07-780R-0291P��C�I►iI���f>C;TCa31 SECTION 16010 - GENERAL ELECTRICAL PROVISIONS A. GENERAL 1. TRANSPORTATION, INSURANCE, TEMPORARY PROTECTION, SUPERVISION AND INCIDENTAL ITEMS ESSENTIAL FOR PROPER INSTALLATION AND OPERATION, THOUGH NOT SPECIFICALLY MENTIONED OR INDICATED BUT WHICH ARE USUALLY PROVIDED OR ARE ESSENTIAL FOR PROPER INSTMIA11ON AND OPERATION OF ALL SYSTEMS RELATED TO THIS SECTION, AS SPECIFIED HEREIN. 2. ALL MATERIALS SHALL BE NEW AND BARE A UL LABEL 3. ALL CONDUITS, WIREWAYS OR IOTHER ELECTRICAL RACEWAYS PASSING THROUGH FIRE PARTITIONS, FIRE WALLS OR FLOORS SHALL HAVE A FIRE STOP INSTALLED PROVIDING AN EFFECTIVE BARRIER AGAINST THE SPREAD OF FlRE, SMOKE AND GASES, MAINTAINING THE REQUIRED FIRE RATING. B. CODES AND REGULATIONS I. INSTALLATION SHALL CONFORM TO THE FOLLOWING CODES AND REGULATIONS. FLORIDA BUILDING CODE - 2004 WITH 2005 AND 2006 REVISIONS NFPA -70: NATIONAL ELECTRIC CODE - 2005 EDITION NFPA -72: NATIONAL FIRE ALARM CODE - 2002 EDITION NFPA 101: LIFE SAFETY CODE - 2003 EDITION APPLICABLE LOCAL CODES 2. IN THESE SPECIFICATIONS, REFERENCES MADE TO THE FOLLOWING INDUSTRY STANDARDS AND CODE BODIES ARE INTENDED TO INDICATE THE LATEST VOLUME OR PUBLICATION OF THE STANDARD. ALL EQUIPMENT, MATERIALS AND DETAILS OF INSTALLATION SHALL COMPLY WITH THE REQUIREMEN ANSI- AMERICAN NATIONAL STANDARDS INSTITUTE. ASTM- AMERICAN SOCIETY OF TESTING MATERIALS AWG- AMERICAN WIRE GAUGE FM- FACTORY MUTUAL NEMA- NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION UL- UNDERWRITER'S LABORATORIES NETA- NATIONAL ELECTRICAL TESTING ASSOCIATION IEEE- INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS 3. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE CODES, STANDARDS, LOCAL AND STATE ORDINANCES, INDUSTRY STANDARDS AND UTILITY COMPANY REGULATIONS, LATEST EDITIONS. C. SCOPE OF WORK 1. COOPERATE WITH ALL TRADES TO ASSURE THE STEADY PROGRESS OF ALL WORK UNDER THE CONTRACT, AS WELL AS PROVIDING TEMPORARY POWER AT PROJECT SITE FOR ALL OTHERS. 2• IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO STUDY ALL DRAWINGS AND DETAILS SO THAT THE INSTALLATION OF ALL NEW WORK CAN BE FULLY COORDINATED. THE CONTRACTOR SHALL VISIT THE SITE TO SATISFY HIMSELF THAT ALL PROVISIONS HAVE BEEN MADE FOR ALL ASPECTS OF THIS PROJECT. IF DISCREPANCIES EXIST BETWEEN DRAWINGS AND /OR SITE CONDITIONS, THE CONTRACTOR SHALL NOTIFY THE GENERAL CONTRACTOR IN WRITING PRIOR TO SIGNING OF THE CONTRACT FOR CONSIDERATION AND DECISIONS BEFORE PROCEEDING. FAILURE TO DO SO WILL NOT BE ALLOWED AS A BASIS FOR ADDITIONAL COMPENSATION TO CORRECT A DIFFICULTY OF DIFFERENCE FROM CONDITIONS INFERRED OR INDICATED ON THE DRAWINGS. 3. PREPARE AND SUBMIT SHOP DRAWINGS OF PERTINENT ELECTRICAL EQUIPMENT, DEVICES ETC., AS ARE INDICATED IN THE SCOPE OF WORK, AND RECORD FOR ALL WORK PROVIDED UNDER THIS CONTRACT TO THE ARCHITECT /ENGINEER'S REVIEW. PROVIDE SEVEN (7) COPIES OF ALL SUBMITTALS AS NOTED HEREINAFTER. 