07-780-017,/ASHRAE 62 CONFORMANCE UNIT # EXHAU `r FAN SCHEDULE AIR DISTR- iowrION SCHEDULE REQ'D O.A. VENTILATION (CFM) FAN LOCATION SERVED MANUFACTURER MODEL VOLT CFM HP OR WATTS FRAME S.P DRIVE SONES WEIGHT 75 WATTS W 0.375 DIRECT 1.5 10 LBS. EF -1 TOILET GREENHECK SP-13110 120-1-60 EF -2 TOILET GREENHECK SP-B110 120 -1 -60 75 WATTS NOTES 0.375 DIRECT 1.5 10 LBS. C A CEILING 24X24 AS SHOWN AS SHOWN TYPE 3 (LAY -IN) DIFFUSER NOTES: 1. INTERLOCK WITH LIGHTSWITCH (LION). 5. MOTOR SHALL COMPLY WITH FLORIDA ENERGY CODE 2. UNIT- MOUNTED SPEED CONTROLLER. 6. ALL FANS SHALL BE Mild. UL -705 LISTED. 3. PROVIDE BACKDRAFT DAMPER. 7. MANUFACTURER SHALL ?ROVIDE SPEED CONTROLLER 4. PROVIDE FACTORY ISOLATORS CONNECTION FOR ALL EXHAUST FANS AND SHALL BE A MIN. OF 87%EFF. FACTORY WIRED FOR ONE POINT ,/ASHRAE 62 CONFORMANCE UNIT # OCCUPANCY (�f OF PEOPLE) AIR DISTR- iowrION SCHEDULE REQ'D O.A. VENTILATION (CFM) TOTAL O.A. SUPPLIED (CFM) AREA SERVED MARK TYPE OVERALL NECK SIZE AIR FLOW FRAME THROW C)-) 0 ._ MAKE MODEL REMARKS W SIZE (CFM) C - D. -0 (D V) Cr SEE PLAN y- 41 TITUS TDC -AA SEE NOTES ARCH LICENSE AR n7R i 1 C A CEILING 24X24 AS SHOWN AS SHOWN TYPE 3 (LAY -IN) DIFFUSER B - CEILING AS SHOWN AS SHOWN AS SHOWN TYPE 1 (SURFACE) SEE PLAN TITUS TDC -AA SEE NOTES GRILLE - C CEILING AS SHOWN AS SHOWN AS SHOWN TYPE (LAY -IN) SEE PLAN TITUS TLF -AL SEE NOTES GRILLE D CEILING AS SHOWN AS SHOWN AS SHOWN TYPE 3 (LAY -IN) SEE PLAN TITUS 3FL SEE NOTES GRILLE - E CEILING AS SHOWN AS SHOWN AS SHOWN TYPE" 1 (SURFACE) SEE PLAN TITUS 3FL SEE NOTES GRILLE DIFFUSER GRILLE LEGENDS NOTES; ,& 1. TITUS IS THE BASIS OF DESIGN AND STANDARD FOR COMPARISON. DEVICE TYPE THROW PATTERN 2. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPE. NECK SIZE--8"O Al 3. PROVIDE OFF WHITE FINISH UNLESS OTHERWISE NOTED 100 AIR VOLUME (CFM) (SUBJECT TO ARCH. APPROVAL). 6X6 -FACE -ACE SIZE 4. SEE FLOOR PLANS FOR VARIATIONS OF THROW & DIRECTIONS. OR OVERALL SIZE 5. ALL AIR DISTRIBUTION DEVICES ARE ALUMINUM. 6. PROVIDE IF REQUIRED TRANSITIONS FOR NECK SIZES. ,/ASHRAE 62 CONFORMANCE UNIT # OCCUPANCY (�f OF PEOPLE) INTERMITTENT OCCUPANCY FACTOR ( +) O.A. VENTILATION (CFM PER PERSON) REQ'D O.A. VENTILATION (CFM) TOTAL O.A. SUPPLIED (CFM) AREA SERVED AHU -101 22 0.75 20 330 330 NE OFFICE C)-) 0 ._ W Lij 7 C NOTE: * ASHRAE 62 -1989 ALLOWS "WHERE PEAK OCCUPANCIES OF LESS THAN THREE HOURS DURATION OCCUR, THE OUTDOOR AIR FLOW RATE MAY BE DETERMINED ON THE BASIS OF AVERAGE TTHE AVERAGE OCCUPANCY USED THE NOTRLESS THAN ONET10 HALF THE MAXIMUM PROVIDED BASIC TEST FOR SMOKE DETEC"TO� WITH AIR HANDLING UNIT OFF AND POWER APPLIED TO THE AIR DUCT DETECTOR /SENSOR, INTRODUCE SMOKE INTO THE DETECTOR /SENSOR, OR ACTIVATE THE BUILT -IN TEST FEATURE AS DESCRIBED IN THE 4098 DETECTORS, SENSORS AND BASES APPLICATION MANUAL 574 -709. OBSERVE ALARM LED OPERATIONS. RESTORE NORMAL OPERATION TO DETECTOR BY MOMENTARILY REMOVING AC POWER, OR BY REMOVING AND REPLACING THE DETECTOR HEAD AFTER SMOKE HAS BEEN CLEARED FROM ITS CHAMBER. SPLIT SYSTEM AIR HANDLING UNIT SCHEDULE AIR COOLED CONDENSING UNIT SYSTEM DATA AIR IIANDLING UNI f COOLING CAPACITY EER REMARKS AIRFLOW CFM) ESP FAN D�( COIL HEATER ELECTRICAL WT MARK MODEL Wr ELECTRICAL COMPRESSOR FAN UNIT TMB° SMBH EAT (SEER) MARK LOCATION TRANE ( ROWS NO. LBS VOLTS -PH -HZ QTY. TONS RLA HP FLA MCA MOCP DB /WB MODEL -- SERVED N0. TOTAL OA HP FLA / /F.P.I. KW STAGE V /0 /HZ MCA MOCP B 12 7 2 1 208/1/60 47 50 173 CU -101 2TTA0060A300 227 208/3/60 1 5.0 19.7 0.25 1.9 27 45 59. - 39.9 78.4'/66.4' 10.75 SEE NOTES AHU -101 NE OFFICE TWE060P13 1,600 330 0.50 0.50 3.1 3/ GENERA( NoIES FOR ALL UNIT 1. TRANE IS THE BASIS OF DESIGN AND THE STANDARD FOR COMPARISON. 