07-780R-023SYMBOL LIST MOUNTING HEIGHTS SHALL BE AS INDICATED UNLESS SHOWN OTHERWISE ON ELECTRICAL DRAWINGS OR ARCHITECTURAL ELEVATIONS RACEWAYS AND WIRING L43 -1,3 HOMERUN TO PANELBOARD. "L43" INDICATES PANEL, "1,3" INDICATES CIRCUIT LOAD -BREAK SWITCH NUMBERS, (20A, 1P, UNLESS INDICATED OTHERWISE) NUMBER OF SLASH MARKS - INDICATE NUMBER OF #12AWG CONDUCTORS IN MINIMUM 3/4 �� C. NO SLASH MOUNTED 54 "AFF MARKS INDICATE 2 #12 & 1 #12G -3/4 "C UNLESS INDICATED OTHERWISE. TELEPHONE NOTES: FLOOR MOUNTED 1. GREEN GROUND CONDUCTOR NOT INDICATED BUT SHALL BE INCLUDED IN EACH CEILING MOUNTED RACEWAY. SIZE SHALL BE #12AWG UNLESS INDICATED OTHERWISE. VP 2. HOMERUNS TO PANELBOARDS SHALL HAVE A MAXIMUM OF THREE (3) OUTLET, PHASE CONDUCTORS (ONE PER PHASE) PLUS NEUTRAL AND GROUND ♦S CONDUCTORS IN EACH CONDUIT. 16 FEEDER TAG - REFER TO LEGEND OF FEEDER SIZES LIGHTING FIXTURES F1 2 FLUORESCENT LIGHTING FIXTURE CEILING OR RECESSED MOUNTED. "Fl" INDICATES OUTLET V COMBINATION FIXTURE TYPE, "2" INDICATES CIRCUIT NUMBER, "a" INDICATERS SWITCH CONTROL, � 121 PLUG -IN BUSWAY MOM "• " INDICATES WIRED TO EMERGENCY BATERY BALLAST a CABLE TAP BOX V FLUORESCENT BARE LAMP STRIP OR INDUSTRIAL STRIP r'-- ---- -� FLUORESCENT UNDERCOUNTER TASK LIGHT O INCANDESCENT OR COMPACT FLUORESCENT RECESSED OR SURFACE MOUNTED !WIRED ON EMERGENCY CIRCUIT LIGHTING FIXTURE F T2 WALL MOUNTED LIGHTING FIXTURE (EMERGENCY WALL WASH OR DIRECTIONAL LIGHTING FIXTURE ® CEILING MOUNTED ILLUMINATED EXIT SIGN, ARROWS AS INDICATED ON DRAWINGS II EMERGENCY BATTERY UNIT F1 -'"' ARROW INDICATES TYPICAL LIGHTING FIXTURES IN CONTINUOUS ROW. FURNISH AND C� INSTALL ALL CORNERS, ENDCAPS, EXTENSIONS AND FITTINGS AS RQUIRED FOR A IKI LOVOLT-AM PERES COMPLETE INSTALLATION TOGGLE SWITCHES (MOUNTED 48" AFF) Sa SINGLE POLE TOGGLE SWITCH. "a" INDICATES FIXTURE CONTROL S2 DOUBLE POLE, DOUBLE THROW CENTER OFF TOGGLE SWITCH. HUBBELL SERIES 1382 S3 THREE WAY TOGGLE SWITCH SP SINGLE POLE TOGGLE SWITCH WITH PILOT LIGHT 2 INCANDESCENT DIMMER SWITCH. "D1" INDICATES 1000 WATT DIMMER, "D2" INDICATES 2000 WATT DIMMER. RECEPTACLES (MOUNTED 18" AFF) R21 -2 DUPLEX RECEPTACLE, "R21 " INDICATES PANEL, "2" INDICATES CIRCUIT NUMBER, GFI�E "E" INDICATES WIRED TO EMERGENCY PANEL, GFI INDICATES INTEGRAL GROUND FAULT DUPLEX RECEPTACLE MOUNTED 6" ABOVE COUNTER TOP DOUBLE DUPLEX RECEPTACLE DOUBLE