07-878-001
SEQUENCE OF OPERATION: 1. FIRE ALARM INITIATING DEVICES: A.- MANUAL FIRE ALARM PULL STATIONS ACTIVATION OF ANY FIRE ALARM PULL STATION SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: - ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY. - ACTIVATE THE ALARM LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. - INDICATE THE LOCATION OF THE PULL STATION BY DISPLAYING IN ENGLISH THE ALARMED DEVICE ON THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNC - TRANSMITS A FIRE ALARM SIGNAL TO THE DESIGNATED THIRD PAR LISTED CENTRAL MONITORING STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. Q B.- AUTOMATIC FIRE DETECTORS ACTIVATION OF ANY AUTOMATIC FIRE DETECTION DEVICE SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: - ACTIVATE THE AUDIBLE AND VISUAL SIGNAL THROUGHOUT THE FACILITY. - ACTIVATE THE ALARM LIGHT AND SOUNDER AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. - INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN ENGLISH, THE ALARMED DEVICE ON THE FACP ALPHANUMERIC DISPLAY AND REMO CIATOR. TRANSMITS A FIRE ALARM SIGNAL TO THE DESIGNATED THIRD PAR LISTED ENTRAL MONITORING STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. Q 2.- SUPERVISORY ALARM INITIATING DEVICES, 1 A. -DUCT DETECTORS ACTIVATION OF ANY DUCT DETECTOR SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: - ACTIVATE THE SUPERVISORY LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. - INDICATE THE LOCATION OF THE DUCT DETECTOR BY DISPLAYING IN ENGLISH THE ACTIVATED DEVICE ON THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNCIATOR. - TRANSMITS A SUPERVISORY ALARM SIGNAL TO THE DESIGNATED THIRD PART LISTED Q CENTRAL MONITORING STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. 1 B.- SPRINKLER CONTROL VALVES ACTIVATION OF ANY CONTROL VALVE SUPERVISORY SIGNAL INITIATING DEVICE (TAMPER SWITCHES, P.I.V. AND BACK FLOW PREVENTOR) SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: - ACTIVATE THE SUPERVISORY LIGHT AND A DISTINCTIVE SOUND AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. - INDICATE THE LOCATION OF THE ACTIVATED DEVICE ON THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNCIATOR. - TRANSMITS A SUPERVISORY ALARM SIGNAL TO THE DESIGNATED THIRD PARTY LISTED Q CENTRAL MONITORING STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. 1 C.- ELEVATOR SHUNT TRIP POWER LOSS OF VOLTAGE TO THE CONTROL CIRCUIT FOR THE DISCONNECTING MEANS SHALL CAUSE A SUPERVISORY SIGNAL TO BE INDICATED AT THE F.A.C.P AND REMOTE ANNUNCIATOR. NOTE: NOTIFICATION APPLIANCES WILL NOT BE ACTIVATED. 3.- TROUBLE SIGNALS, THE OCCURRENCE OF ANY TROUBLE IN THE SYSTEM SHALL CAUSE THE FOLLOWING ACTION AND INDICATIONS: - ACTIVATE THE TROUBLE LIGHT AND A DISTINCTIVE TROUBLE SOUND AT THE FIRE ALARM CONTROL PANEL AND REMOTE ANNUNCIATOR. - DISPLAY A TROUBLE DESCRIPTION ON THE FACP ALPHANUMERIC DISPLAY AND REMOTE ANNUNCIATOR. - TRANSMITS A TROUBLE SIGNAL TO THE DESIGNATED THIRD PAR LISTED ENTRAL MONITORING STATION BY WAY OF DIGITAL ALARM COMMUNICATOR. i NOTE: TROUBLE SIGNALS AND THEIR RESTORATION TO NORMAL SHALL B I ATED WITHIN 200 SECONDS. 