07-790R-013(A PARTIAL FLOOR FLAN - POWER
SCALE: 1/4" = V -011
i
I
PARKING
DRAWING LEGEND (POWER & SIGNAL)
SYMBOL
PE5CRIP'ION
U
DUPLEX GROUNDED RECEPTACLE RATED 20A, 125V, MOUNTED 16 INCHES AFF.
i
TYPICAL, AS DIRECTED BY ARCHITECT EXCEPT OTHERWISE INDICATED.
DUPLEX GROUNDED RECEPTACLE RATED 20A, 125V, CENTER PILL DENOTES
I
OUTLET MOUNTED 48 INCHES AFF. OR ABOVE COUNTER (COUNTER HEIGHT) AS
GFI
DIRECTED BY ARCHITECT EXCEPT OTHERWISE INDICATED. 'l DENOTES DUPLEX
RECEPTACLE WITH GROUND FAULT INTERRUPTER DEVICE TYPE.
(A PARTIAL FLOOR FLAN - POWER
SCALE: 1/4" = V -011
i
I
PARKING
DRAWING LEGEND (POWER & SIGNAL)
SYMBOL
PE5CRIP'ION
U
DUPLEX GROUNDED RECEPTACLE RATED 20A, 125V, MOUNTED 16 INCHES AFF.
TYPICAL, AS DIRECTED BY ARCHITECT EXCEPT OTHERWISE INDICATED.
DUPLEX GROUNDED RECEPTACLE RATED 20A, 125V, CENTER PILL DENOTES
E-�
OUTLET MOUNTED 48 INCHES AFF. OR ABOVE COUNTER (COUNTER HEIGHT) AS
GFI
DIRECTED BY ARCHITECT EXCEPT OTHERWISE INDICATED. 'l DENOTES DUPLEX
RECEPTACLE WITH GROUND FAULT INTERRUPTER DEVICE TYPE.
m
SINGLE GROUNDED RECEPTACLE: 125V., 20A, + 16 INCHES. NEMA 5 -20R,
EXCEPT OTHERWISE INDICATED.
COMBO TELEPHONE/DATA OUTLET MULTIPLE CONFIGURATION, FLUSH WALL
T
MOUNTED IN A 4" SQUARE BY 11/2" DEEP BOX WITH PLASTER RING. UP IS" AFF.,
d
OR COUNTER HEIGHT, EXCEPT OTHERWISE INDICATED.
DUPLEX TELEPHONE OUTLET, FLUSH WALL MOUNTED IN A 4" SQUARE
T
BY 11/2" DEEP BOX WITH PLASTER RING. UP 18" AFF., EXCEPT
w
OTHERWISE INDICATED.
T
SINGLE TELEPHONE OUTLET - FLUSH WALL MOUNTED IN A 4" SQUARE BY 1.1/2"
"W"
P W
DEEP BOX WITH PLASTER RING UP, DENOTES WALL MOUNTED 52" AP:,
w c 0
"P11 DENOTES FOR PUBLIC USE EXCEPT OTHERWISE INDICATED.
�j
"TV" (AUDIO/VISUAL) OUTLET, FLUSH WALL MOUNTED IN A 4" SQUARE BY 2 3/4"
ry
DEEP BOX WITH PLASTER RING. PLATE AND JACK BY "TV" (AUDIOMSUAL)
o
CONTRACTOR SYSTEM CABLE IN I" CONDUIT, RUNNING IN CEILING SPACE
FIRE ALARM HORN/STROBE LIGHT. PROVIDE A 4" $MARE BY 2 1 /8" DEEP WITH PLASTER RING WITH
�5C0
CANDELA (15CD) AS $HM ON PLAN. MOUNT 60" APA TO BOTTOM. MANUFACTURER TO MATCH EXISTING.
F[]Q
REFER TO BASE BUILDING UNIT MANUFACTURER SHOP DRAWINGS
$PEA .ER/STROBE - SYNCHRONIC. 15CO DENOTE$ UNIT CANDELA LIGHT LEVEL
FIRE ALARM PULL STATION. PROVIDE A 4" $QUARE BY 2 1 /$" DEEP WITH PLASTER RING
C]
MOUNT 42 AF):. TO BOTTOM. MANUFACTURER TO MATCH EXISTING.
REFER TO BASE BUILDING UNIT MANUFACTURER $HOP DRAWINGS
,HD
DENOTES AREA FURNISHED WITH OUTLET($) (DEVICE AND COVER PLATE)
HOSPITAL GRADE TYPE AS SHOWN
•D
DENOTES DEDICATED EQUIPMENT OUTLET
OF
DENOTES DRINKING FOUNTAIN
0
PROXIMITY /SECURITY BADGE. 2
al-I
DENOTES DRINKING FOUNTAIN 2
POWER &SIGNAL NOTES "B"
I. FOR R165R DIAGRAM AND GENERAL NOTES REFER TO SHEET E -5
2. FOR WIRING SIZES SEE PANEL SCHEDULE SHEET E -5 �I
3. FOR ELECTRICAL ENLARGED ROOM LAYOUT SEE SHEET E -4--'
4. NO RECEPTACLES SHALL BE LOCATED ABOVE SINK. RECEPTACLES SHALL BE LOCATED
6 INCHES MINIMUM FROM SINK EDGE WHEN APPLICABLE AND SHALL BE G.F.I. TYPE.
5. FOR DATA/TELEPHONE, WIRED WITH APPROVED CAT6 CLASS E PLENUM RATED CABLE, PROVIDE A
MULTIPLE CONFIGURATION COMBO DATA/VOICE- TELEPHONE OUTLET (TYPICAL). EXTEND WITH A 2
3 /4 "EC TO CEILING SPACE (NETWORK, DIGITAL DATA AND TELEPHONE SIGNAL) DATA /TELEPHONE
CABLE AND OUTLETS SHALL BE INSTALLED TO COMPLY WITH EIA/TIA WIRING METHODS AND
STANDARDS AND STRICTLY.COORDINATED WITH VOICE -DATA CONTRACTOR AND MEDICAL
EQUIPMENT MANUFACTURER REPRESENTATIVE.
