07-992-019r W Y ELECTRICAL NOTES 1. ALL CONDUCTORS SHALL BE COPPER, RATED 75 C WET /DRY EXCEPT WHERE OTHERWISE REQUIRED BY U.L. OR CODES, LION, MINIMUM WIRE SIZE SHALL BE R12 AWG. EXCLUDING CONTROL WIRING. 2. ALL CONDUIT RISERS SHALL BE RIGID GALVANIZED STEEL (RGS). WHERE CONDUIT )ENDS UPWARD FROM UNDERGROUND TO ABOVE GROUND, USE AN APPROVED PVC TO RGS COUPLER, AS REQUIRED. RGS CONDUITS SHALL EXTEND A MINIMUM OF le' BELOW GRADE. 3. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. 4, ENTIRE INSTALLATION SHALL BE IN ACCORDANCE `,WITH THE NATIONAL ELECTRICAL CODE. LATEST EDITION (NEC) AND THE LATEST EDITIONS OF THE FLORIDA BUILDING CODE AND ALL LOCAL CODES, RULES AND ORDINANCES HAVING JURISDICTION, 5. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY, EXACT ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS OTHERWISE NOTED. G. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC TO ACCOMMODATE EQUIPMENT SERVED, INCLUDINIi REQUIRED FUSFS, DUN. SWITCHES SHALL BE HORSE POWER RATED AND SIZED FOR 112 MAX, HORSEPOWER, HEAVY DUTY TYPE. 7. ALL ELECTRICAL EQUIPMENT SMALL BE RAINTIG14T WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. B, WIRE WAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED (UON). 7. COORDINATE ALL ELECTRICAL SITE WORK WITH GENERAL CONTRACTOR. 10, FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE FULL BOXES, SUCH THAT NO SINGLE CONDUIT RUN HAS (ENDS IN EXCESS OF 360, PULL BOXES SHALT_ BE SUITABLE AND APPROVED FOR THE INTENDED USE. WARNING TAPE 'WHICH SAYS 'WARNING BURIED ELECTRIC" SHALL BE PLACED IN TRENCHES ABOVE ALL UNDERGROUND ELECTRIC CONDUITS, WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL BE RGS. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY SHALL DE SCHEDULE 40 PVC, ALL CONDUIT RISERS SHALL BE RGS. 11. FOR TELEPHONE SYSTEMr A. PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND EQUIPMENT PER REQUIREMENTS OF TELEPHONE COMPANY. 1, VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY, PRIOR TO SUBMITTING BID. 12, ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC). TWO AND THREE PULE CIRCUIT BREAKERS SHALL BE COMMON TRIP. NO TIE HANDLES PERMITTED. 13, ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SMALL BE LISTED, FOR THE INTENDED USE, WITH UNDERWRITER'S LABORATORY, INC. (U.L.) WHERE STANDARDS HAVE BEEN ESTABLISHED BY U.L. 14, ALL CONDUCTORS SHALL BE IN CONDUITS. ALL CONDUITS SHALL BE INTERMEDIATE (IMC) OR RIGID GALVANIZED STEEL (RGS) EXCEPT THAT, (A) POLY VINYL CHLORIDE (PVC) CONDUITS MAY BE USED IN CONCRETE SLAPS AND UNDERGROUND PROVIDED ELBOWS AND RISERS ARE RGSI (D) ELECTRICAL NON - METALLIC TUBING (ENT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL TIGHT EkEXilLEOCONDUITS HERE REQUIRED, (D) FLEXIIBLE) METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATIONS, ALL CONDUITS IN HAZARDOUS AREAS PER NEC SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. 