12-86 4OF7-1651 2 3
LOW VELOCITY SUPPLY
M AIR DUCT (SEE PLAN
VIEW) Alf? F�pW�
RECTANGULAR
DUCT W/45 DEG.
SCOOP MVD
1100
"THERMA FIN" OR EQUAL -
INSULATED FLEX DUCT
RATED FOR 450 ' F MIN.
K DIFFUSER
IJI
ins
ice■
ANGLE RIVETED OR
SPOT WELDED
REQUIRED_-,
PROVIDE ALUMINUM
F BIRD SCREE"
,
ice■
I Dim
!D■
0
o■
n■
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
RECT /ROUND
TRANSITION
SEAL JOINT WITH DUCT
SEALER & TAPE
ROUND DUCT TO
SQUARE ADAPTOR
\ DIFFUSER
J
FITTING
SEAL JOINT WITH DUCT
SEALER &TAPE
OPPOSED BLADE
DAMPER
INSULATED
FLEX DUCT
FLEXIBLE DUCT CONNECTION DETAIL
(SIMILAR FOR TRUNK DUCT BOTTOM CONNECTION N.T.S.
WHEN CEILING SPACE ALLOWS)
`STANDARD DUCT
MADE WATER TIGHT
�1/2" SCREEN
�xx MAN, .
R= 2
SPECIFIED
DUCT SIZE
io
WEATHER PROOF MEMBRANE
� COUNTER FLASHING
mm
WOOD NAILER
FLASHING (SEE ARCH.
DRAWING FOR DETAIL)
12" MIN. PREFABRICATED
j BUILT UP ROOFING
W
�•• • •• . . . • A . •� jo
\-SECURE CURB TO ROOF
W /LAG BOLTS ® 12"
0/C ALL AROUND
TYPICAL RECTANGULAR
GOOSENECK DETAIL
N.T.S.
1 2 3
SEAL JOINT
WITH DUCT
SEALER &
TAPE
SPIN COLLAR
W /DAMPER
VAV BOX
OR OUTLET
DISCHARGE
PLENUM
T /ROUND
VSITION WHEN
UIRED
BALL BEARING
MOTOR
DISCONNECT SWITCF
VIBRATION ISOLATOR
ROOF CURB
SEE PLAN FOR SIZES
45° 1/4W 4" MIN.
---- PROVIDE MANUAL VOLUME
DAMPER
W BRAN CH DUCT
PLAN VIEW
NOTE: TYPICAL LOCATION OF MANUAL
VOLUME DAMPER FOR ALL LOCATION
TYPICAL SUPPLY /EXHAUST AND /OR
RETURN BRANCH DUCT
NTS
MIMI[ "I
_0�
0
a
REMOVABLE SERVICE PANEL
1" ALUMINUM FILTER
(TYPICAL)
GALVANIZED
STEEL
WIND BAND
DUCT ADAPTER
ROOFING
i— ROOF SYSTEM
FLEXIBLE CONNECTION " � DUCT
ROOF SUPPLY FAN DETAIL
N.T.S.
WEATHER PROOF MEMBRANE
SHEET METAL DUCT
VAPOR BARRIER
COUNTER FLASHING
RIGID BOARD INSULATION
(WHERE REQUIRED)
ROOF FELT
TREATED WOOD CURB
4' CONT. MINERAL FIBER
CANT ( ALL SIDES )
BUILT - UP TAR & _
GRAVEL ROOF
INSULATION
SLAB . •
•.
TYPICAL DUCT PENETRATION
4 5 6 7
THRU ROOF
N.T.S.
THERMALLY PROTECTED MOTOR
2" OF THERMAL &
ACOUSTICAL INSULATION
1/4!'X27 SPONGE
RUBBER PAD
SEALING COMPOUND
1/4!' BOLT EVERY 12"
NUT & 3/4" DIA. WASHER
PREFAB. ROOF CURB
DUCTWORK TO- SYSTEM
NEO -PRENE OR BUTYL
RUBBER FLEX CONN.
OUTSIDE AIR DUCT ON ROOF
AIR DUCT ABOVE
CELING
M.V.D._/
(TYP.)
AIR DUCT ABOVE
GEEING
10 - 000, r+K
I - \L� �_j
M.V.D. AT OR IN
DROP DUCT
CEILING PLAN VIEW
TYPICAL SUPPLY /EXHAUST AND /OR
AIR FLO
FULL RADIUS ELBOW
ROOF CURB. FOR FLASHING -
DETAILS SEE ARCH. DRAWINGS
ROOF
FUM
N.T.S.
VIBRATION ISOLATORS
(TYPICAL)
REMOVABLE SERVICE PANEL
),Z_6�AICUALMjNUM FILTER
j DISCONNECT SWITCH
BALL j
MOTOR
RING
j
ROOF CURB. FOR
j FLASHING DETAILS
SEE ARCH. DWGS.
2 I Du
MIN.
SUPPLY FAN ROOF MOUNTING DETAIL
SERVICE DISCONNECT SWITCH
PRE -FAB ROOF CURB
0
GRAVITY DAMPER
BOLT TO CURB
MIN. (2) PER SIDE
ROOF SLAB
FLEXIBLE CONNECTION
\\-MOTORIZED DAMPER &
BURGLAR BARS.
NOTE: FOR ROOF FLASHING DETAIL SEE
ARCHITECTURAL DRAWINGS.
EXHAUST FAN MOUNTING DETAIL
N.T.S.
8 9 10 11 12 13
14
N.T.S.
PROPERTY
I DO" wo [I
l�l
NA11O1Vf4 CITY VGl \1Gll
P.O. BOX 7033
INDIANAPOLIS IN 46207
(317)63E1600
L
!fl
COUR41
co
nu l.mrom Rood Mmn
Sdte510
MIDI Bmdt FI.39199
(909532.0139
I�
J
q
I � o
a
F
H
G
F
,o, M
r RMIT." mm
ilimp)
ARCHI'ffiCTURB • fiNGINffitING
PLANNING • INTERIOR DHSIGN
5960 S.W. 57TH AVE.
MIAMI, FLORIDA 33143
TEL (305) 666 -5474
FAX (305) 666 -4994
7 E AA 0002416
EB 0002354
MARIO H. GUTIERREZ, P.E
FL MECHANICAL ENGINEER
REG. NO. 0019687
STL PL 3 8X6X6
W/ 4 -1 %2" DIA GALV
NEO -PRENE OR BUTYL STEEL BOLTS
RUBBER FLEX CONN. ISSUE DATE
FULL RADIUS ELBOW - °o
° ° -�
1 /8 (TYP) C :,°� REVISION DATE
_ o�
P I lij DOG.
12 -10 -96 I z
REVISION
CURB .0
2' -p' - /-ROOF MIN. ' v
W
_o
ANGLE STEEL FAN SPRING TYPE B _ a-
SUPPORT. SET IN PITCH PANS VIBRATION ISOLATOR
<2- 1/2X2- 1/2X1/4
CADD FILE NAME
M701 -RT
EXHAUST FAN DETAIL DRAWING TITLE
HVAC - DETAILS
(UTILITY SET)
N.T.S. SHEET NUMBER
AI I
M7.01
15 16 17 18 ov