07-780-027ELECTRICAL NOTES ALL CONDUCTORS SHALL BE COPPER, RATED 75 C WET /DRY EXCEPT WHERE OTHERWISE REQUIRED BY Uk, OR CODES, UON. MINIMUM WIRE SIZE SHALL BE 012 AWG. EXCLUDING CONTROL WIRING. ALL CONDUIT RISERS SHALL BE RIGID GALVANIZED STEEL (RGS). WHERE CONDUIT BENDS UPWARD FROM UNDERGROUND TO ABOVE GROUND, USE AN APPROVED PVC TO RGS COUPLER, AS REQUIRED. RGS CONDUITS SHALL EXTEND A MINIMUM OF 10' BELOW GRADE. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW, ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, LATEST EDITION (NEC) AND THE LATEST EDITIONS OF THE FLORIDA BUILDING CODE AND ALL LOCAL CODES, RULES AND ORDINANCES HAVING JURISDICTION. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY, EXACT ROUTING SHALL BE DETERMINED 114 THE FIELD, UNLESS OTHERWISE NOTED, ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC TO ACCOMMODATE EQUIPMENT SERVED, INCLUDING REQUIRED FUSES, UON. SWITCHES SHALL BE HORSE POWER RATED AND SIZED FOR 112 MAX. HORSEPOWER, HEAVY DUTY TYPE, ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. WIRE WAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED (UON). COORDINATE ALL ELECTRICAL SITE WORK WITH GENERAL CONTRACTOR. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE FULL BOXES, SUCH TITAT NO SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES SHALL BE SUITADLE AND APPROVED FOR THE INTENDED USE. WARNING TAPE WHICH SAYS 'WARNING BURIED ELECTRIC' SHALL BE PLACED IN TRENCHES ABOVE ALL UNDERGROUND ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL BE RGS. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC, ALL CONDUIT RISERS SHALL BE RGS. FOR TELEPHONE SYSTEI41 A. PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND EQUIPMENT PER REQUIREMENTS OF TELEPHONE COMPANY. B. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY, PRIOR TO SUBMITTING BID, ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC). TWO AND THREE POLE CIRCUIT BREAKERS SHALL BE COMMON TRIP. NO TIE HANDLES PERMITTED. ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE LISTED, FOR THE INTENDED USE, WITH UNDERWRITER'S LABORATORY, INC. (U.L.) WHERE STANDARDS HAVE BEEN ESTABLISHED BY U.L. ALL CONDUCTORS SHALL BE IN CONDUITS, ALL CONDUITS SHALL BE INTERMEDIAIE (IMC) OR RIGID GALVANIZED STEEL (RGS) EXCEPT THAT, (A) POLY VINYL CHLORIDE (PVC) CONDUITS MAY BE USED IN CONCRETE SLABS AND UNDERGROUND PROVIDED ELBOWS AND RISERS ARE RGS) (B) ELECTRICAL NUN - METALLIC TUBING (ENT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL TIGHT E(LEXIBLEOCONDUITSWHERE REQUIRED, 0)1 FLEXIBI E) METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS. ALL CONDUITS IN HAZARDOUS AREAS PER NEC SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. PROVIDE LAMPS WITH FIXTURES, VERIFY LAMP TYPE WITH MANUFACTURER. COORDINATE ELECTRIC SERVICE WITH POWER COMPANY. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO ARCHITECTURAL PLANS A140 ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE, ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN AND /OR NOTED ON THE DRAWINGS. THIS SHALL INCLUDE ANY AND ALL FABRICATIONS PRIOR TO INSTALLATION. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCED ORDERING OF LONG LEAD ITEMS, AS NOT TO INTERFERE Willi THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED ON THE DRAWINGS. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED ELECTRICAL CONTRACTOR AND IN A FIRST -CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES, THE ELECTRICAL_ CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR TO ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT AND FURNISHINGS CAUSED DURING PERFORMANCE OF WORK. THE ELECTRICAL CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROO14 CLEAN AT THE END OF EACH WORKING DAY. IT SHALL NOT BE THE INTENT OF THESE PLANS AND /OR SPECIFICATION TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE ELECTRICAL CONTRACTOR SHALL BE EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEI4 AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT 10 BE PLACED IN PROPER WORKING ORDER. WI4ERE CORE DRILLING OF FLOOR /WALLS IS REQUIRED, CONTRACTOR SHALL SEAL OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN AND FUNCTIONAL, THE CONTRACTOR SHALL INSTALL ONLY' 014E CONDUIT PER HOLE AND SEAL T14C OPENING AROUND THE CONDUIT AS SPECIFIED. ELECTRICAL CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FUR EQUIPMENT PRIOR TO C❑NSTRUCTIUN. METER CANS, HUBS, & LUGS FOR SAME ARE TO BE FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED WITH F.P.L. PRIOR 10 BID. LIGHTING PLAN SCALE : 1/4" - V -0" GALLARDO ELECTRICAL SYMBOL LEGEND /O/ FLUORESCENT LIGHT FIXTURE Q DOWN LIGHT T --i FLUORESCENT STRIP © EXIT LIGHT 1:J EMERGENCY BATTERY PACK Q DUPLEX RECPT - 20 AMP (FLOOR BOX) 4� DUPLEX RECPT - 20 AMP (18' A.F.F.) ' DUPLEX RECPT - 20 AMP (42' A.F.F.) 7 SPECIAL PURPOSE RECEPTACLE(18' A.F.F.) [] SINGLE POLE SWITCH - 20 AMP (48' A.F.F.) So THREE WAY SWITCH - 20 AMP (48' AF.F.) 0 DIMMER SWITCH 2000 WATTS 48' A.F.F.) Q MOTOR RATED SWITCH RHEOSTAT FAN CONTROL (48' AF FJ Q JUNCTION BOX ELECTRICAL PANELBOARD Ur THERMOSTAT Q DUCT SMOKE DETECTOR /O/ MOTOR 0 TRANSFOR14ER /VN/V'\A FLEXIBLE CONDUIT 1 GROUNDING ELECTRODE 6 CONDUCTOR SYSTEM !] TELEVISION OUTLET (18' A.F.F.) E INTERCOM SYSTEM ® CENTRAL VACUUM STATION v TELEPHONE OUTLET (FLOOR BOX) 7 TELEPHONE OUTLET (18' A.F.FJ [] COMPUTER OUTLET (18' A.F.F.) So SMOKE DETECTOR (PHOTOELECTRIC TYPE) 0 DUCT SMOKE DETECTOR Q SPEAKER - CEILING MOUNTED FUSIBLE DISCONNECT SWITCH 3144 PULE DISCONNECT FRAME _ MANUFACTURER FUSE RECUI4MENDA HON 52', 5 BLADE CEILING FAN WITH FAN J -BUX VERIFY COLOR WITH TENANT i .. A i xr iA ,' n4 40 t- A � tit '� y i ♦ � �.; +'� may, ARCH LICENSE AR 07671 L� C 0 QD ­�0 U) U �_ 0q)(1) U� ARCH. LICENSE AR 07671 job no. 9903 date. 01 -28 -07 scale. As Shown drawn by. A G. reviewed by. C.M issued. 01 -28 -07 31 U O E .> Q� 0 0 0 (D V) 0 m * N - O �LL_ �+- v .��Q0 L� C 0 QD ­�0 U) U �_ 0q)(1) U� ARCH. LICENSE AR 07671 job no. 9903 date. 01 -28 -07 scale. As Shown drawn by. A G. reviewed by. C.M issued. 01 -28 -07 31