DUPLEX RECEPTACLE MOUNTED 6" ABOVE COUNTER ® DUPLEX RECEPTACLE FLOOR MOUNTED (�l SPECIAL PURPOSE RECEPTACLE, "2" INDICATES TYPE, SEE SPECIAL PURPOSE Y RECEPTACLE SCHEDULE =0:0 TWO DUPLEX RECEPTACLES MOUNTED AT 18" AFF AND 24" AFF `f' SINGLE RECEPTACLE TELECOMMUNICATIONS (MOUNTED 18" AFF) NOTE: ALL OUTLET BOXES SHALL HAVE 1/2" CONDUIT STUBBED 6" ABOVE CEILINGS WITH BUSHING. BRANCH CIRCUIT WIRING NOTES: 1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES OR SPECIAL CONDITIONS 2. WIRING AND CONDUIT SHALL BE REQUIRED BETWEEN ALL OUTLETS INDICATED WITH CIRCUIT NUMBERS AND PANEL DESIGNATIONS 3. ALL SWITCH CONTROLS SHALL BE PROVIDED WITH WIRING AND CONDUIT AS REQUIRED 4. ALTHOUGH ALL BRANCH CIRCUIT WIRING AND CONDUIT IS NOT SHOWN, IT IS THE INTENT OF THESE DOCUMENTS THAT A COMPLETE BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED 5. A GREEN GROUNDING CONDUCTOR SHALL BE RUN WITH ALL CIRCUITS. VERIFY CONDUIT SIZE TO ENSURE IT CAN ACCOMODATE ALL PHASE, NEUTRAL AND GROUND CONDUCTORS. : \iobs \Mar r c Wa Z - Wa. : : POWER DISTRIBUTION EQUIPMENT ® DISTRIBUTION PANEL ® PANELBOARD, SURFACE MOUNTED PANELBOARD, FLUSH MOUNTED 0 JUNCTION BOX, SIZED PER NEC MOTOR, "2" INDICATES HORSEPOWER ® MAGNETIC MOTOR STARTER $M MANUAL MOTOR STARTER WITH THERMAL OVERLAOD. "P" INDICATES PILOT LIGHT a6P NON -FUSED DISCONNECT SWITCH, SIZE AS REQUIRED. "6P" INDICATES 6 POLE FUSED DISCONNECT SWITCH, SIZE OF SWITCH AND FUSE AS REQUIRED �J COMBINATION MAGNETIC STARTER AND FUSED DISCONNECT SWITCH. SIZE OF STARTER, SWITCH AND FUSE AS REQUIRED nT DRY -TYPE DISTRIBUTION TRANSFORMER. ONE TELEPHONE OUTLET LOAD -BREAK SWITCH Vw TELEPHONE OUTLET MOUNTED 54 "AFF ® TELEPHONE OUTLET FLOOR MOUNTED VC CEILING MOUNTED TELEPHONE OUTLET VP TELEPHONE OUTLET, PAYPHONE ♦S TELEPHONE OUTLET, SECURITY V COMPUTER SYSTEM OUTLET V COMBINATION TELEPHONE /DATA OUTLET NOTE: ALL OUTLET BOXES SHALL HAVE 1/2" CONDUIT STUBBED 6" ABOVE CEILINGS WITH BUSHING. BRANCH CIRCUIT WIRING NOTES: 1. WIRING IS SHOWN ON DRAWINGS ONLY FOR SPECIFIC ROUTES OR SPECIAL CONDITIONS 2. WIRING AND CONDUIT SHALL BE REQUIRED BETWEEN ALL OUTLETS INDICATED WITH CIRCUIT NUMBERS AND PANEL DESIGNATIONS 3. ALL SWITCH CONTROLS SHALL BE PROVIDED WITH WIRING AND CONDUIT AS REQUIRED 4. ALTHOUGH ALL BRANCH CIRCUIT WIRING AND CONDUIT IS NOT SHOWN, IT IS THE INTENT OF THESE DOCUMENTS THAT A