4. THE CONTRACTOR, FOR THE WORK IN HIS SCOPE OF WORK, SHALL GIVE ALL NECESSARY NOTICES, OBTAIN ALL PERMITS, PAY ALL GOVERNMENTAL TAXES, FEES, INSPECTIONS, AND OTHER COSTS IN CONNECTION WITH HIS WORK; FILE FOR NECESSARY APPROVALS WITH THE JURISDICTION UNDER WHICH THE WORK IS TO BE PERFORMED. ELECTRICAL CONTRACTOR SHALL OBTAIN ALL REQUIRED CERTIFICATES OF INSPEC11ON FOR RESPECTIVE WORK AND DELIVER SAME TO THE GENERAL CONTRACTOR BEFORE REQUEST FOR ACCEPTANCE OF HIS PORTION OF WORK IS MADE AND BEFORE FINAL PAYMENT. 5. CUT ALL OPENINGS, CHASES AND PATCHING REQUIRED TO ACCOMMODATE THE WORK UNDER THIS DIVISION, SEAL WITH ACOUSTICAL CAULK AND /OR BLOWOUT PATCH AND REPAIR ALL FLOORS, WALLS, ETC., DAMAGED BY SUCH CUTTINGS. ALL WORK DONE UNDER THIS HEADING MUST CONFORM IN EVERY RESPECT TO FINISH AND QUALITY OF MATERIALS AND WORKMANSHIP SPECIFIED UNDER APPROPRIATE SECTIONS FOR THE BUILDING. ALL CUTTING, CORE DRILLING, ETC. REQUIRED FOR THE INSTALLATION OF THE ELECTRICAL EQUIPMENT SHALL BE BY THE CONTRACTOR. APPROVED BY THE OWNER. 6. VERIFY EQUIPMENT SIZES, VOLTAGE AND CURRENT CHARACTERISTICS, ETC. BEFORE THE ORDERING OF ANY EQUIPMENT AND BEFORE ROUGHING -IN FOR EQUIPMENT TO BE SUPPLIED BY OTHERS, AND PROVIDE READY ACCESSIBILITY OF SYSTEM REQUIRED TO BE REACHED FOR MAINTENANCE AND OPERATIONS. 7. CHECK OTHER SECTIONS OF THE SPECIFICA11ONS FOR EQUIPMENT TO BE CONNECTED UNDER THIS CONTRACT. 8. THE ELECTRICAL CONTRACTOR SHALL MAKE ALL REQUESTS FOR SYSTEMS SHUT DOWNS TO THE OWNER 72 HOURS IN ADVANCE AND SHALL RESTORE ALL SYSTEMS TO NORMAL OPERATIONS BY 3:30PM EVERY WORK DAY. 9. THE ENTIRE AREA SHALL BE BROUGHT UP TO MEET CODE REQUIREMENTS INCLUDING EXISTING CONDITIONS. 10. ALL ABANDONED UTILITIES SHALL BE REMOVED. D. THE FOLLOWING GENERAL SYSTEMS AND EQUIPMENT SHALL BE PROVIDED AS A MINIMUM, BUT NOT BE LIMITED TO THE FOLLOWING: NORMAL DISTRIBUTION SYSTEM. EMERGENCY DISTRIBUTION SYSTEM. GROUNDING. LIGHTING FIXTURES INCLUDING LAMPS. CONNECTIONS TO WAC, PLUMBING, ELEVATORS. EMPTY CONDUIT SYSTEM FOR TELEPHONE /COMMUNICATIONS SYSTEMS. HOISTING, RIGGING, SETTING OF ALL CONDUIT, CABLE AND EQUIPMENT. TESTING, CLEANING AND ADJUSTING. FEES, PERMITS, ROYALTIES, GUARANTEES. FIRESTOPPING, SMOKEPROOFING, WATERPROOFING SHOP DRAWINGS, RECORD DRAWINGS, COORDINATION DRAWINGS. FIRE ALARM SYSTEM. CONNECTIONS TO OWNER- FURNISHED EQUIPMENT. ACCESS DOORS. BOXES - JUNCTION. \jobs \Mar r 5c Wa - u K bo 5 T. BOXES - OUTLET. BOXES - PULL CONDUCTORS - 60OV. CONDUIT - METALLIC. DISCONNECT SWITCHES. HANGERS AND SUPPORTS. EMPTY CONDUITS FOR TELEVISION SYSTEM. MECHANICAL SUSPENSION CHANNEL MOTOR DISCONNECT DEVICES. PANELBOARDS - LIGHTING AND DISTRIBUTION. WIRING DEVICES AND DEVICE PLATES. SUBMITTALS AND APPROVALS OF ALL STATE AND LOCAL AUTHORITIES. DIMMERS. LIGHTING CONTROL SYSTEMS. SECTION 16110 - RACEWAYS A. RACEWAYS SHALL BE AS FOLLOWS: 1. RACEWAYS FOR FEEDERS AND BRANCH CIRCUITS SHALL BE METALLIC, RIGID METAL CONDUIT, INTERMEDIATE METAL CONDUIT (IMC) OR ELECTRICAL METALLIC TUBING SIIZE 3/4 '. EMT SHALL NOT I BEO USED FI IN CONS UC ON ORE� WHERE UM SUBJECTED TO MECHANICAL DAMAGE. 