07-790-025SPLIT SYSTEM A/C UNIT SCHEDULE
TWO -SPEED
UNIT DESIGNATION
AC -1
AC -2
AC -3
AREA SERVED
MEDICAL OFFICE
MEDICAL OFFICE
VARIAN
VAULT MRI
REFRIGERANT TYPE
R -22
R -22
R -22
EXHAUST
LOCATION
ABOVE CLG
ABOVE CLG
ABOVE CLG
FIRE STOPPING
OPERATING WEIGHT, POUNDS
193
193
200
CABINET
DESIGN MANUFACTURER MODEL NO.
4TEC3F60A1
4TEC3F60A1
TWE049E13
z
TOTAL AIR, CFM, HIGH LOW SPEED
1800
1720
2000710-00
DIRECT
OUTSIDE AIR, CFM
400
425
150
o
EXTERNAL STATIC PRESSURE IN W.G.
0.5
0.5
0.75
0.25
FAN MOTOR HP NON - OVERLOAD
3/4
3/4
3/4
3
ELECTRICAL SERVICE -VOLTS PH HZ
208-230/l/60
208-230/1/60
208-230/l/60
o
GRAND TOTAL CAPACITY, MBH
56.5
54.8
54.7
40 WATTS
TOTAL SENSIBLE CAPACITY, MBH
42.3
39.3
48.6
120/11/60
ENTERING AIR TEMPERATURE, 'F DB WB
80/67
80/67
76/61-
--
LEAVING AIR TEMPERATURE, -F OB WB
-
-
-
--
TYPE
T A.
T.A.
T A.
J
THICKNESS
1
I*
1
'i
QUANTITY AND SIZE
1 -19x19
1 -19x19
1 -19x19
GREENHECK
SP -6 -QD
ELECTRICAL SERVICE REQUIRED
208 - 230/1/60
208 - 230/1/60
208 - 230/1/60
TOTAL HEATING CAPACITY, KW
7.5
7.5
5
=
NUMBER OF STEPS
1
1
1
UNIT DESIGNATION
CU -1
CU -2
CU -3
LOCATION
GARAGE
GARAGE
GARAGE
NUMBER OF COMPRESSORS
1
1
1
CAPACITY REDUCTION
100 -0
100 -0
100 -0
CONDENSER FAN -TYPE
PROPELLER
PROPELLER
PROPELLER
N
TOTAL FULL LOAD AMPS (FLA)
21.2
21.2
25.8
w
AMBIENT AIR TEMPERATURE 'F DB
95
95
95
°z
OPERATING WEIGHT, POUND
335
335
300
°
ELECTRICAL SERVICE REQUIRED
208-230/1/60
208-230/1/60
208-230/1/60
DESIGN MANUFACTURER MODEL NO.
4TTR406081
4TTR406081
2TTZ906061
SEER RATING, MINIMUM
13.5
13.5
16.5
DESIGN MANUFACTURER
TRANE
TRANE
TRANE
NOTES & ACCESSORIES:
Q1 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS.
02 PROVIDE FACTORY FURNISHED HEAT /COOL PROGRAMMABLE THERMOSTAT. SEE WORK NOTES ON M -3.
HVAC SYSTEM
REQUIREMENTS
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
v
AREA SERVED
FIRE DAMPER (S)
TOILET
v
SMOKE DAMPER (S)
SERVICE
v
FIRE RATED ENCLOSURE
EXHAUST
v
FIRE RATED ROOF /FLOOR
CEILING ASSEMBLY
ABOVE CLG
v
FIRE STOPPING
ABOVE CLG
v
SMOKE CONTROL
CABINET
CABINET
FAN SCHEDULE
UNIT DESIGNATION
EF -1
EF -2
EF -3
EF -4
AREA SERVED
TOILET
TOILET
TOILET
TOILET
SERVICE
EXHAUST
EXHAUST
EXHAUST
EXHAUST
LOCATION
ABOVE CLG
ABOVE CLG
ABOVE CLG
ABOVE CLG
FAN TYPE
CABINET
CABINET
CABINET
CABINET
FAN WHEEL TYPE
BI CENTRIF
BI CENTRIF
BI CENTRIF
BI CENTRIF
DRIVE TYPE
DIRECT
DIRECT
DIRECT
DIRECT
TOTAL AIR, CFM
74
74
74
74
TOTAL STATIC PRESS., IN. W.G.
0.25
0.25
0.25
0.25
FAN SPEED, RPM MAX
1500
1500
1500
1500
FAN BRAKE HORSEPOWER MAX.
--
--
--
--
FAN MOTOR HP NON - OVERLOAD
40 WATTS
40 WATTS
40 WATTS
40 WATTS
ELECTRICAL SERVICE AVAILABLE
120/l/60
120/l/60
120/11/60
120/l/60
MOTOR STARTER TYPE
--
--
--
--
MOTOR STARTER ENCLOSURE
--
--
--
--
OPERATING WEIGHT, LBS.
20
20
20
20
ACCESSORIES
RUBBER
ISOLATORS
RUBBER
ISOLATORS
RUBBER
ISOLATORS
RUBBER
ISOLATORS
MFGR./MODEL NO.
GREENHECK
SP -6 -QD
GREENHECK
SP -6 -QD
GREENHECK
SP -6 -QD
GREENHECK
SP -6 -QD
J
OUTSIDE AIR SCHEDULE AC -3
ASHRAE 62 -2001
AC No.
AREAS
No. OF
CFM PER PERSON
CALCULATED 0/A
DESIGN OVA
AC No.
SERVED
PEOPLE
REQUIRED
TOTAL CFM
TOTAL C M
AC -3
ICAQ EXAM
20/1000 sq.ft.
15(0.5)*
143
150
954
20 /1000 sq.ft.
15(0.5)*
494
1645 SQ.FT.
*INTERMITTENT OCCUPANCY PER ASHRAE 62 SECTION 6.1.3.4
OUTSIDE AIR SCHEDULE AC -1 & AC -2
ASHRAE 62 -2001
AC No.
AREAS
No. OF
CFM PER PERSON
CALCULATED 0/A
DESIGN 0/A
SERVED
PEOPLE
REQUIRED
TOTAL CFM
TOTAL CFM
C- I &AC-2
WAITING
350 SQ.FT.
60/1000 sq.ft.
15(0.5)*
158
MEDICAL EXAM
20 /1000 sq.ft.
15(0.5)*
494
1645 SQ.FT.
CORRIDOR
419 SQ.FT.
0.1 CFM / sq.ft.
--
42
�
OFFICE
870 SQ.FT.
7/1000 sq.ft.
20
122
816
825
AC -1
ti
400
AC -2
425
*INTERMITTENT OCCUPANCY PER ASHRAE 62 SECTION 6.1.3.4