COMPLETE BRANCH CIRCUIT WIRING SYSTEM BE INSTALLED 5. A GREEN GROUNDING CONDUCTOR SHALL BE RUN WITH ALL CIRCUITS. VERIFY CONDUIT SIZE TO ENSURE IT CAN ACCOMODATE ALL PHASE, NEUTRAL AND GROUND CONDUCTORS. : \iobs \Mar r c Wa Z - Wa. : : POWER DISTRIBUTION EQUIPMENT ® DISTRIBUTION PANEL ® PANELBOARD, SURFACE MOUNTED PANELBOARD, FLUSH MOUNTED 0 JUNCTION BOX, SIZED PER NEC MOTOR, "2" INDICATES HORSEPOWER ® MAGNETIC MOTOR STARTER $M MANUAL MOTOR STARTER WITH THERMAL OVERLAOD. "P" INDICATES PILOT LIGHT a6P NON -FUSED DISCONNECT SWITCH, SIZE AS REQUIRED. "6P" INDICATES 6 POLE FUSED DISCONNECT SWITCH, SIZE OF SWITCH AND FUSE AS REQUIRED �J COMBINATION MAGNETIC STARTER AND FUSED DISCONNECT SWITCH. SIZE OF STARTER, SWITCH AND FUSE AS REQUIRED nT DRY -TYPE DISTRIBUTION TRANSFORMER. ONE LINE POWER DIAGRAM �— LOAD -BREAK SWITCH E -3 FUSE, SIZE AS INDICATED �N TRANSFORMER, SIZE AS INDICATED E -5 CIRCUIT BREAKER -- <F- -�->>- DRAW -OUT CIRCUIT BREAKER ®i KIRK -KEY INTERLOCK �- CURRENT TRANSFORMER --3 �-- POTENTIAL TRANSFORMER AUTOMATIC TRANSFER SWITCH SOLID STATE TRIP UNIT _]__ GROUND ® AMMETER ® AMMETER SWITCH Q VOLTMETER ® VOLTMETER SWITCH � 121 PLUG -IN BUSWAY MOM FEEDER BUSWAY FT BI CABLE TAP BOX V PLUG -IN BUSWAY CIRCUIT BREAKER F DRY TYPE TRANSFORMER. "2" INDICATES SIZE, REFER TO DRY TYPE 2 TRANSFORMER SCHEDULE !WIRED ON EMERGENCY CIRCUIT "K" FACTOR DRY TYPE TRANSFORMER. "2" INDICATES SIZE, REFER TO "K" F T2 FACTOR DRY TYPE TRANSFORMER SCHEDULE MISCELLANEOUS ELECTRIC DUCT HEATER, FURNISHED AND INSTALLED BY HVAC SUBCONTRACTOR,. ED WIRED BY ELECTRICAL SUBCONTRACTOR TWO GANG OUTLET BOX WITH TELEVISION ANTENNA OUTLET AND ADJACENT T[V� DUPLEX RECEPTACLE. RUN 3/4" C FROM OUTLET BOX TO ABOVE NEAREST ACCESSIBLE CORRIDOR CEILING `x1 MUSHROOM TYPE PUSHBUTTON STATION FOR ACTIVATION OF SHUNT -TRIP DEVICE ST MOTOR RATED SWITCH FIRE ALARM SYSTEM F[] MANUAL PULL STATION MOUNTED 48" AFF ADA COMPLIANT AUDIO /VISUAL ALARM MOUNTED 80" AFF. 'V" INDICATES VISUAL V UNIT ONLY FC} NON ADA COMPLIANT AUDIOVISUAL ALARM MOUNTED 80" AFF O PHOTOELECTRIC SMOKE DETECTOR TAMPER SWITCH FURNISHED AND INSTALLED BY THE FIRE PROTECTION © SUBCONTRACTOR, WIRED BY THE ELECTRICAL SUBCONTRACTOR ® WATER FLOW SWITCH FURNISHED AND INSTALLED BY THE FIRE PROTECTION SUBCONTRACTOR, WIRED BY THE ELECTRICAL SUBCONTRACTOR. ® DUCT MOUNTED SMOKE DETECTOR WA-Cpi FIRE