4. -FIRE SAFETY FUNCTIONS. A.- ELEVATOR RECALL (TYPICAL) ACTIVATION OF ANY AUTOMATIC DETECTOR IN ELEVATOR LOBBIES, ELEVATOR MACHINE ROOM AND ELEVATOR SHAFT SHALL AUTOMATICALLY INITIATE THE FOLLOWING FUNCTIONS: - INITIATE AN ALARM CONDITION IN THE BUILDING FOR EVACUATION PURPOSES. - INDICATE THE LOCATION OF THE AUTOMATIC DETECTOR BY DISPLAYING IN ENGLISH, THE ALARMED DEVICE ON THE FACP ALPHANUMERIC DISPLAY. - INITIATE THE AUTOMATIC RECALL OPERATION AS FOLLOWS: 1- PRIMARY ELEVATOR RECALL: ACTIVATION OF ANY ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON FLOORS 2, 3 & 4 AND /OR ANY SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM OR ELEVATOR SHAFT SHALL INITIATE PRIMARY RECALL WHICH WILL BRING THE ELEVATOR CAR TO THE 1ST FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. 2- SECONDARY ELEVATOR RECALL: ACTIVATION OF ANY ELEVATOR LOBBY SMOKE DETECTOR LOCATED ON THE 1ST FLOOR SHALL INITIATE RECALL WHICH WILL BRING THE ELEVATOR CAR TO THE 2ND FLOOR AND LOCK THE DOORS IN THE OPEN POSITION. 3- ELEVATOR WARNING LIGHTS: ACTIVATION OF ANY ELEVATOR MACHINE ROOM SMOKE DETECTOR OR ELEVATOR HOISTWAY DETECTOR SHALL ALSO INITIATE THE ELEVATOR WARNING LIGHTS TO ALERT THE FIGHTERS AND OTHER EMERGENCY PERSONNEL THAT THE ELEVATORS ARE NO LONGER SAFE TO USE. 4- ELEVATOR SHUNT TRIP: HEAT DETECTORS LOCATED IN THE ELEVATOR HOISTWAY AND ELEVATOR MACHINE ROOM SHALL BE ACTIVATE A CONTROL SHUNT TO DISCONNECT THE ELEVATOR POWER UPON ACTIVATION. THE SHUNT POWER SHALL BE MONITORED BY THE FIRE ALARM CONTROL PANEL. (SEE 2 -C. ABOVE) THE MAXIMUM TIME PERIOD FROM ACTUATION OF THE INITIATING DEVICE UNTIL INITIATION OF ALL RELATED FUNCTIONS AS LISTED ABOVE SHALL BE TEN SECONDS. THE REQUIREMENTS OF SECTION 11 -4.28 OF THE FLORIDA ACCESSIBILITY CODE ARE BEING SATISFIED BY UTILIZING THE STANDARDS OF SECTION 4 -4.4 OF NFPA 72 FOR THE PLACEMENT OF VISIBLE NOTIFICATION DEVICES. KEY PLAN (FIRST FLOOR) N.T.S FIRE ALARM NOTES 1 —FIRE ALARM SYSTEM SHALL BE U.L. LISTED AND NFPA 72 APPROVED AND COMPATIBLE. 2 —RISER INTERCONNECTIONS ARE DIAGRAMMATIC ONLY. 3 —TOTAL ACTIVE AREA: 4,651 SO. FT. 4 —FIRE ALARM SYSTEM TO BE "POWER LIMITED ". 5 —THE INSTALLATION SHALL COMPLY WITH NFPA 70 CHAPTER 760 6 —ALL WIRING AND CONDUIT SIZE SHALL BE IN ACCORDANCE WITH MANUFACTURER RECOMMENDATION, LOCAL CODES AND NFPA. 7 —ALL CONDUCTORS SHALL BE SOLID OR STRANDED COPPER. 8— MAXIMUM CONDUIT FILLS TO BE 40 %. MINIMUM RACEWAY SIZE ". 9— SYSTEM SHALL BE GROUNDED ACCORDING TO MANUFACTURER SPECIFICATION AND NEC ARTICLE 250. 10 —ALL FIRE WALL PENETRATION SHALL BE MADE WITH APPROVED (NEC) ELECTRICAL TUBING AND SEALED WITH A U.L. LISTED FIRE STOPPER. (SEE FIRE STOP DETAIL). 11 —THE 120V AC POWER FEED FOR THE FIRE PANEL MUST BE FROM A DEDICATED CIRCUIT AND THE BREAKER MUST BE IDENTIFIED FIRE ALARM CIRCUIT AND HAVE A LOCK ON IT. 12— VISUAL ALARM PER ANSI A117.1, 4.26, SFBC 513.3 AND ADA APPROVED. WALL MOUNTS 80" A.F.F. TO BOTTOM OF STROBE LENS. 13 —ALL NEW WIRING INSTALLED IN DUCTS, PLENUMS AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP, AS PER NEC (NATIONAL ELECTRIC CODE) ARTICLE 760 -61. 