15. PROVIDE LAMPS WITH FIXTURES, VERIFY LAMP TYPE WITH MANUFACTURER. 16. COORDINATE ELECTRIC SERVICE WITH POWER COMPANY. 17. ELECTRICAL_ CONTRACTOR SHALL NOT SCALE DRAWINGS, CONTRACTOR SHALL REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE. 10. ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CUNDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN AND /UM NOTED ON THE DRAWINGS. THIS SHALL INCLUDE ANY AND ALL FABRICATIONS PRIOR TO INSTALLATION. 19. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCED ORDERING OF LONG LEAD ITEMS, AS NOT TO ?NTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. 20. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR i0 PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED ON THE DRAWINGS. 21. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DOME BY A LICENSED ELECTRICAL CONTRACT ❑R AND IN A FIRST -CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES. 22. THE ELECTRICAL CONTRACTOR SMALL DE RESPONSIBLE TO REPAIR TO ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT AND FURNISHINGS CAUSED DURING PERFORMANCE OF WORK. 23. THE ELECTRICAL CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL BE LEFT BROOM CLEAN AT THE END OF EACH WORKING DAY, 24. IT SIIALL NOT BE THE INTENT OF THESE PLANS AND /OR SPECIFICATION TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE ELECTRICAL CONTRACTOR SHALL BE EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO DE PLACED IN PROPER WORKING ORDER. 25. WHERE CORE DRILLING OF FLOOR /WALLS IS REQUIRED, CONTRACTOR SHALL SEAL OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED, LOCATION OF CORED HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN AND FUNCTIONAL. THE CONTRACTOR SHALL INSTALL ONLY' ONE CONDUIT PER HOLE AND SEAL THE OPENING AROUND THE CONDUIT AS .SPECIFIED. 26. ELECTRICAL CONTRACTOR SMALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR TO CONSTRUCTION, 27. METER CANS, HUBS, R LUGS FOR SAME_ ARE TO BE FURNISHED L INSTALLED BY ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED WITH F.R.L. PRIOR TO DID. ELECTRICAL SYMBOL LEGEND Is r; THIS AREA UNDER BASE/ BUILDING PERMIT r \ 5-691 I —0 _oJ� �o- I S W/H ` EXIST. I I P.N.L (TYP) ! (TYP) i 1 ' r 1 _0117 ( TYP) it f i 1 I � ♦ i � i .i EF. 2 —o —U F_ 0_ i i HC. _. _.______- — ` O ^ ------- - - - - -- RLSTROOM I L: l` I 1 1 B 1 1 i i (TYP) i i r I it o - LIGHTING PLAN SCALE : 1/4" = 1' -0" GALLARDO , ♦ l\ I 1 B I I. i (TYP)i I r i I r I i �1 r t l I 1 B I i 1 (TYP) i r r i f I I � I NOTIN CONTRACt" W� C. m ) I I' '\T2 -2 I 11 ®r i 1 � 1 j r I o 1 r J (TYP) ------ r , I I I I , NOTE: ' CONNECT EXIT AND EMERGENCY LIGHTS TO ,I �P NEAREST LIGHTING CIRCUIT AI -BEAD OF SWITCHES u AND CONTROL DEVICES. I 1 T FLUORESCENT LIGHT FIXTURE 0 DOWN LIGIIT 1---i FLUORESCENT STRIP ^at EXIT LIGIIT In EMERGENCY