2. OUTSIDE AIR DESIGN CONDITIONS: 91'F0B - 79'FOB. 3. MECHANICAL CONTRACTOR SHALL PROVIDE, AND ELECTRICAL CONTRACTOR SHAILL WIRE AND INSTALL DISCONNECT FOR DISCONNECT FOR CONDENSING UNIT 4. MECHANICAL CONTRACTOR SHALL PROVIDE, AND ELECTRICAL CONTRACTOR SHAILL 5. MANUFACTURER SHALL PROVIDE COMPLETE WITH ELECTRIC HEAT AND SINGLE (POINT ELECTRICAL CSS, COASTAL FILTER, CRANKCASE HEATER, ANTI-SHORT SS 6. MANUFACTURER SHALL PROVIDE COMPLETE WITH FILTER - DRIER, LIQUID LINE SOLENOID, SIGHT GLA, CYCLE PROTECTION, HIGH- PRESSURE SWITCI1.L PRESSURE SWITCH. N D TI IE.RMOSTATIC EXPANSION VALVE. 7. CONTRACTOR SHALL PROVIDE COMPLETE WITH 95% 8. MANUFACTURER SHALL PROVIDE COMPLETE WITH FOUR INCH 457, A.D.S. EFFICIENCY FILTERS FOR AHU -101, & 102. 9. PROVIDE A/C UNITS WITH DIGITAL PROGRAMMABLE HEATING AND COOLING THERMOSTAT WITH ON-OFF FOR INNS ALLEU LENGTH OF RUN. MECHANICAL 10. SIZE AND RUN REFRIGERANT PIPING AS PER MANUFACTURER'S. AND ASHRAES PU @USHED RECOMMENDATIONS CONTRACTOR SHALL CLOSELY COORDINATE ALL REQUIRED APPURTENANCES REQUIRED FOR THE INSTALLED DISTANCE REQUIREMENTS WITH THE UNIT MANUFACTURER. 11. PROVIDE PROPER VIBRATION ISOLATORS AS PER MANUFACTURERS RECOMMENIDATIONS, PLANS AND SPECIFICATIONS. 12. INSULATE REFRIGERANT SUCTION LINE WITH 3/4 , FIRE RETARDANT ARMAFLEX. 13. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES. 14. PROVIDE BUILT -IN DISCONNECT WITH ALL AIR HANDLING UNITS. 15. CONTRACTOR SHALL COORDINATE WITH STRUCTURAL ENGINEER SIZE OF HANGER RODS AND, CONCRETE INSERT FOR ALL EQUIPMENT. 16. ALL AIR HANDLING UNITS 'AND CONDENSING UNITS INDICATED IN THE BUILL.NG SHALL HAVE THE FOLLOWING. a) NON BLEED THERMOSTATIC EXPANSION VALVE, CRANK CASE HEATER, SOLENOID VALVE, HARD START KIT & THE PIPING Si1ALL BE INSTALLED USING LONG RADIUS ELBOWS. E_ QUIPMENT SYSTEM NOTES (TRANEL; * AIR HANDLERS MUST HAVE A LIQUiD LINE SOLENOID INSTALLED AT THE AIR HANDLERS. * PROVIDE ALL CONDENSER COMPRESSORS WITH CRANK CASE HEATERS. * 2ND MOUNTED CONDENSING UNITS TO BE POSITIONED WITH UNITS SERVING THE LOWEST LEVELS CLOSER TO THE LINE CHASE TO MINIMIZE REFRIGERANT LINE DISTANCE. * PROVIDE EVAPORATOR COILS WITH NON BLEED TXV'S * ADD 2 OZ. OF OIL FOR EACH 10 FEET OF LINE. OVER 200 FEET. * ALL LINE LENGTH, SIZES AND UNIT LOCATION MUST BE REVIEWED AND APPROVED BY THE INSTALLING CONTACTOR. ALL LINE LENGTH AND SIZES MUST FOLLOW TRANE APPLICATION GUIDE PUBLICATION # 32- 3CJJ -03, THEN SUBMITTED TO THE LOCAL TRANE OFFICE FOR APPROVAL. %It% of agUtfl Building Do%p ar AD U7 0 (p) U s p C)-) 0 ._ W Lij 7 C - D. -0 (D V) Cr y- 41 0 ' �-- Cfl ARCH LICENSE AR n7R i 1 C U7 0 (p) U C)-) 0 ._ W U 0 7 C - D. -0 (D V) Cr y- 41 0 ' �-- Cfl C U .o a cD C�d 0 (D Co V J c0 00) r� V) Q) U a� 0- ai 0 I- 0 CD ° Y U__ o U ARCH. LICENSE AR 07671 job no. 9903 date. 01-28-07. scale. As Shown drawn by. A G. reviewed by. C.M issued. 01 -28 -07 I