2. FLEXIBLE METAL CONDUIT SHALL BE USED ONLY FOR CONNECTION TO MOTORS, PUMPS, AIR HANDLING UNITS AND TRANSFORMERS, AND SHALL BE WATERPROOF TYPE, WITH AN INTERWOVEN GROUND CONDUCTOR. SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN ALL FLEXIBLE CONDUIT SIZES. FLEXIBLE CONDUIT NON - WATERPROOF TYPE CAN BE USED FOR CONNECTING TO LIGHTING FIXTURES ONLY. MAXIMUM LENGTH OF ALL FLEXIBLE CONDUIT ALLOWED SHALL BE 5' -0 3. EXPANSION FITTINGS SHALL BE USED WHERE CONDUIT PASSES THROUGH BUILDING EXPANSION JOINTS, WEATHERPROOF TELESCOPIC TYPE. THE EXPANSION FITTING SHALL PERMIT A MINIMUM MOVEMENT OF 4 ". 4. SET SCREW TYPE CONNECTORS AND COUPLINGS WILL NOT BE ALLOWED, EXCEPT FOR EMT TYPE CONDUIT. EMT FITTINGS SHALL BE ANSI C80.4 STEEL TYPE, INSULATED THROAT, GLAND COMPRESSION TYPE OR SET SCREW TYPE. DIECAST FITTINGS ARE NOT ACCEPTABLE. 5. RACEWAYS SHALL NOT BE ALLOWED IN ANY CONCRETE FLOOR SLABS. 6. ALL EMERGENCY SYSTEM WIRING SHALL BE INSTALLED IN CONDUIT. 7. PROVIDE ALL MATERIALS, DEVICES, HANGERS, CLAMPS, ETC. AND LABOR REQUIRED TO PROPERLY SUPPORT ALL CONDUITS /BOXES INSTALLED UNDER THIS CONTRACT IN ACCORD WITH NEC. PROVIDE MINIMUM OF 1" SEPARATION BETWEEN ALL CONDUITS RACKED TOGETHER. 8. CONDUIT AND BOXES IN CEILING SPACES SHALL BE SUPPORTED FROM STRUCTURE. 9. PROVIDE NYLON PULL STRINGS IN ALL EMPTY CONDUITS. 10. CONDUIT AND TUBING SHALL BE MANUFACTURED BY ONE OF THE FOLLOWING: ANACONDA METALHOSE, RUSSELL & STOLL, OR ALLIED TUBE & CONDUIT. 11. FLEXIBLE CONDUIT SHALL BE MANUFACTURED BY ONE OF THE FOLLOWING: ANACONDA METALIiOSE, RUSSELL & STOLL, OR AWED TUBE & CONDUIT. SECTION 16120 - CONDUCTORS A. FEEDERS I. 600V FEEDERS SHALL BE SINGLE - CONDUCTOR, 600V RATED WITH XHHW OR XHHW -2 INSULATION, FEEDERS SHALL BE COLOR -COOED USING COLOR TAPE AT ALL CONNECTIONS AND IN ALL PULL AND JUNCTION BOXES. ALL FEEDERS SHALL BE INSTALLED IN CONDUIT. ALL WIRING *B AWG AND LARGER SHALL BE STRANDED. 2. PROVIDE COLOR -CODED CABLE SYSTEM APPROVED BY OWNER. IF NONE IS REQUIRED BY OWNER, PROVIDE THE FOLLOWING COLOR - CODING: a. 208/120V 1) A PHASE: BLACK 2 B PHASE: RED 3 C PHASE: BLUE 4 NEUTRAL WHITE 5 GROUND: GREEN NOTE: COLOR - CODING SHALL BE CONTINUOUS ON INSULATION FOR J6 AWG OR SMALLER AND CONTINUOUS OR MARKED WITH COLOR TAPE AT ALL CONNECTIONS FOR CONDUCTORS LARGER THAN J6 AWG. B. BRANCH CIRCUITS 1. BRANCH CIRCUIT CONDUCTORS SHALL BE SINGLE - CONDUCTORS 600V RATED WITH THWN OR THHN INSULATION WITH CONTINUOUS COLOR- CODING. 2. BRANCH CIRCUIT CONDUCTOR SHALL BE DESIGNEDD TO UTILIZE THE ADVANTAGE OF MULTI -WIRE DISTRIBUTION, HOWEVER, NO MORE THAN (5) CONDUCTORS (3- PHASE, 1 NEUTRAL AND 1 GROUND) SHALL BE INSTALLED IN A COMMON CONDUIT. 3. MINIMUM SIZE WIRE FOR BRANCH CIRCUIT AND POWER WIRING SHALL BE #12 AWG, FOR REMOTE CONTROL SIGNAL CIRCUIT AND INTERLOCK WIRING CAN BE 114 AWG. FOR 20A BRANCH CIRCUIT RUNS EXCEEDING 100' -0" IN LENGTH FROM PANELBOARD TO THE FIRST OUTLET, THE ENTIRE BRANCH CIRCUIT RUN SHALL BE J10 AWG OR LARGER. FOR RUNS OVER 175' -0" TO THE FIRST OUTLET, USE J8 AWG OR LARGER FOR THE ENTIRE BRANCH CIRCUIT RUN. 4. MULTICONDUCTOR ARMORED CABLE MAY BE USED FOR NORMAL POWER, GENERAL PURPOSE 20A BRANCH CIRCUIT WIRING FOR