6. PROVIDE A DEDICATED GROUNDED RECEPTACLE AND PHONE LINE FOR SECURITY ALARM EQUIP.
1. tHERMOSTAT WIRING $HALL BE DONE BY ELECTRICAL CONTRACTOR, AS PER UNIT MANUP. CONTROL DI .
6. PROVIDE AIR HANDLER UNIT DISCONNECT SWITCH TO COMPLY WITH N.E.C. 440 VERIFY EXACT WIRING
REQUIREMENTS AND PROTECTION SIZE WITH UNIT MANUFACTURER NAMEPLATE RECOMMENDATIONS,
9. EXISTING TELEPHONE SERVICE PROVISIONS I "C FROM BUILDING MAIN TELEPHONE BOARD LOCATED
AT EXISTING BUILDING METER ROOM. EXTEND EXISTING CONDUIT (TO MATCH EXISTING) TO TENANT
TELEPHONE BOARD/TELEPHONE SYSTEM, TERMINATE AS REQUIRED BY EQUIPMENT FURNISHED.
VERIFY EXACT LOC AND MTG HEIGHTS AT FIELD WITH OWNER REP AND IT CONSULTANT BEFORE
ROUGHING -IN. SEE PARTIAL SITE PLAN DWG E -4.
10 ALL FIRE ALARM DEVICES $WOLIN FOR REFERENCE ONLY. EXISTING FACILITY FIRE ALARM UNIT
MANUFACTURER IN$TALLER/CONTRACTOR $HALL PROVIDE SHOP DRAWINGS FOR THE TENANT
ADDITIONAL AND RELOCATED DEVICES,
II, ALL FIRE ALARM DEVICES INSTALLED, SHALL BE UL LISTED, UL, AND SAME MANUFACTURER
COMPATIBLE WITH EXISTING SYSTEM AND APPROVED FOR THE PURPOSE WHICH THEY
ARE INTENDED. FINAL CONNECTION BETWEEN NEW COMPONENTS AND EXISTING
EQUIPMENT $HALL BE MADE UNDER DIRECT SUPERVISION OF A QUALIFIED TECHNICAL
REPRESENTATIVE OF THE EQUIPMENT MANUFACTURER, WHO $HALL TEST THE SYSTEM
COMPLETELY, COORDINATE AT FIELD ALL REQUIRED INSPECTION$ AND PROVIDE AN
"AS BUILT" SHOP DRAWING AND CERTIFICATE IN WRITHING AS TO PROPER INSTALLATION
AND OPERATION OF THE FIRE ALARM PRIOR TO THE FINAL ACCEPTANCE OF THE
SYSTEM BY THE OWNER
12. PROVIDE AIR HANDLER UNIT DISCONNECT SWITCH TO COMPLY WITH N.E.C. 440 VERIFY EXACT WIRING
REQUIREMENTS AND PROTECTION SIZE WITH UNIT MANUFACTURER NAMEPLATE RECOMMENDATIONS.
INDOOR BLOWER UNIT WIRED FROM OUTDOOR CONDENSER UNIT TERMINAL BLOCK, CKT PROT, FROM
OUTDOOR UNIT, REFER TO UNIT MANUFACTURER INSTALLATION REQUIREMENTS,
13. AC -3 VENTILATION SYSTEM ON -OFF SWITCH, SHALL BE WIRED THROUGH THE
VARIAN VAULT DOOR OPERATOR REFER TO UNIT MANUFACTURER WIRING
REQUIREMENTS. EF -5 $HALL BE INTERLOCK WITH AC -3 PER MECHANICAL a
SEQUENCE OF OPERATION, REFER TO MECHANICAL DRAWINGS.
0CEP, .
Am
0
p � Xrn
C o °
v = Ip w ^
u O t2
o E lu 3
V) W rn N �3
t5 5
� a
E-+
U
0
E-�
s
uV
Z
W
2
N
o
W
d
1
.r
Q_
w
U
O N N
u
w c 0
�j
° ��
a
o
Q
0
W
O
jig
j1plax.-wil
6 j fiN IS2
51 533WR89"
DATES 03114107
PROJ No$ -
0114 BYE JEB
REv, -
04/08/07
11/18/2007
FIELD -CHG.
A 212/10/2007
IT- REVISION
02/04/2008
3 CT -CHG.
E -2
0 F
0
(n
Z
W
2
N
o
W
w
0
5
Q_
w
U
W °�
�j
� =M
zUaQ
Q
04�
Z
00
0
CL
jig
j1plax.-wil
6 j fiN IS2
51 533WR89"
DATES 03114107
PROJ No$ -
0114 BYE JEB
REv, -
04/08/07
11/18/2007
FIELD -CHG.
A 212/10/2007
IT- REVISION
02/04/2008
3 CT -CHG.
E -2
0 F