Loading...
12-86 1OF7-045C' t .y I . I 1 10 11 1 12 M L Elm J I lowl G F E [E 0 J 13 MA I 15 16 17 LIFE SAFETY PLAN — FOURTH FLOOR SCALE: 1" = 30' -0" NOTE: THIS LIFE SAFETY PLAN IS BASED ON RETAIL /RESTAURANT AREAS IDENTIFIED BY WAP AS OF 2/13/96 N 'k I I 1 1 BAKERY CENTRE REDEVELOPMENT Applicable Codes: South Florida Building Code — 1994 (SFBC) NFPA 101 Life Safety Code — 1994 (LSC) (supersedes SFBC Ch. 31) Construction: — Type I automatic sprinklers all areas — Structural 2 hour fire rating (except at exterior walls frame walls with higher rating). — Floor 2 hours — Roof 2 hours — Vertical Opening 2 hours Protection — Occupancy Separation 2 hours or 15 feet of Parking Structure — Occupancy Separation 2 hours of apartments Occupancy; Mercantile with integrated assembly occupancies Apartment and open parking structure separated Exiting: Covered mall requirements will facilitate emergency egress means. LSC 24 -4.4 permits public corridors to function as 'pedestrian ways" which contribute no occupant load and allow 200 feet additional exit travel. Pedestrian ways must provide 10 feet unobstructed width, separate facing tenant spaces by at least 20 feet, have demising partitions between tenants, lead to minimum 66 inch wide exits and have full coverage sprinkler protection. The required smoke control is met by the mall being open to the sky. 10 11 Travel distance to an exit or the pedestrian way is 200 feet from the most remote point for mercantile and assembly occupancies plus 200 feet additional along the pedestrian way to an exit, is 200 feet from the entrance doors of apartments and 300 feet in open parking structures. Dead end travel distance is limited to 50 feet except as limited to 20 feet for exterior ways of exit access and not allowed for assembly corridors. Fire resistant separated exit passageways are provided to reduce exit access travel distance and eliminate dead ends. Occupancy Load for mercantile tenants is 30 sq —ft per person on ground floors and 60 sq —ft per person on upper floors. Theater auditorium occupancy is based on seating capacity, plus waiting patrons of a number approximating the capacity of two auditoriums. Restaurant occupancy is based on an approximation of 70% dining (15 sq —ft per person), 25% office or kitchen (100 sq —ft per person) and 5% rest rooms and corridors as retail (30 sq —ft or 60 sq —ft per person). Apartment occupancy is 200 sq —ft per person. Arrangement for stores having public access from one side, a maximum of one —third of occupancy may exit through rear exits. For assembly occupancies, the main entrance must provide capacity for at least fifty percent of occupancy load, and other exits provide at least fifty percent. Single exits are permitted for a maximum 3000 sq —ft stores (Class C) where travel distance does not exceed 100 feet in fully sprinklered facilities. Horizontal exiting is permitted to separate building areas provided that bridges or two hour fire resistance barriers are used for separation and that there is at least one standard type of exit (not another horizontal 12 I 13 I 14 0 MT USE. .6.5 I I OdO Mot& 7.9 is. i �r FLOOR NOTES W exit) leading from it. The capacity of horizontal exits is limited to not more than one —half the required exits or egress capacity of the Fourth Floor: buildings. Total occupant load: 258 people Mall exits in this life safety analysis are defined as those exits which are accessible by occupants in the general mall areas. Tenant exits in this life safety analysis are defined as those exits which are accessible to only those occupants who are in specific tenant spaces. Unprotected Vertical Openings between two adjacent floors are permitted in class A and class B mercantile occupancies having full coverage, supervised automatic sprinkler protection. Exit passageway enclosures may not contain openings which are used for purposes other than providing access into the enclosure from normally occupied spaces or for providing egress from the enclosure into the exit discharge. No openings through the passageway enclosure walls are permitted from storage rooms, closets, boiler rooms, eqiupment spaces, utility rooms, electrical vaults, or similar spaces that are not normally occupied. 