Loading...
07-790-025SPLIT SYSTEM A/C UNIT SCHEDULE TWO -SPEED UNIT DESIGNATION AC -1 AC -2 AC -3 AREA SERVED MEDICAL OFFICE MEDICAL OFFICE VARIAN VAULT MRI REFRIGERANT TYPE R -22 R -22 R -22 EXHAUST LOCATION ABOVE CLG ABOVE CLG ABOVE CLG FIRE STOPPING OPERATING WEIGHT, POUNDS 193 193 200 CABINET DESIGN MANUFACTURER MODEL NO. 4TEC3F60A1 4TEC3F60A1 TWE049E13 z TOTAL AIR, CFM, HIGH LOW SPEED 1800 1720 2000710-00 DIRECT OUTSIDE AIR, CFM 400 425 150 o EXTERNAL STATIC PRESSURE IN W.G. 0.5 0.5 0.75 0.25 FAN MOTOR HP NON - OVERLOAD 3/4 3/4 3/4 3 ELECTRICAL SERVICE -VOLTS PH HZ 208-230/l/60 208-230/1/60 208-230/l/60 o GRAND TOTAL CAPACITY, MBH 56.5 54.8 54.7 40 WATTS TOTAL SENSIBLE CAPACITY, MBH 42.3 39.3 48.6 120/11/60 ENTERING AIR TEMPERATURE, 'F DB WB 80/67 80/67 76/61- -- LEAVING AIR TEMPERATURE, -F OB WB - - - -- TYPE T A. T.A. T A. J THICKNESS 1 I* 1 'i QUANTITY AND SIZE 1 -19x19 1 -19x19 1 -19x19 GREENHECK SP -6 -QD ELECTRICAL SERVICE REQUIRED 208 - 230/1/60 208 - 230/1/60 208 - 230/1/60 TOTAL HEATING CAPACITY, KW 7.5 7.5 5 = NUMBER OF STEPS 1 1 1 UNIT DESIGNATION CU -1 CU -2 CU -3 LOCATION GARAGE GARAGE GARAGE NUMBER OF COMPRESSORS 1 1 1 CAPACITY REDUCTION 100 -0 100 -0 100 -0 CONDENSER FAN -TYPE PROPELLER PROPELLER PROPELLER N TOTAL FULL LOAD AMPS (FLA) 21.2 21.2 25.8 w AMBIENT AIR TEMPERATURE 'F DB 95 95 95 °z OPERATING WEIGHT, POUND 335 335 300 ° ELECTRICAL SERVICE REQUIRED 208-230/1/60 208-230/1/60 208-230/1/60 DESIGN MANUFACTURER MODEL NO. 4TTR406081 4TTR406081 2TTZ906061 SEER RATING, MINIMUM 13.5 13.5 16.5 DESIGN MANUFACTURER TRANE TRANE TRANE NOTES & ACCESSORIES: Q1 SIZE AND INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS. 02 PROVIDE FACTORY FURNISHED HEAT /COOL PROGRAMMABLE THERMOSTAT. SEE WORK NOTES ON M -3. HVAC SYSTEM REQUIREMENTS HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR v AREA SERVED FIRE DAMPER (S) TOILET v SMOKE DAMPER (S) SERVICE v FIRE RATED ENCLOSURE EXHAUST v FIRE RATED ROOF /FLOOR CEILING ASSEMBLY ABOVE CLG v FIRE STOPPING ABOVE CLG v SMOKE CONTROL CABINET CABINET FAN SCHEDULE UNIT DESIGNATION EF -1 EF -2 EF -3 EF -4 AREA SERVED TOILET TOILET TOILET TOILET SERVICE EXHAUST EXHAUST EXHAUST EXHAUST LOCATION ABOVE CLG ABOVE CLG ABOVE CLG ABOVE CLG FAN TYPE CABINET CABINET CABINET CABINET FAN WHEEL TYPE BI CENTRIF BI CENTRIF BI CENTRIF BI CENTRIF DRIVE TYPE DIRECT DIRECT DIRECT DIRECT TOTAL AIR, CFM 74 74 74 74 TOTAL STATIC PRESS., IN. W.G. 0.25 0.25 0.25 0.25 FAN SPEED, RPM MAX 1500 1500 1500 1500 FAN BRAKE HORSEPOWER MAX. -- -- -- -- FAN MOTOR HP NON - OVERLOAD 40 WATTS 40 WATTS 40 WATTS 40 WATTS ELECTRICAL SERVICE AVAILABLE 120/l/60 120/l/60 120/11/60 120/l/60 MOTOR STARTER TYPE -- -- -- -- MOTOR STARTER ENCLOSURE -- -- -- -- OPERATING WEIGHT, LBS. 20 20 20 20 ACCESSORIES RUBBER ISOLATORS RUBBER ISOLATORS RUBBER ISOLATORS RUBBER ISOLATORS MFGR./MODEL NO. GREENHECK SP -6 -QD GREENHECK SP -6 -QD GREENHECK SP -6 -QD GREENHECK SP -6 -QD J OUTSIDE AIR SCHEDULE AC -3 ASHRAE 62 -2001 AC No. AREAS No. OF CFM PER PERSON CALCULATED 0/A DESIGN OVA AC No. SERVED PEOPLE REQUIRED TOTAL CFM TOTAL C M AC -3 ICAQ EXAM 20/1000 sq.ft. 15(0.5)* 143 150 954 20 /1000 sq.ft. 15(0.5)* 494 1645 SQ.FT. *INTERMITTENT OCCUPANCY PER ASHRAE 62 SECTION 6.1.3.4 OUTSIDE AIR SCHEDULE AC -1 & AC -2 ASHRAE 62 -2001 AC No. AREAS No. OF CFM PER PERSON CALCULATED 0/A DESIGN 0/A SERVED PEOPLE REQUIRED TOTAL CFM TOTAL CFM C- I &AC-2 WAITING 350 SQ.FT. 60/1000 sq.ft. 15(0.5)* 158 MEDICAL EXAM 20 /1000 sq.ft. 15(0.5)* 494 1645 SQ.FT. CORRIDOR 419 SQ.FT. 0.1 CFM / sq.ft. -- 42 � OFFICE 870 SQ.FT. 7/1000 sq.ft. 20 122 816 825 AC -1 ti 400 AC -2 425 *INTERMITTENT OCCUPANCY PER ASHRAE 62 SECTION 6.1.3.4 '�1 •��Ltk i. Y H ■ r H U H M r1a � W U 0 ti W u) Z W (V O w � > W F_- 0 04 (� Q W ❑ U w o z Q Z w 4 (vo- U 00 a. 0 �902� W