07-780-026I ELECTRICAL NOTES 1. ALL C1114UUCTURS SHALL BE COPPER, RATED 75 C WET /DRY EXCEPT WHERE OTHERWISE REQUIRED BY U,I_, OR CODES, UHN. MINIMUM WIRE SIZE SHALL BE 1112 AWG, EXCLUD114G CONTROL WIRING. 2. ALL CONDUIT RISERS SMALL BE RIGID GALVANIZED STEEL (RGS). WHERE CONDUIT BENDS UPWARD FROM UNDERGROUND TO ABOVE GROUND, USE AN APPROVED PVC TO RGS COUPLER, AS REQUIRED. RGS CONDUITS SHALL EXTEND A MINIMUM OF 10' BELOW GRADE. J. UNLESS NUIED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. 4. ENTIRE INSTAI_I_ATION SHALL BE IN ACCORDANCE `,![1H THE NATIONAL ELECTRICAL CODE, LATEST EDITION (NEC) AND THE LATEST EDITIONS OF THE FI_URIDA BUILDING CODE AND ALL LOCAL CODES, RULES AND ORDINANCES HAVING JURISDICTION. 5. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT ROUTING SHALL BE DETERMINED 114 THE FIELD, UNLESS OTHERWISE NOTED, 6. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC TO ACCOMMODATE EQUIPMENT SERVED, INCLUDING REQUIRED FUSES, LION. SWITCHES SHALL BE HORSE POWER RATED AND SIZED FOR 112 MAX, HORSEPOWER, HEAVY DUTY TYPE. 7. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO 111E WEATHER. ALL FLEX CONDUITS CONNECTED TU SUCII EQUIPMENT SHALL BE LIQUID TIGHT, 0, WIRE WAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NUIED (UON). 9. COORDINATE ALL ELECTRICAL SITE WORK Willi GENERAL CONTRACTOR. 10. FOR UNDERGROUND ELECTRICAL CUNUUITS, PROVIDE FULL BOXES, SUCH THAT NO SINGLE_ CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE, WARNING TAPE WHICH SAYS 'WARNING BURIED ELECTRIC' SHALL BE PLACED IN TRENCHES ABOVE ALL UNDERGROUND ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL BE RGS. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY SHALL BE SCHEDULE 40 PVC. ALL CONDUIT RISERS SHALL BE RGS. IT. FOR TELEPHONE SYSTEI•11 A. PROVIDE GROUNDING FOR ALL TELEPIIIJ14E OIJILETS AND EQUIPMENT PER REQUIREMENTS OF TELEPHONE COMPANY. B. VERIFY LOCATION OF JELEPlIU14E SERVICE WITH TELEPHONE COMPANY, PRIOR TO SUBMITTING BID. 12. ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC). TWO AND THREE PULE CIRCUIT BREAKERS SHALL BE COMMON TRIP. NO TIE HANDLES PERNITTED. 13, ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE LISTED, FUR THE INTENDED USE, WITH UNDERWRITER'S LABORATORY, INC. (U.L.) WIIERE STANDARDS HAVE BEEN ESTABLISHED BY U.L. 14, ALL CONDUCTORS SHALL BE IN CONDUITS, ALL CONDUITS SIIALL BE INIERMEDIATE 0110 OR RIGID GALVANIZED STEEL (RGS) EXCEPT THATI (A) POLY V114YL CHLORIDE (PVC) CONDUITS MAY BE USED IN CU14CRETE SLABS AND UNDERGROUND PROVIDED ELBOWS AND RISERS ARE RGSI(B) ELECTRICAL NUN - METALLIC TUBING, (ENT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT 10 MECHANICAL DAMAGE DAMP CU14DIT1014S OR CORROSIVE CONDITIONS) (C) LIQUID TIGHT (LEXIBLE CONDUIT WHERE REQUIRED, (D) FLEXIBLE METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS, ALL CONDUITS IN HAZARDOUS AREAS PER NEC SHALL MEET THE REQUIREMENTS OF NEC CIIAPIER 5. 15. PROVIDE LAMPS WITII FIXTURES, VERIFY LAMP TYPE WITH MANUFACTURER. 16. COORDINATE ELECTRIC SERVICE WITH POWER COMPANY. 17, ELECTRICAL_ CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TU ARCH[TECIURAL PLANS AND ELEVATIUIIS FUR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE, 10. ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN AND /UR NOTED ON THE DRAWINGS. 111IS SMALL INCLUDE ANY AIJD ALL FABRICATIU14S PRIOR TO INSTALLATION. 19. IT SHALL BE THE RESPONSIBILITY OF 111E ELECTRICAL CONTRACTOR FUR IIIE ADVANCED ORDERING OF LONG LEAD [ISMS, AS NOT lO INTERFERE WITH TIIE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. 20. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY 10 ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED 014 THE DRAWINGS. 