RECEPTACLES AND LIGHTING FIXTURES ONLY, 60OV, COPPER, WITH A BONDING WIRE CONDUCTOR OR THE METAL SHEATHING OF CABLE SHALL NOT BE USED AS THE GROUNDING CONDUCTOR, BUT SHALL BE USED AS A SECOND PATH FOR GROUNDING PER NEC, TO BONO METALLIC SHEATHING TO OTHER WIRING METHODS. ALL ARMORED CABLES WHERE INSTALLED SHALL BE RUN CONCEALED. THIS WIRING METHOD USING ARMORED CABLE OR ANY OTHER ASSEMBLED CABLE(S) SHALL NOT BE USED FOR EMERGENCY SYSTEM BRANCH /FEEDER CIRCUITS. ARMORED CABLE SHALL BE UL LISTED AND SHALL COMPLY WITH FEDERAL SPECIFICATION J -C -30 AND SHALL BE MANUFACTURED BY AFC OR APPROVED EQUAL. ARMORED CLAD CABLE CONDUCTORS SHALL BE COLOR - CODED, CONTINUOUS ON INSULATION AS CALLED FOR HEREIN BEFORE. 5. BRANCH CIRCUIT AND FEEDER CONDUCTORS SHALL BE MANUFACTURED BY ONE OF THE FOLLOWING: CAROL CABLE, OKONITE, PIRELLI OR ROME CABLE CORP. C. ALL WIRE AND CABLE SHALL BE ANNEALED, COATED COPPER PER ASTM B 33 OR B 189 WITH CONDUCTIVITY OF NOT LESS THAN 98 PERCENT. ALL WIRE SHALL BE STRANDED, UNLESS SIZE 8 OR SMALLER, CLASS B PER ASTM 88. D. ALL WIRE SHALL HAVE 600 VOLT INSULATION, UL LISTED AND COMPLYING WITH UL83, ICEA S -61 -402 OR ICFA S -66 -524 FOR RESPECTIVE INSULATION TYPE AND SHALL BE COLOR - CODED. 0,ITj3UIL0INC OF -P'T'. rr1t %1:ECT- SE -TION 'w ROMITECTURE, irm Cert. No. AA2600115 210 Windy Preserve ake Worth, Florida 33467 honer (561)649 -505 ax:' Y (561) 649 -5�5 E -Mai l: MDT Arch - comdast.net ark D Taudien• AIA •rilncpai 9 l ' V✓ 'L ARCH. OF RLURpi MARK D. TAUDIEN AR 0011821 { €. B. A SEPARATE INSULATED GREEN GROUNDING CONDUCTOR SHALL BE PROVIDED FOR SECTION 16721 - FIRE ALARM AND DETECTION SYSTEM SECTION 16130 - BOXES EACH SINGLE AND 3 -PHASE FEEDER. AND BRANCH CIRCUIT, GROUNDING CONDUCTOR SHALL BE RUN WITH THE RELATED PHASE AND NEUTRAL CONDUCTORS. PANEL A. THE CONTRACTOR SHALL PROVIDE CONNECTION TO THE OWNERS EXISTING FIRE ALARM A. BOXES SHALL BE AS FOLLOWS: W z FEEDERS INSTALLED IN MORE THAN (1) RACEWAY- SHALL HAVE, INDIVIDUAL, FULL SIZED, SYSTEM. PROVIDE ALL; NECESSARY SYSTEM CABINETS, POWER SUPPLIES, O GREEN GROUNDING CONDUCTOR IN EACH RACEWAY. THE EQUIPMENT GROUNDING LL M00 CONTROLLERS, ekEY00AR0 DISPLAYS, LED DISPLAYS, BATTERIES, PERIPHERAL 1. GALVANIZED STEEL OUTLET BOXES CONFORMING TO UL STANDARD NO. 514 WILL BE SYSTEM SHALL NOT RELY ON THE METALLIC RACEWAYS FOR GROUNDING CONTINUITY. 111 DEVICES, VOICE EVACUA11ON SYSTEMS, ETC. FOR A COMPLETE AND FUNCTIONING USED FOR CONCEALED OUTLETS. C. a PROVIDE BONDING OF AL EQUIPMENT IN ACCQRDANCE WITH NFPA -70. u) SYSTEM. FIRE ALARM SYSTEM COMPONENTS SHALL MATCH EXISTING. 2. EXPOSED OUTLET BOXES SHALL BE CAST -METAL CONDUIT TYPE FS OR FD WITH ; B. THE SYSTEM SHALL COMPLY WITH ALL CURRENT, APPLICABLE CODES INCLUDING THE THREADED HUBS. FOLLOWING:,, 3. PULL AND JUNCTION BOXES SHALL CONFORM TO UL STANDARD 50, CONSTRUCTED SECTION 16460 - TRANSFORMERS t:' NATIOkAECTRICAL CODE (NEC) OF CODE GAUGE GALVANIZED STEEL AND BE SIZED PER THE REQUIREMENTS OF THE AI. STEPDOWN TRANSFORMERS, 480V TO 208/12OV, 3- PHASE, 4 -WIRE, SHALL BE DRY -TYPE, 2. NATIONAL FIRE