BATTERY PACK 0 DUPLEX RECPT - 20 AMP (FLOOR IIOX) ® DUPLEX RECPT - 20 AMP (19' A.F.F.) Q' DUPLEX RECPT - 20 AMP (42' A.F.F,) `r SPECIAL PURPOSE RECEPTACLE(IN' A.F.F.) © SINGLE POLE SWITCH - 20 AMP (41' A.F.F.) s, THREE WAY SWITCH - 20 AMP (41' A.F.F.) © DIMMER SWITCH 2000 WATTS 4B' A.FF,) Qs MOTOR RATED SWITCH C P RHEOSTAT FAN CONTROL (41' A.F.F.) O JUNCTION BOX ELECTRICAL PANELBOARD O THERMOSTAT Oi DUCT SMOKE DETECTOR Is r; THIS AREA UNDER BASE/ BUILDING PERMIT r \ 5-691 I —0 _oJ� �o- I S W/H ` EXIST. I I P.N.L (TYP) ! (TYP) i 1 ' r 1 _0117 ( TYP) it f i 1 I � ♦ i � i .i EF. 2 —o —U F_ 0_ i i HC. _. _.______- — ` O ^ ------- - - - - -- RLSTROOM I L: l` I 1 1 B 1 1 i i (TYP) i i r I it o - LIGHTING PLAN SCALE : 1/4" = 1' -0" GALLARDO , ♦ l\ I 1 B I I. i (TYP)i I r i I r I i �1 r t l I 1 B I i 1 (TYP) i r r i f I I � I NOTIN CONTRACt" W� C. m ) I I' '\T2 -2 I 11 ®r i 1 � 1 j r I o 1 r J (TYP) ------ r , I I I I , NOTE: ' CONNECT EXIT AND EMERGENCY LIGHTS TO ,I �P NEAREST LIGHTING CIRCUIT AI -BEAD OF SWITCHES u AND CONTROL DEVICES. I 1 T MOTOR El TRANSFORMER FLEXIBLE CONDUIT ow GROUNDING ELECTRODE L CONDUCTOR SYSTEM In TELEVISION OUTLET (10' A.F.F.) rc INTERCOM SYSTE14 ® CENTRAL VACUUM STATION TELEPHONE OUTLET (FLOOR BOX) `r TELEPHONE OUTLET (18' A.F.F.) © COMPUTER OUTLET (I$' AF,F) s, SMOKE DETECTOR (PHOTOELECTRIC TYPE) © DUCT SMOKE DETECTOR Qs SPEAKER - CEILING MOUNTED C P FUSIBLE DISCONNECT SWITCH 3LF ' POLE DISCONNECT FRAME MANUFACTURER FUSE RECOMMENUATIUN O 52', 5 BLAnE CEILING FAN WITH FAN J- BUX VERIFY COLOR WITH TENANT Is r; THIS AREA UNDER BASE/ BUILDING PERMIT r \ 5-691 I —0 _oJ� �o- I S W/H ` EXIST. I I P.N.L (TYP) ! (TYP) i 1 ' r 1 _0117 ( TYP) it f i 1 I � ♦ i � i .i EF. 2 —o —U F_ 0_ i i HC. _. _.______- — ` O ^ ------- - - - - -- RLSTROOM I L: l` I 1 1 B 1 1 i i (TYP) i i r I it o - LIGHTING PLAN SCALE : 1/4" = 1' -0" GALLARDO , ♦ l\ I 1 B I I. i (TYP)i I r i I r I i �1 r t l I 1 B I i 1 (TYP) i r r i f I I � I NOTIN CONTRACt" W� C. m ) I I' '\T2 -2 I 11 ®r i 1 � 1 j r I o 1 r J (TYP) ------ r , I I I I , NOTE: ' CONNECT EXIT AND EMERGENCY LIGHTS TO ,I �P NEAREST LIGHTING CIRCUIT AI -BEAD OF SWITCHES u AND CONTROL DEVICES. I 1 T ARCH.LICENSE I AR 07671 . W U N LL O _ LL_ LL 0 0� - E U C) o W �^ L O LLJ Cr- U) (9 Q LLJ75 6 E U U O L O 0-) In r7 00 00 ow In U ., cn a� U J w+ yy���J�fff ti 1 CD It ARCH.LICENSE I AR 07671 . W U N LL O _ LL_ LL 0 0� - E U C) o W �^ L O LLJ Cr- U) (9 Q LLJ75 6 E U U O L O 0-) D q) 4- C ! — W � n1 � �LJ � � _ z U CD ARCH. LICENSE AR 07671 job no. 9906 date. 05 -24 -07 scale. As Shown drawn by. A G. reviewed by. C.M issued. 05 -24 -07 sheet no. F-2 In r7 00 00 ow In U cn a� U J a� 07 �I CD It D q) 4- C ! — W � n1 � �LJ � � _ z U CD ARCH. LICENSE AR 07671 job no. 9906 date. 05 -24 -07 scale. As Shown drawn by. A G. reviewed by. C.M issued. 05 -24 -07 sheet no. F-2