10 MBAUD
HUB
N CONDUIT (TYPICAL) HUB
Z01a
OUTDOOR AIR
D DAMPER OPEN DO
CLOSED SIGNAL
C
B
A
EMT CONDUIT
PROVIDED BY
DIV. 16 ELECTRICAL
CONTRACTOR (TYPICAL).
LIGHTING LOCATED IN EACH
CONTROL ELECTRICAL
PANEL ROOM
(TYPICAL)
3/4 EMT CONDUIV
PROVIDED BY
DIV. 16 ELECTRICAL
CONTRACTOR (TYPICAL).
BAS DIV. 17
-CONTRACTOR TO
PROVIDE COMM.
CABLE TO EACH
TENANT LOCATION
FOR FUTURE TENANT
CONNECTION.
STARTER
MAY BE
LOCATED
IN THE
ELECTRICAL ROOM
13
OA
FAN STARTS
— ETHERNET 10 MBAUD
VIA
A TIME DELAY
RELAY SET AT
90
SECONDS
AMPERAGE \/
SENSOR
(ANALOG)
OUTDOOR AIR FAN &EXHAUST FAN CONTROL DIAGRAM
s a �
FIBER OPTIC — ETHERNET 10 MBAUD
r
NODE 2 PENTHOUSE
CHILLER PLANT
CHILLER PLANT BUILDING — B
CONTROLLER
1" EMT CONDUIT
PROVIDED BY
DIV. 16 ELECTRICAL
CONTRACTOR (TYPICAL).
LIGHTING LOCATED IN EACH
CONTROL ELECTRICAL
PANEL ROOM
(TYPICAL)
314 EMT CONDUIT/
PROVIDED BY
DIV. 16 ELECTRICAL
CONTRACTOR (TYPICAL).
TENANT CONTROLLERS
TYPICAL NETWORK FOR
EACH MAIN CONTROLLER BAS DIV. 17
CONTRACTOR TO
PROVIDE COMM.
CABLE TO EACH
TENANT LOCATION
FOR FUTURE TENANT
CONNECTION.
of
ELE
TO EACH TENANT
OUTDOOR AIR
SUPPLY DUCTS E
0
E
A
LOCAL
CONTROL
FOR
TENANT
SPACE
FERN
1I
" EMT CONDUIT
PROVIDED BY
DN. 16 ELECTRICAL
CONTRACTOR (TYPICAL).
LIGHTING LOCATED IN EACH
CONTROL ELECTRICAL
PANEL ROOM
(TYPICAL)
314 EMT CONDUIT'
PROVIDED BY
DIV. 16 ELECTRICAL
CONTRACTOR (TYPICAL).
TENANT CONTROLLERS
TYPICAL NETWORK FOR
EACH MAIN CONTROLLER
BAS DIV. 17
CONTRACTOR TO
PROVIDE COMM.
CABLE TO EACH
TENANT LOCATION
FOR FUTURE TENANT
CONNECTION.
N.T.S.
120 VAC
Ne
N.T.S.
lit
1 2 3 4 5
LOCAL
CONTROL
FOR
TENANT
SPACE
11
5960 S.W. 57TH AVE.
�
12
MIAMI, FLORIDA
13
FIBER OPTIC
— ETHERNET 10 MBAUD
NIKE AHU
CONTROLLER
14 I 15
Ll
pk L•
"1" EMT CONDUIT
PROVIDED BY
DIV. 16 ELECTRICAL
CONTRACTOR (TYPICAL).
LIGHTING LOCATED IN EACH
CONTROL ELECTRICAL
PANEL ROOM
(TYPICAL)
VAV BOX
CONTROLLERS 3/4" EMT CONDUI
FOR NIKE AHU PROVIDED BY
�-- PROVIDED BY DIV. 16 ELECTRICAL
TENANT CONTRACTOR (TYPICAL).
(OPTIONAL)
BAS DIV. 17
CONTRACTOR TO
PROVIDE COMM.
CABLE TO EACH
TENANT LOCATION
FOR FUTURE TENANT
CONNECTION.
TENANT CONTROLLERS
�-- TYPICAL NETWORK FOR
.EACH MAIN CONTROLLER
re
17 I 18
C
qp � C Sy M H S4
C �
SPACE TEMP.
OA T SENSOR
DO
SUPPLY FAN
ON —OFF
CHILLED @0 AI TEMPERATURE
WATER
VALVE
FAN COIL UNIT CONTROL DIAGRAM
,ANT TYPICAL FOR PUBLIC AND SERVICE AREAS
N.T.S.
SPACE TEMP.
OA T SENSOR
DO DO
SUPPLY FAN HEATER
ON —OFF ON —OFF
(IF APPLICABLE)
CHILLED SPACE
WATER � � TEMPERATURE
VALVE
FAN COIL UNIT CONTROL DIAGRAM
RETURN AIR RETURN AIR FILTER SUPPLY FAN #i
TEMPERATURE AI AI HUMIDITY 9 Al DP SENSOR �� ON —OFF
(ANALOG) AIDE VARI —CONE #1
SIGNAL
DI FAN #1 STATUS
� VARI —CONE #1
POSITION
-EI-] RA SA
C
OA LOCATE 213_ RD
DOWNSTREAM
ER OF SUPPLY FAN
Al VARI —CONE #2
POSITION
SUPPLY FAN jJ2
DO ON —OFF
AO VARI —CONE #2
SIGNAL
RETURN NR MIXED SUPPLY SUPPLY
IAQ — CO2 LEVEL AI DO AIR Al DI FAN #2 STATUS AOE AI AI AI AMP AI AIR AI STATIC
OUTDOOR AMP' CHILLED ChWS ChW TEMP. PRESSURE
AIR DAMPER WATER TEMP FLOW
OPEN /CLOSE VALVE
AHU CONTROL DIAGRAM —NIKE
N.T.S.
rmn A
w W w w Em- m out] to 9 MOVISA1109 WRI toil
6 7 80 9 10 11 13 14 15 16 1 17
I i L
NATIONAL CITY CENTER
P.O. BOX 7033
INDIANAPOLIS, IN 46207
(317) 636-1600
Of I
r
J iiilD ) ) F
i ) T
A d ,
J ) A
C { d a
d
E {
7 `<
d t < t
d { a<
" L {
d � d
a
d�
E-+
H O
G
ra
AROMICYt1it8 • ffiVGIIJH MMG
PLANNING•INMOR DMM4
5960 S.W. 57TH AVE.
MIAMI, FLORIDA
33143
(305) 666 -5474
E
FAX (305) 666 -4994
A.A.C. 000404
MARIO H. GUTIERREZ, P.E
FL. MECHANICAL ENGINEER
REG. NO. 0019687
♦6Y
.R
ISSUE 1)A
C>
ul.)
d
cv
REVISION DATE
PRICING I W.
0
z
I—
U
w
0
a
B
a
/1
CADD FILE NAME
M501 -RT
DRAWING TITLE
HVAC - CONTROLS
SHEET NUMBER
A
M5oOl