21. IT SHALL BE U14DERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED ELECTRICAL CUNTRACIUR AND IN A FIRST -CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHAI_I. MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL URU[NANCE AND GOVERNING AUIIIURITIES. 22. THE EI_ECIRICAI_ CLINTRACIUR SMALL BE RESPONSIBLE TO REPAIR TO ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT AND FURNISHINGS CAUSED DURING PERFUIRMA14CE OF WORK. 23. THE EI_FCTRICAL CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE FRU14 DEBRIS AT ALI. TIMES AND SAID AREAS SHALL BE LEFT BROU14 CLEAN AT THE END OF EACH WORKING DAY. 24, IT SHALL NOT BE THE INTENT OF THESE PLANS AIJD /OR SPECIFICATION TO SHOW EVERY MINOR DETAIL OF CUNS1RUCT1UN. THE ELECTRICAL CONTRACTOR SMALL BE EXPECTED TU FURNISH AND INSTALL_ ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM ANO PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 25, WHERE CORE DRILLING OF FLOOR /WALLS IS REQUIRED, CONTRACTOR SHALL SEAL OPEN114GS WATERTIGITT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALI_ COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN AND FUNCTIONAL, THE CONTRACTOR SHALL INSTALL 0141-y' LINE CONDUIT PER HOLE AND SEAL THE OPENING AROUND TILE CONDUIT AS SPECIFIED, 26. ELECTRICAL CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FUR EQUIPMENT PRIOR 10 CONSTRUCTION. 27. METER CANS, HUBS, & LUGS FOR SAME_ ARE TO BE FURNISHED & INSTALLED BY ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED WITH F.P.L. PRIOR 10 DID. LIGHTING PLAN SCALE i/4" = 1' -0" GAILARUO B , i 1 (-rYP) i 1 1 / i i B (TYP) I I 1 i 1 r r , (� I \ -------- -- (TYP) -- , -- - --- -i Ct V I i 1 NOTE: CONNECT EXIT AND EMERGENCY LIGHTS TO Q NEAREST LIGHTING CIRCUIT AHEAD OF SWITCHES U AND CONTROL DEVICES. ELECTRICAL SYMBOL LEGEND F—J FLUORESCENT LIGIIT FIXTURE O DOWN LIGHT F - -i FLUORESCENT STRIP p EXIT LIGHT Q EMERGENCY BATTERY PACK 0 DUPLEX RECPT — 20 AMP (FLOUR BUX) 9P DUPLEX RECPT — 20 AMP (18' A.F.F.) U DUPLEX RECPT — 20 AMP (42' A.F.F.) ® SPECIAL PURPOSE RECEPTACLE(18' A.F.F.) (Cj SINGLE PULE SWITCH — 20 AMP (40' A.F.F.) so TIIREE WAY SWITCN — 20 AMP (40' A.F.F.) DQ DIMMER SWITCN 2000 WATTS 40' A.F.F.) 0 MOTOR RATED SWITCII Cy RHEOSTAT FAN CONTROL (48' A.F.F.) Q JUNC110" BOX C ELECTRICAL PANELBOARD Qt THERMOSTAT OD DUCT SMOKE DETECTOR 10/ MOTOR OT TRANSFORMER INv%l /lv\ FLEXIBLE CONDUIT I GROUNDING ELECTRODE & CONDUCTOR SYSTEM Q TELEVISION OUTLET (18' A.F.F.) 1C INIERCUN SYSTEI4 CENTRAL VACUUM STATION U IELEPHONE UUTLEF (FLUOR BOX) TELEPHONE OUILEF (18' A.F.F.) (Cj CU14PUIER OUTLET (18' A.F.F.) so SMOKE DETECTOR (PIIOTOELECTRIC TYPE) DQ DUCT SMOKE DETECTOR 0 SPEAKER — CEILING MUUNTED Cy FUSIBLE DISCONNECT SWITCH 3J- -Q PULE DISCONNECT FRA14E_ MANUFACTURER FUSE REC014MENUATICU4 52', 5 BLADE CEILING FAN WITH FAN J -BUX VERIFY COLOR WITH TENANT 1­16_1�00 1119 ----- I ---- �1 ---- I I I I r � ! 1 1 B j TYP B (TYP) B ( ) Lam_ (TYP) - _ - r - '1 1 __ O O 0 _ 0 , B i (TYP) T1 —8 _ T1 —10 I -- ------------------------- - - - - -- I "- - - - - -- I ,, I - - O " - - - - -- I i 1 - ; - I B (TYP) / _ � r T1 -6 I L, —0J r I —Dy — I (TYP) B / ` 1 I i 1 � , / r I 1 _ B (TYP) C i I _� G I -rY P I , r , r ! 1 r � 1 , (TYP)1 1 (TYP)" 'i ,i ilr _ r I } I _O_ o e I .� P 1--�—I P-N-L/ P N RELOCATED - E ) (TY I (TYP) i I /. - �A m y Rrr 4 3\ ''i; U_ P� a. dIc ARCH.LICENE AR 07671 L_t__. O W _U O o �1 =N-C C)� 0 0 o c) LL C 1 D � cfl _z EL W V I z 1 0(1) 1 Gr (TYP) i I /. - �A m y Rrr 4 3\ ''i; U_ P� a. dIc ARCH.LICENE AR 07671 L_t__. O W _U O o �1 =N-C C)� 0 0 o c) LL C 1 D � cfl _z EL W V I z (J� U - a UU U n 1 U ARCH. LICENSE AR 07671 job no. 9903 date. 01 -28 -07 scale. As Shown drown by. A G. reviewed by. C.M issued. 01 -28 -07 sheet no. E-2 0(1) (J� U - a UU U n 1 U ARCH. LICENSE AR 07671 job no. 9903 date. 01 -28 -07 scale. As Shown drown by. A G. reviewed by. C.M issued. 01 -28 -07 sheet no. E-2