ALARM CONTROL PANEL ELECTRICAL DRAWING INDEX E -1 ELECTRICAL SYMBOLS E -2 FLOOR PLAN - UGHTING E -3 FLOOR PLAN - POWER AND SYSTEMS E -4 ELECTRICAL RISER DIAGRAMS E -5 ELECTRICAL DETAILS E -6 ELECTRICAL SPECIFICATIONS ABBREVIATIONS A /AMPERES AF /AMPERE FRAME (CIRCUIT BREAKER RATING) AFF /ABOVE FINISHED FLOOR AFG /ABOVE FINISHED GRADE AIC AMPERE INTERRUPTING CAPACITY AL ALUMINUM ARCH (ARCHITECT AT (AMPERE TRIP (CIRCUIT BREAKER RATING) ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GUAGE BLDG 03UILDING C (CONDUIT C.B. (CIRCUIT BREAKER C.T. (CURRENT TRANSFORMER CAT (CATALOG CIR (CIRCUIT COL (COLUMN CU (COPPER A [DELTA DWG [DRAWING E !WIRED ON EMERGENCY CIRCUIT EC EMPTY CONDUIT EM (EMERGENCY F (FLUSH FT (FEET G (GROUND KCMIL (ONE THOUSAND CIRCULAR MILS KVA IKI LOVOLT-AM PERES KVAR IKILOVOLT- AMPERES REACTIVE KW IKILOWATTS MCB (MAIN CIRCUIT BREAKER MCC IMOTOR CONTROL CENTER MISC IMISCELLANEOUS MLO ]MAIN LUGS ONLY NC ] NORMALLT CLOSED NEC (NATIONAL ELECTRICAL CODE NL INIGHT LIGHT NO (NORMALLY OPEN NTS INOT TO SCALE 0 !PHASE P IPOLE P.T. IPOTENTIAL TRANSFORMER PVC (POLYVINYL CHLORIDE R (RECESSED S 'SURFACE SCR 'SHORT CIRCUIT INTERRUPTING RATING SP 'SPARE SW SWITCH TEL TELEPHONE UG !UNDERGROUND V VOLT Y 'WYE W 'WATT WP 'WEATHERPROOF XFMR 'TRANSFORMER LIGHTING FIXTURE SCHEDULE LAMP DATA I FIXTURE DESCRIPTION MANUFACTURER CATALOG NUMBER VOLT NOTES QUANTITY WATTAGE TYPE DESIGNATION 2'x4' LENSED FLUORESCENT DAYBRITE 2DPG332- FA12 -1 /3EB 3 32 F32T8 F1 FIXTURE. RECESSED MOUNTED 120 2'x2' LENSED FLUORESCENT DAYBRITE 2DPG332- FA12 -1 /3EB 3 32 F321`8 F2 FIXTURE. RECESSED MOUNTED 120 RECESSED INCANDESCENT OMEGA OM615OA21SPLCL 1 150W A21 F3 DOWNUGHT 120 RECESSED FLUORESCENT OMEGA OMB2H26QPL -CS -120 2 26W QPL F4 DOWNUGHT 120 RECESSED FLUORESCENT CAPRI CR1QP- SHR12)C 1 25 A19 F5 SHOWER UGHT 120 RECESSED FLUORESCENT OMEGA OM61H18QPL -CS -120 2 18W QPL F6 DOWNUGHT 120 RECESSED FLUORESCENT OMEGA OM61H13QPL -CS -120 2 13W QPL F7 DOWNUGHT 120 -. SINGLE FACE EXIT SIGN BEGHEW APE- RU -W -AT LED ® ARROWS AS INDICATED ON PLANS 2 5W HALOGEN 120 W/ EMERGENCY BATT. AND HEADS -� DOUBLE FACE EXIT SIGN WITH EMERGENCY BATT. AND HEADS SAME AS SINGLE FACE SIGN GENERAL ELECTRICAL NOTES 1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND SHALL COMPLY WITH ALL LOCAL CODES AND ORDINANCES. 