PROTECTION AGENCY NATIONAL ELECTRIC CODE. O 2- WINDING, SELF - COOLED. ALL BUSES SHALL BE COPPER. TRANSFORMER SOUND 4. PROVIDE PULL AND JUNCTION BOXES AS REQUIRED. LEVELS SHALL NOT EXCEED THE ANSI AND NEMA SELF- COOLED RATING LEVELS. a. NFPA 72 EDITION 5. ALL JUNCTION AND PULL BOXES FOR EMERGENCY SYSTEMS AND LOW VOLTAGE B. TRANSFORMERS SHALL BE BY WESTINGHOUSE, SQUARE D OR GENERAL ELECTRIC. w > b. NFPA 101 LIFE SAFETY CODE SYSTEMS SHALL HAVE COVER PLATES PAINTED. COLORS FOR COVERS SHALL BE AS Z INDICATED BELOW: SECTION 16471 - DISTRIBUTION AND BRANCH CIRCUIT PANELBOARDS 0 3. ALL APPLICABLE UL STANDARDS AL PANELBOARDS SHALL BE DEAD FRONT SAFETY TYPE EQUIPPED WITH W 12u)", 4. AMERICANS WITH DISABILITIES ACT (ADA) LIFE SAFETY BRANCH YELLOW CRITICAL BRANCH ORANGE o THERMAL MAGNETIC AND /OR DIGITAL RMS SENSING TYPE MOLDED CASE CIRCUIT U) 5. LOCAL CODE REQUIREMENTS EQUIPMENT BRANCH GREEN BREAKERS OF TRIP RATINGS AS SHOWN ON THE DRAWINGS. LLJ CL o.Q FIRE ALARM RED B. PANELBOARD BUS STRUCTURE SHALL BE COPPER AND HAVE AN ASSEMBLY RATING IN C. CONTROL PANEL DATA/TELEPHONE SYSTEM BROWN EXCESS OF THE AVAILABLE SHORT CIRCUIT CURRENT (RMS SYMMETRICAL AMPS). ALL 1. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY HARDWARE A. Soym ARE U COPPER PARTS SHALL BE PLATED TO PREVENT CORROSION. r � PROGRAMMING NECESSARY TO ACCOMMODATE MODIFICATIONS INDICATED ONN SECTION 16140 - WIRING DEVICES C. CIRCUIT BREAKERS SHALL BE EQUIPPED WITH INDIVIDUALLY INSULATED BRACED AND DRAWINGS. LIGHT SWITCHES PROTECTED CONNECTORS. THE FRONT FACES OF ALL CIRCUIT BREAKERS SHALL BE D. BUILDING AUTOMATION SYSTEM INTERFACE REVISION DATE FLUSH WITH EACH OTHER. 1. SWITCHES SHALL BE FULL SIZE, HEAVY DUTY, AC TYPE, RATED FOR 120/277 VOLTS, I. WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE HUBBELL #122 -1, 11223 -1, #1224 -1. D. LARGE, PERMANENT, INDIVIDUAL CIRCUIT NUMBERS SHALL BE AFFIXED TO EACH BUILDING AUTOMATION SYSTEM (AUTOMATIC TEMPERATURE CONTROL SYSTEM) TO BREAKER IN A UNIFORM POSITION (OR EQUIP EACH BREAKER WITH A CIRCUIT CARD SEND AND RECEIVE SIGNALS FROM ALARM INITIATING DEVICES AND H -O -A SWITCHES ITIi 2. DIMMERS SHAM 8E 120 VOLTS 600 1000 AND 1500 WAIFS WITH SLIDER CONTROL, 0 WATT HOLDER AND NEATLY PRINTED CARD IDENTIFYING THE CIRCUIT). LEAVE "SPARE" FOR THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND COLOR SELECTED BY ARCHITECT, MANUFACTURED BY N SERIES OR CIRCUITS BLANK. TRIPPED ALL BE CLEARLY SHOWN BY THE BREAKER HANDLE TAKING COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WITH DIVISION 15000. APPROVED EQUAL WATTAGE OF CONNECTED LOAD TO THE DIMMER SHALT. NOT A POSITION BETWEEN ON AND OFF. PROVISIONS FOR ADDITIONAL BREAKERS SHALL BE A. EXCEED 80 PERCENT OF DIMMER RATING. SUCH THAT NO ADDITIONAL CONNECTORS WILL BE REQUIRED TO ADD BREAKERS. E. ALARM INITIATING DEVICES B. DUPLEX, RECEPTACLES E. PANELBOARD ASSEMBLY SHALL BE ENCLOSED IN A STEEL CABINET. THE SIZE OF 1 • PROVIDE ALL ALARM INITIATING DEVICES AS INDICATED ON FLOOR PLANS. DEVICES 1. DUPLEX RECEPTACLES SHALL BE HOSPITAL GRADE, U- GROUND, RATED FOR 120 WIRING