07-780R-012::vobs\M 1. THE CONTRACTOR SHALL CAREFULLY STUDY'AND COMPARE THE REFLECTED CEILING PLANS WITH THE ELECTRICAL LIGHTING PLANS, WITH THE MECHANICAL SUPPLY, RETURN AND EXHAUST PLANS, AND WITH THE FIRE PROTECTION PLANS AND REPORT TO THE ARCHITECT ANY ERROR, INCONSISTENCY OR OMISSION THAT HE MAY DISCOVER. 2. SPRINKLER HEADS ARE NOT INDICATED ON THE REFLECTED CEILING PLAN(S). THE CONTRACATOR SHALL INSTALL SUFFICIENT HEADS IN ALL SPACES TO MPROVIDE (100 %) AUTOMATIC COVERAGE AS DEFINED IN NFPA STANDARD 13 AND AS REQUIRED BU OWNERS INSURANCE UNDERWRITER. REFER TO FIRE PROTECTION DRAWINGS FORM LOCATIONS OF THE SPRINKLER HEADS. 3. THE CONTRACATOR SHALL VERIFY THAT ACCESS PANELS OF APPRORIATE SIZE ANAD TYPE ARE INSTALLED IN GYPSUM BOARD CEILINGS OR SOFFITS, IN CEMENT PLASTER CEILINGS OR SIFFITS, AND OTHER NON ACCESSIBLE TYPE CEILINGS OR SOFFETS WHERE ACCESS, SERVICE OR ADJUSTMENT TO MECHANICAL, PLUMBING, OR ELECTYRICAL ITEMS MAY BE NEEDED. ACCESS PANELS SHALL BE FIRE RATED TYPE EQUAL TO THE RATING OF THE CEILING OR SOFFIT IN WHICH THEY OCCUR. 4. ONLY CEILING MOUNTED EXIT LIGHTS ARE SHOWN ON THE REFLECTED CEILING PLAN(S). REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF WALL MOUNTED EXIT LIGHTS. 5. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF CEILING MOUNTED SMOKE DETECTORS, SPEAKERS, FIRE ALARM DEVICES, NURSE CALL DOME LIGHTS, ETC. 8. THE CONTRACTOR SHALL ADVISE THE OWNER AND TENANTS THAT AN 18' MINIMUM VERTICAL CLEARANCE SHALL BE MAINTAINED BETWEEN THE BOTTOM OF THE EXTENDED SPRINKLER HEADS AND THE TOP OF AN" FILES, SHELVING, LOCKERS, ETC. (WHETHER CONTRACATOR FURNISHED OR OWNER FURNISHED). THE CONTRACTOR SHALL ADVISE ALSO ADVISE THE OWNER AND TENANTS THAT ITEMS SHALL NOT REPLACED OR STORED ON TOP OF SUCH SHELVING SO THAT THIS CODE REQUIRED 18' MINIMUM VERTICAL CLLARANCE WILL BE MAINTAINED. THE CONTRACTOR SHALL PAINT 2' WIDE REDLINE ON THE WALLS OF ALL STORAGE ROOMS WITH STENCILING NOTED "DO NOT STORE OR PLACE ANY ITEMS ABOVE THIS LINE'. 7. WHERE EXISTING LAY -IN CEILINGS ARE REMOVED AND REINSTALLED, THE CONTRACTOR SHALL TAKE CARE NOT TO DAMAGE EITHER THE GRID OR CEILING TILES. ANY DAMAGED TILES OR GRID SHALL BE REPLACED WITH NEW MATERIALS. THESE MATERIALS SHALL MATCH THE EXISTING IN AUNIFORM MAANNER FOR COLOR, TEXTURE, PAATTERN, ETC. IF UNIFORMITY CAN NOT BE ACHIEVED; THE CONTRACTOR SHALL REPLACE THE ENTIRE CEILING WITHIN THAT SPACE WITH NEW MATERIAL. THE CONTRACTOR SHALL PROVIDE NEW MATERIAL AS APPROVED BY BOTH THE OWNER AND ARCHITECT. 8. THE CONTRACTOR SHALL PROVIDE ACCESS PANELS IN GYPSUM BOARD CEILINGS AND IN HARD SURFACE SOFFITS SO THAT THE ARCHITECT AND THE STATE AND LOCAL OFFICIALS CAN INSPECT RATED WALLS. THESE ACCESS PANELS SHALL BE LOCATED AT INTERVALS NOT TO EXCEED 30' -0' ON CENTER, MINIMUM OF ONE PER SPACE, AND IN SUCH MULTIPLE LOCATIONS AS NECESSARY TO VIEW ALL SURFACES OF THE RATED WALLS(S). 9. WHERE SUPPORT WIRES FOR ACOUSTICAL CEILING GRID CAN NOT BE INSTALLED VERTICALLY, THE CONTRACTOR SHALL PROVIDE/INSTALL A UNISTRUCT TRAPEZE BENEATH THE OBSTRUCTION (USUALLY DUCTS EXCEEDING 48' IN WIDTH) AS TO PERMIT WIRES TO BE VERTICALLY ATTACHMENT TO THE UNISTRUT. 10. PROVIDE UNISTRUT TO COMPLY WITH THE OWNNER FURNISHED VENDOR DRAWINGS FLOOR PLAN -- REFLECTED CEILING SCALE: 1/4" = 1' -0" LEGEND A = HEIGHT OF 9' -T B - HEIGHT OF 7' -e C - HEIGHT OF W & GYP. BD - PAINTED ACOUSTICAL CEILING LIGHTING FIXTURE RETURN AIR DIFFUSER AlWiff -vADZE (:o. RR -E,1; PAIWI ., L�-,r SUPPLY DIFFUSER FIRE SPRINKLER HEAD EXHAUST FAN MCNITECTURE, to „m Cert. Na. AA2600115 210 Windy Preserve aloe Worth, Florida 33467 hone: (561)649 -5025 ax: (561) 649 -5025 -Mail: MDT Arch Acom cast. ne lark D. Taudien: AIA Ancipai CONSULTANTS SEAL ARCH. OF `RECORD " MARK D. TAUOIEN AR 0011821 Q OO L.L. O r' V- J N ^ O LL. Q U O _ 0 3: Q ® Z O w z W U W �" a � DC LLJ U) ® U W F" U LjL LLj ® Z z o :5 CL 0 � r � r- O N0. I REVISION DATE 1 1' P. }?0.1?0 � I 1- ZNJ -a$ SHEET m PROD. NO. 07 -11 -01 DATE: DEC. 10, 2007 I,