15 I 16 I 17 I 18 INATIONAL CITY CENTER P.O. BOX 7033 INDIANAPOLIS, IN 46207 (317) 636-1600 L K THE -] COMRAS COMPANY 1111 Lincoln Road Mall Suite 510 Miami Beach, FL. 33139 (301) 532-0433 rx J 0-1k { aal 4. Q O r� I wj E-1 0�/� V1 C�®r �Tarl �ampbcll & Associates, Inc. „.AHO Brickell Ave. Suite 430 & Miami, Fl 33131 ASSOCIATES (305) 374 -4091 5960 S.W. 57TH AVE. MIAMI, FLORIDA 33143 E(305) 666 -5474 A.A.C. 000404 } REED B. VARLEY 'FL. ENGINEER FL11 EtG,. Ij N0: 27465 _ v V) 'S' 'o IS- U E PATE a, 24 -96 c o R�RMIT SET LO REYIISION; D4ZTE O Z ' U €w O tY Q CADD FILE NAME VC —LS4 DRAWING TITLE LIFE SAFETY PLAN SHEET NUMBER A LS -04 38 OF 38 c B 0 J 13 MA I 15 16 17 LIFE SAFETY PLAN — FOURTH FLOOR SCALE: 1" = 30' -0" NOTE: THIS LIFE SAFETY PLAN IS BASED ON RETAIL /RESTAURANT AREAS IDENTIFIED BY WAP AS OF 2/13/96 N 'k I I 1 1 BAKERY CENTRE REDEVELOPMENT Applicable Codes: South Florida Building Code — 1994 (SFBC) NFPA 101 Life Safety Code — 1994 (LSC) (supersedes SFBC Ch. 31) Construction: — Type I automatic sprinklers all areas — Structural 2 hour fire rating (except at exterior walls frame walls with higher rating). — Floor 2 hours — Roof 2 hours — Vertical Opening 2 hours Protection — Occupancy Separation 2 hours or 15 feet of Parking Structure — Occupancy Separation 2 hours of apartments Occupancy; Mercantile with integrated assembly occupancies Apartment and open parking structure separated Exiting: Covered mall requirements will facilitate emergency egress means. LSC 24 -4.4 permits public corridors to function as 'pedestrian ways" which contribute no occupant load and allow 200 feet additional exit travel. Pedestrian ways must provide 10 feet unobstructed width, separate facing tenant spaces by at least 20 feet, have demising partitions between tenants, lead to minimum 66 inch wide exits and have full coverage sprinkler protection. The required smoke control is met by the mall being open to the sky. 10 11 Travel distance to an exit or the pedestrian way is 200 feet from the most remote point for mercantile and assembly occupancies plus 200 feet additional along the pedestrian way to an exit, is 200 feet from the entrance doors of apartments and 300 feet in open parking structures. Dead end travel distance is limited to 50 feet except as limited to 20 feet for exterior ways of exit access and not allowed for assembly corridors. Fire resistant separated exit passageways are provided to reduce exit access travel distance and eliminate dead ends. Occupancy Load for mercantile tenants is 30 sq —ft per person on ground floors and 60 sq —ft per person on upper floors. Theater auditorium occupancy is based on seating capacity, plus waiting patrons of a number approximating the capacity of two auditoriums. Restaurant occupancy is based on an approximation of 70% dining (15 sq —ft per person), 25% office or kitchen (100 sq —ft per person) and 5% rest rooms and corridors as retail (30 sq —ft or 60 sq —ft per person). Apartment occupancy is 200 sq —ft per person. Arrangement for stores having public access from one side, a maximum of one —third of occupancy may exit through rear exits. For assembly occupancies, the main entrance must provide capacity for at least fifty percent of occupancy load, and other exits provide at least fifty percent. Single exits are permitted for a maximum 3000 sq —ft stores (Class C) where travel distance does not exceed 100 feet in fully sprinklered facilities. Horizontal exiting is permitted to separate building areas provided that bridges or two hour fire resistance barriers are used for separation and that there is at least one standard type of exit (not another horizontal 12 I 13 I 14 0 MT USE. .6.5 I I OdO Mot& 7.9 is. i �r FLOOR NOTES W exit) leading from it. The capacity of horizontal exits is limited to not more than one —half the required exits or egress capacity of the Fourth Floor: buildings. Total occupant load: 258 people Mall exits in this life safety analysis are defined as those exits which are accessible by occupants in the general mall areas. Tenant exits in this life safety analysis are defined as those exits which are accessible to only those occupants who are in specific tenant spaces. Unprotected Vertical Openings between two adjacent floors are permitted in class A and class B mercantile occupancies having full coverage, supervised automatic sprinkler protection. Exit passageway enclosures may not contain openings which are used for purposes other than providing access into the enclosure from normally occupied spaces or for providing egress from the enclosure into the exit discharge. No openings through the passageway enclosure walls are permitted from storage rooms, closets, boiler rooms, eqiupment spaces, utility rooms, electrical vaults, or similar spaces that are not normally occupied. 15 I 16 I 17 I 18 INATIONAL CITY CENTER P.O. BOX 7033 INDIANAPOLIS, IN 46207 (317) 636-1600 L K THE -] COMRAS COMPANY 1111 Lincoln Road Mall Suite 510 Miami Beach, FL. 33139 (301) 532-0433 rx J 0-1k { aal 4. Q O r� I wj E-1 0�/� V1 C�®r �Tarl �ampbcll & Associates, Inc. „.AHO Brickell Ave. Suite 430 & Miami, Fl 33131 ASSOCIATES (305) 374 -4091 5960 S.W. 57TH AVE. MIAMI, FLORIDA 33143 E(305) 666 -5474 A.A.C. 000404 } REED B. VARLEY 'FL. ENGINEER FL11 EtG,. Ij N0: 27465 _ v V) 'S' 'o IS- U E PATE a, 24 -96 c o R�RMIT SET LO REYIISION; D4ZTE O Z ' U €w O tY Q CADD FILE NAME VC —LS4 DRAWING TITLE LIFE SAFETY PLAN SHEET NUMBER A LS -04 38 OF 38