GUTTERS SHALL BE IN ACCORDANCE WITH UL STANDARD 67. FRONTS SHALL SHALL MATCH EXISTING. WHERE SHOWN PROVIDE ALL MANUAL PULL STATIONS, SMOKE DETECTORS, HEAT DETECTORS, FLOW SWITCHES, AND TAMPER SWITCHES. VOLTS, 20 AMPERES. CATALOG NUMBERS ARE AS FOLLOWS. HUBBELL J5362. HAVE DOOR WITH MATCHING ONE PIECE TRIM, BE OF CODE GAUGE FULL FINISHED PROVIDE CONNECTION TO ALL DOOR RELEASE CIRCUITS AND ANCILLARY FIRE ALARM STEEL WITH RUST INHIBITING BAKED ENAMEL FINISH. CABINETS TO BE EQUIPPED WITH SPRING LATCH AND TUMBLER -LOCK ON DOOR OF TRIM. DOORS OVER 48" LONG SHALL FUNCTIONS AS INDICATED ON DRAWINGS. C. DEVICE PLATES BE EQUIPPED WITH THREE -POINT LATCH AND VAULT LOCK. ALL LOCKS SHALL BE F. ALARM INDICATING DEVICES 1. SWITCH DEVICE PLATES SNAIL BE MANUFACTURED OF NYLON. COLOR SHALL BE AS KEYED ALIKE. TRIMS SHALL BE DOOR -IN -DOOR DESIGN SO THAT BREAKERS AND SELECTED BY THE ARCHITECT. DEVICE PLATES SHALL BE NYLON AND OF THE SAME GUTTERS SHALL BE EXPOSED WHEN OTHER DOOR IS OPENED. 1. VISUAL STROBE UNITS SHALL MEET THE° REQUIREMENTS OF ADA, UL AND NFPA. MANUFACTURER AS WIRING DEVICES. DEVICE PLATE SCREWS SHALL. MATCH PLATES. F. PANELBOARDS SHALL BE FURNISHED WITH GROUND BUS. 2. AUDIBLE UNITS IN PUBLIC AND STAFF SPACES «SHAALL., BE SPEAKERS WITH A PEAK D. RECEPTACLES AND LIGHT SWITCHES ON EMERGENCY POWER SHALL BE RED IN COLOR OUTPUT OF 96 dB AT 10' -0 '. WITH RED DEVICE PLATES. C. PANELBOARDS RATED 480 -VOLTS AC SHALL HAVE SHORT CIRCUIT RATINGS AS 3. AUDIBLE UNITS IN MECHANICAL AREAS OR OTHER ARIAS WITH HIGH AMBIENT NOISE SECTION 16170 - CIRCUIT AND MOTOR DISCONNECTS INDICATED BELOW, BUT NOT LESS THAN 14,000 RMS SYMMETRICAL SHALL BE TRUMPET TYPE SUITABLE FOR SUC LOCH DNS. °> G. WIRING A. DISCONNECT SWITCHES SHALL BE AS FOLLOWS: H. BREAKERS SHALL BE A MINIMUM OF 100 AMPERE FRAME. BREAKERS 15 THROUGH 100 AMPERES TRIP SIZE SHALL TAKE UP THE SAME POLL= SPACING. I. ALL FIRE ALARM WIRING SHALL BE SUPERVISED. ALL WIRE AND CABLE SHALL BE I. FURNISH AND INSTALL DISCONNECT SWITCHES FOR DISCONNECTING MEANS FOR ALL SUITABLE FOR FIRE ALARM USE MO SHALL BE INSTALLED IN CONDUIT. EQUIPMENT. DISCONNECT SWITCHES SHALL BE OF THE TYPE 'A', QUICK -MAKE, 11. PANELBOARDS SHALL BE LABELED WITH THE UL SHORT CIRCUIT RATINGS AS 2. ALL WIRING SHALL BE STRANDED AND COLOR -CODED PER THE HOSPITAL'S QUICK -BREAK CONSTRUCTION. DISCONNECT SWITCHES SHALL HAVE INTERLOCKING INDICATED ON THE DRAWINGS. STANDARDS. DOORS. CABINETS SHALL BE BONDERIZED AND FINISHED IN GRAY ENAMEL NEMA TYPE 3R ENCLOSURES SHALL BE USED WHERE THE DISCONNECT SWITCH IS EXPOSED H. TESTING TO THE WEATHER OR IN WET AREAS. K. DISTRIBUTION PANELBOARDS SHALL BE PROVIDED FROM MANUFACTURERS AS LISTED 2• DISCONNECT DEVICES SHALL BE ONE OF THE FOLLOWING MANUFACTURERS: SQUARE BELOW- 1 • THE ENTIRE SYSTEM SHALL BE TESTED TO THE SATISFACTION OF THE OWNER AFTER D, GENERAL ELECTRIC OR WESTINGHOUSE. WHICH A FINAL ACCEPTANCE TEST WITNESSED BY THE LOCAL AUTHORITY, THE I. G.E. - TYPE SPECTRA SERIES OWNER'S BUILDING CONSTRUCTION DEPARTMENT AND AHCA. 3. ALL EQUIPMENT SHALL BE PROVIDED WITH THE PROPER SIZE /RATING DISCONNECT 2. SQUARE D COMPANY SWITCH WHETHER INDICATED ON THE DRAWINGS OR NOT TO COMPLY WITH NEC. SECTION 16740 -EMPTY RACEWAY SYSTEM ALSO, INSTALL AND CONNECT DISCONNECT SWITCHES FURNISHED BY OTHER TRADES. 