2. UNLESS OTHERWISE NOTED ALL INTERIOR CONDUCTORS SHALL BE COPPER WITH THHN INSULATION AND ALL EXTERIOR OR IN GROUND SHALL BE THWN INSULATION. ALL CONDUCTORS SHALL BE STRANDED. 3. ALL RACEWAYS SHALL COMPLY WITH THE GOVERNING CODES, EXCEPT E.M.T SHALL NOT BE USED AT THE EXTERIOR OF A BUILDING OR AT LOCATIONS SUBJECT TO SEVERE CORROSION. 4. OUTLET BOXES SHALL BE STAMPED STEEL IN DRY LOCATIONS, CAST ALLOY W /THREADED HUBS IN WET OR DAMP LOCATIONS AND SPECIAL ENCLOSURES FOR OTHER CLASSIFIED AREAS. 5. DISCONNECT SWITCHES SHALL BE H.P. RATED, GENERAL OR HEAVY DUTY, QUICK -MAKE, QUICK -BREAK ENCLOSURES AS REQUIRED BY EXPOSURE. 6. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ITEMS FOR COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 7. ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED BY THE LATEST EDITION OF THE N.E.C. 8. LOAD DATA IS BASED ON INFORMATION PROVIDED BY OWNER AT TIME OF DESIGN. VERIFY ALL EQUIPMENT AND PANEL SIZES. 9. ALL MATERIALS SHALL BE NEW AND SHALL BEAR UNDERWRITERS'. AND UNION LABELS, WHERE APPLICABLE. 10. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST -CLASS WORKMAN -LIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE, AND ACCEPTANCE BY OWNER MUST BE A CONDITION OF THE CONTRACT. 11. THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF THE LOCAL POWER AND LIGHT COMPANY AND THE LOCAL TELEPHONE COMPANY. 12. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR SHALL PROVIDE CIRCUITS AND ROUTING OF CONDUIT TO SUIT JOB CONDITIONS. 13. FURNISH AND INSTALL DISCONNECTED SWITCHES, WIRING AND CONNECTIONS ON AIR CONDITIONING SYSTEM AS SHOWN ON PLANS. CONTROLS ARE TO BE SUPPLIED BY THE AIR CONDITIONING CONTRACTOR AND CONNECTED BY THE ELECTRICAL CONTRACTOR. 14. ARCHITECTURAL AND /OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO REVISIONS OR SUBSTITUTIONS REQUESTED BY THE CONTRACTOR SHALL BE PAID FOR BY THE CONTRACTOR. CITY OF SOUTH MIAMI BUILDING 0f:PT, ELECTRICAL SECrION APPROVED BY:_ DATE: I I I IRONITECTURE, LC irm Cert. No. AA2600115 210 Windy Preserve ake Worth, Florida 33467 hone: (561)649 -5025 ax: (561) 649 -5025 -Mail: MDT Arch(@comcast.net lark D. Taudien: AIA 'rincipal CONSULTANTS SEAL J ,f ARCH. 'RECORD MARK TAUDIEN AR 0011821 Q D O J WN 0 U) Z� _ O Q� � O zvW w >_ oho uj � Z 00� a r Cfl NO. I REVISION SHEET E -1 PROJ. NO. 07 -11 -01 DATE: DEC. 10, 2007 W Z Z J U U) O W Q U U W W DATE