14 —ALL N.A.C. WIRING SHALL BE CLASS "B" (STYLE "Y "). SIGNALING LINE CIRCUIT WIRING SHALL BE CLASS "B" (STYLE "4 "). 15 —HORN /STROBES SHALL BE LOCATED AS PER NFPA 72, CHAPTER 7. 16— STROBE LIGHT CIRCUITS SHALL BE SYNCHRONIZED AT 1HZ PER ADA AND NFPA 72. 17— UNLESS OTHERWISE NOTED ALL CEILING HEIGHTS DO NOT EXCEED 10' -0" AND ALL CEILINGS ARE FLAT. 18— FURNITURE AND EQUIPMENT SHALL NOT EXCEED 72" IN HEIGHT WHERE PLACED ALONG THE PATH OF VISUAL SIGNALS. 19— SYSTEM IS CLASSIFIED AND CERTIFICATED FOR CENTRAL STATION SERVICE PER NFPA 72 8.2. 20 —THE SYSTEM SHALL HAVE BATTERY BACK UP FOR 24 HRS IN STANDBY MODE AND 5 MINUTES IN ALARM. THIS IS AN EXISTING 4 STORY FULLY — SPRINKLED BUILDING SCOPE OF WORK: 1. FURNISH AND INSTALL NEW DEVICES TO EXISTING SYSTEM AS FOLLOWS: 0 1 REMOTE POWER SUPPLY FIRE —LITE 15 STROBE LIGHT SYSTEM SENSOR ORN TRO EM SENSOR 4 ADDRESSABLE DUCT DETECTOR NOTIFIER 4 ADDRESSABLE RELAY NOTIFIER 2. RELOCATED EXISTING DEVICES TO EXISTING SYSTEM AS FOLLOWS: 3 STROBE LIGHT SYSTEM SENSOR 3 HORN /STROBE SYSTEM SENSOR FIRE ALARM PLAN SCALE: 1/8" = V -0" Dr.Barroso FIRE ALARM LEGEND SYMBOL DESCRIPTION MANUFACTURER MODEL FAC FIRE ALARM CONTROL PANEL NOTIFIER NFW -100 -2 ANN REMOTE ANNUNCIATOR NOTIFIER FDU -80 RPS REMOTE POWER SUPPLY FIRE -LITE FCPS -24S8 SD ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR NOTIFIER NP -100 HD ADDRESSABLE HEAT DETECTOR NOTIFIER NH -100 ADDRESSABLE DUCT DETECTOR NOTIFIER ND -100 19 MONITOR MODULE NOTIFIER NMM -100P © CONTROL MODULE NOTIFIER NC -100 ® ADDRESSABLE RELAY NOTIFIER NC -10OR © wp PULL STATION WEATHER PROOF NOTIFIER NBG -12LO © ADDRESSABLE PULL STATION NOTIFIER NBG -12LX I BWP HORN /STROBE WEATHER PROOF (75cd, 11 Ocd) SYSTEM SENSOR P1224MCK © gyp STROBE LIGHT WEATHER PROOF (75cd, 1 10cd) SYSTEM SENSOR S1224MCK 1B HORN /STROBE (75cd) SYSTEM SENSOR P2R © STROBE LIGHT (15/75cd, 75cd) SYSTEM SENSOR SR © STROBE LIGHT CEILING MOUNT (75cd) SYSTEM SENSOR SCR R gyp SPRINKLER BELL WEATHER PROOF AMSECO MBA -10 -24 ©S TAMPER SWITCH BY OTHERS FS WATER FLOW SWITCH BY OTHERS FIRE ALARM SYSTEM TO BE INSTALLED IN ACCORDANCE WITH NFPA 72; 70;101- N: DENOTES NEW DEVICE E: DENOTES EXISTING DEVICE ER: DENOTES EXISTING RELOCATED DEVICE NUAM -DARE COUNTY FIRE DEPARTMENT SLOG. PERMIT FIRE ALARM FIRE SUPPRESSION— WATER MAIN EXT.�� M ANiI -DARE CO. FIRE DEPARTMENT APPLICATION #-L 7 3 3 Z= FIRE ALARM SHALL BE A CENTRAL STATION SERVICE. A CERTIFICATE OR PLACARD SHALL BE POSTED AT FINAL INSPECTION, AS PER NFPA 72 TUPACK RHEA P.E. ELECTRICAL ENGINEER FLORIDA LIC #40217 9380 SUNSET DR #2484 MIAMI, FL 33173 PHONE: (305) 569 019.'1 {i 0 I ADVANCED DETECTION TECHNOLOGIES, INC. ► LICENSE NO.: EF0001218 UL 100045/337 1781 S.W. 3RD AVE A ��,� MIAMI, FLORIDA 33129 • • . , TEL. (305) 663 -0738 L ••. FAX: (305) 856 -4514 �� -�' �� •: � vo� �� � ,� 300 °� a QUALIFIER: E.E. FELIXTUGA REVISIONS AFIRE DEPARTMENT 05/06/07 A • �1 •• O O �%4 O c W E-4 C) ^ M � E-� O E-+ A � W PROJECT NO.: DRAWING NO.: SCALE: 1/8. = 1' -0' DATE: 03/20 /07 DRAWN BY: I.M. ISSUED: FOR PERMIT SHEET NO.: FA -01 01 OF 02