3. WESTINGHOUSE A. AN EMPTY RACEWAY SYSTEM SHALL BE PROVIDED FOR USE BY THE TELECOMMUNICATION VENDOR FOR THE PULLING IN OF TELECOMMUNICATIONS WIRING SECTION 16190 - SUPPORTS IL INSTALLATION: AND EQUIPMENT. THE RACEWAY SYSTEM SHALL MEET THE EIA/TIA -569 STANDARDS. A. PROVIDE SUPPORTS AS FOLLOWS: I. PANELBOARDS SHALL BE INSTALLED IN LOCATIONS AS SHOWN ON THE DRAWINGS. B. TELECOMMUNICATIONS OUTLETS PANELBOARDS SHALL BE MOUNTED SUCH THAT THE HANDLE OF THE HIGHEST CIRCUIT 1. ALL SUPPORTS REQUIRED TO PROPERLY SUPPORT ALL EQUIPMENT, DEVICES, BREAKER DOES NOT EXCEED 6' -6" ABOVE FINISHED FLOOR. PANEL.80ARO CABINETS 1. EACH TELECOMMUNICATION OUTLET SHALL CONSIST OF A 4 11/16 " SQUARE OUTLET RACEWAYS, ETC. TO BE INSTALLED UNDER THIS CONTRACT. SHALL BE INSTALLED FLUSH MOUNTED AS INDICATED BY TRIM TYPE AS SHOWN ON THE BOX WITH SINGLE -GANG ADAPTOR AND BLANK COVER PLATE. 3/4 " CONDUIT SHALL RUN DRAWINGS. FROM THE OUTLET TO NEAREST ACCESSIBLE CORRIDOR CEILING. 2. PROVIDE SUPPORTS AS REQUIRED BY THE NEC. 2. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL DISTRIBUTION PANELBOARDS AS C. FURNISH AND INSTALL EMPTY CONDUIT OUTLETS AND MOUNTING BOARDS FOR MAN SECTION 16195 - IDENTIFICATION INDICATED ON THE DRAWINGS. INSTALL BOARDS IN ACCORDANCE WITH AND SECURITY SYSTEMS. A. EQUIPMENT IDENTIFICATION MANUFACTURER'S INSTRUCTIONS AND AS SPECIFIED HEREIN. PROVIDE ALL MOUNTING HARDWARE REQUIRED FOR PROPER INSTALLATION. I. PROVIDE ENGRAVED LAMINATED PHENOLIC NAMEPLATES TO IDENTIFY PANELBOARDS DISCONNECTS AND ALL MAJOR EQUIPMENT. 3• SURFACE MOUNTED PANELBOARDS SHALL BE MOUNTED INDEPENDENT OF THE WALL AND CONNECTING RACEWAYS. FURNISH STEEL CHANNEL SUPPORTS MOUNTED ON 2. NAMEPLATES SHALL INCLUDE THE PANEL AND CIRCUIT DESIGNATION AND SHALL BE THE WALL AND ATTACH THE PANELBOARDS TO THIS SUPPORT. LAMINATED, BAKELITE WITH 1/4 " HIGH, RECESSED LETTERS. NAMEPLATES SHALL BE SECURELY ATTACHED TO THE EQUIPMENT WITH GALVANIZED SCREWS. ADHESIVES OR 4. PANELBOARDS SHALL BE INSTALLED WITH WORK SPACE AS REQUIRED BY NEC. CEMENTS SHALL NOT BE USED. 5. PANELBOARDS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH NEC SEC11ON 3. NAMEPLATE FOR EQUIPMENT ON NORMAL POWER SHALL BE BLACK IN COLOR WITH 384.4. THE CONTRACTOR SHALL COORDINATE WORK WITH ALL OTHER TRADES IN WHITE RECESSED LETTERS. ORDER TO ASSURE COMPLIANCE TO THIS REQUIREMENT. 4. NAMEPLATES FOR DEVICES ON EMERGENCY POWER SHALL BE "RED" IN COLOR WITH WHITE RECESSED LETTERS. N. GROUNDING • 5. FURNISHING AND INSTALLING PERMANENT IDENTIFICATION MARKERS FOR ALL 1. DISTRIBUTION PANELBOARDS SHALL BE GROUNDED IN ACCORDANCE WITH THE NEC ELECTRICAL EQUIPMENT AND RACEWAYS INSTALLED UNDER THIS CONTRACT. AND AS SPECIFIED IN SECTION 16450 OF THIS CONTRACT. 6. NAMEPLATES SHALL INCLUDE THE FOLLOWING INFORMATION: "J. IDENTIFICATION a. EQUIPMENT IDENTIFICATION: SERVICE VOLTAGE- PHASE -WIRE, BRANCH OF POWER 1. PROVIDE NAMEPLATE FOR EACH PANEL IN ACCORD WITH SEC11ON 16195 OF THIS CONNECTED TO, AND SOURCE OF POWER THE EQUIPMENT IS FED FROM. CONTRACT. 7. ALL PANELBOARDS SHALL BE PROVIDED WITH NEW WRITTEN DIRECTORIES. ALL 2, PROVIDE NAMEPLATES FOR EACH BRANCH BREAKER ENCLOSED IN EACH DISTRIBUTION DIRECTORIES SHALL INDICATE LOADS SERVED AS WELL AS BREAKER RATINGS AND PANELBOARD IN ACCORD WITH SECTION 16195 OF THIS CONTRACT. POLE SPACE REQUIREMENTS FOR EACH LOAD. THIS REQUIREMENT APPLIES TO ALL NEW OR REVISED PANELBOARDS. PROVIDE COPY OF ALL DIRECTORIES TO ENGINEER 0. CLEANING OF RECORD. 1. ALL PANELBOARDS SHALL BE COMPLETELY CLEANED PRIOR TO ENERGIZING. B. CONDUIT IDENTIFICATION: 2. CLEANING SHALL. CONSIST OF VACUUMING ALL BUSES, ENCLOSURES (INSIDE AND OUT), 1. PROVIDE MANUFACTURER'S STANDARD PRE - PRINTED, FLEXIBLE OR SEMI - RIGID, ETC. AFTER VACUUMING IS COMPLETE, ALL EQUIPMENT SHALL BE WIPED DOWN. IF PERMANENT, PLASTIC -SHEET CONDUIT MARKERS, EXTENDING 360 DEGREES AROUND EQUIPMENT IS WET OR CONTAINS MOISTURE, IT SHALL BE THOROUGHLY DRIED CONDUITS; DESIGNED FOR ATTACHMENT TO CONDUIT BY ADHESIVE, ADHESIVE LAP BEFORE ENERGIZING. JOINT OF MARKER, MATCHING ADHESIVE PLASTIC TAPE AT EACH END OF MARKER, OR IP. TESTING PREIENSIONED SNAP -ON. EXCEPT AS OTHERWISE INDICATED, PROVIDE LETTERING WHICH INDICATES VOLTAGE OF CONDUCTOR(S) IN CONDUIT. PROVIDE MINIMUM 8 INCH 1. ALL DISTRIBUTION PANELBOARDS SHALL BE TESTED AS DESCRIBED IN SECTION 16198 LENGTH FOR 2 -INCH AND SMALLER CONDUIT, 12 -INCH LENGTH FOR LARGER CONDUIT. OF THIS CONTRACT PRIOR TO FINAL PAYMENT. 2. PAINT CONDUITS FOR EMERGENCY SYSTEMS AND LOW VOLTAGE SYSTEMS IN ACCORD WITH TABLE 1 OF THIS SECTION. SPACING OF PAINT MARKINGS SHALL BE 10' -0" ON CENTERS FOR ENTIRE LENGTH OF CONDUIT. C. COLOR -CODE TAPE 1. COLORED TAPE SHALL BE POLYVINYL CHLORIDE, SELF - ADHESIVE NOT LESS THAN 3 MILS THICK AND 1 -1/2 INCH WIDE, SUITABLE FOR USE ON 90 DEGREE C CONDUCTORS, UL LISTED AND SHALL BE FURNISHED IN COLORS AS SPECIFIED HEREIN. SECTION 16198 - TESTING A. ALLOW VOLTAGE 600V EQUIPMENT, CABLE, MOTORS, DRY TYPE TRANSFORMERS, ETC., SHALL BE FIELD TESTED PER NETA STANDARDS. SECTION 16450 - GROUNDING A A COMPLETE EQUIPMENT GROUNDING SYSTEM SHALL BE PROVIDED SUCH THAT ALL METALLIC STRUCTURES, ENCLOSURES, RACEWAYS, JUNCTION BOXES, OUTLET BOXES, CABINETS, MACHINE FRAMES METAL FENCES, AND ALL OTHER CONDUCTIVE ITEMS OPERATE CONTINUOUSLY AT GROUND POTENTIAL AND PROVIDE A LOW IMPEDANCE PATH TO GROUND FOR POSSIBLE FAULT CURRENTS. 0,ITj3UIL0INC OF -P'T'. rr1t %1:ECT- SE -TION 'w ROMITECTURE, irm Cert. No. AA2600115 210 Windy Preserve ake Worth, Florida 33467 honer (561)649 -505 ax:' Y (561) 649 -5�5 E -Mai l: MDT Arch - comdast.net ark D Taudien• AIA •rilncpai 9 l ' V✓ 'L ARCH. OF RLURpi MARK D. TAUDIEN AR 0011821 { €. SHEET Em6 PROJ. NO. 07 -11 -01 DATE: DEC. 10, 20071 1` Q o W z O LL z ® 111 LL u) z _0 j O U) ® z w > U) W Z U) 0 W 12u)", I- w U ILL o U) L7... z LLJ CL o.Q U) w U Q_ "- U r � � U J W NO. REVISION DATE SHEET Em6 PROJ. NO. 07 -11 -01 DATE: DEC. 10, 20071 1`