07-780R-006KEYED NOTES
[]1 EXISTING STRUCTURAL CONCRETE COLUMN TO REMAIN (TYPICAL). INSTALL 3/4" METAL FURRING
AT 16 O.C. WITH R -4 THERMAL INSULATION AND SHEATHE WITH A LAYER OF 5/8 GYPSUM
WALLBOARD MECHANICALLY FASTENED.
[]2 EXISTTNG 8" CONCRETE BLOCK WALL TO REMAIN (TYPICAL). INSTALL NEW 3/4" METAL FURRING
AT 16m O.C. WITH R -4 THERMAL INSULATION AND SHEATHE WITH 1 LAYER OF 5/8 GYPSUM
WALLBOARD MECHANICALLY FASTENED.
[]3 ALUMINUM THRESHAOLD SET INTO BED OF SEALANT (ACCESSIBLE TYPE)
Q NEW 12'x 12' CERAMIC TILE WAINSCOAT ON WALLS IN TOILETS (3' -4' HIGH ON PLUMBING FIXTURE
WALL AND 5' -0' HIGH ON REMAINING WALLS). PROVIDE 1/4' THICK CLEAR MIRROR ON FIXTURE WALL
FROM WALL -TO -WALL, TOP OF WAINSCOAT TO CEILING.
[5� NEW STACKING REFRIGERATOR / FREEZER TO BE SUPPLIED BY THE TENANT, AND INSTALLED BTY THE
CONTRACTOR. SEE ELECTRICAL DRAWINGS.
[]6 NEW 51b, "MP" SERIES FIRE EXTINGUISHER IN A FULLY RECESSED, STAINLESS STEEL CABINET WITH
A CLEAR ACRYLIC DOOR BY LARSEN (OR APPROVED EQUAL)
[7] 4' DRYER VENTED TO GARAGE
® RELOCATED ELECTRIC PANEL
10 REFRIGERATOR (OFCI) WITH ICE MAKER CONNECTION.
11 DRYER (OFCI)
12 FURR OUT (MIN OP 6 ")
13 NEW RECESSED ELECTRIC PANEL TO BE PINTED TO MATCH WALL
14 FURR OUT WITH 2 -5/8 "x 20 GA METAL STUD FRAMING AT 16' O.C. AND 5/8' GYP. BD.
PROVIDE 2 -1/2' FIBERGLASS THERAML INSULATION
15 PLUMBING CHASE
16 EXISTING MASONRY WALL (1 HOUR FIRE RATED)
17 FIRE STOP ALL CONDUIT PENETRATIONS THROUGH CONCRETE SLAB ABOVE AND
NEW PARTITION (2 HOUR RATED) IN ACCORDANCE WITH UL DESIGN DIRECTORY.
PROVIDE DOCUMENTATION OF SELECTED SYSTEM TO AGENCY HAVING JURISDICTION.
18 EXISTING 20 MINUTE RATED DOORS TO BE REMOVED AND REPLACED WITH NEW.
EXISTING
PARKING
GARAGE
1. DO NOT SCALE DRAWINGS. IF DIMENSIONS ARE IN QUESTION, THE
CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING CLARIFICATION FROM THE
ARCHITECT BEFORE CONTINUING WITH CONSTRUCTION.
2. DIMENSIONS ARE SHOWN ON THE FLOOR PLANS FOR NEW CONSTUCTION ARE TO
CENTERLINE OF COLUMNS, TO FACE OF INTERIOR STUD WALLS, TO FACE OF CONCRETE
OR MASONRY WALLS, AND TO FACE OF EXTERIOR SIDE OF STUDS/ CONCRETE OR
MASONRY IN EXTERIOR WALLS.
3. DIMENSIONS ARE SHOWN ON THE FLOOR PLANS FOR RENOVATED SPACES ARE FROM
FACE OF EXISTING WALLS AND TO FACE OF NEW STUD WALLS, UNLESS OTHERWISE
INDICATED.
4. WHERE NEW GYPSUM BOARD PARATITIONS ARE A CONTINUATION OF AN EXISTING
PARTITION OR COLUMN ENCASEMENT, THE FACE OF THE NEW GYPSUM BOARD SHALL BE
ALIGNED WITH THE FACE OF THE EXISTING SURFACE. WHERE A ONE HOUR OR NOW
RATED PARTITION IS SHOWN AS A CONTINUATION OF A TWO HOUR PARTITION OR
COLUMN ENCASEMENT, THE FACE OF THE GYPSUM BOARD SHALL BE ALIGNED. STUDS
SHALL BE OFFSET AND AADDITIONAL LAYERS OF GYPSUM BOARD SHALL BE PROVIDED
TO PROVIDE FACE OF ALIGNMENT OF GYPUSM BOARD.
5. WHERE INDICATED ON THE FLOOR PLANS, FURR OUT RATED WALL, OR RATED SHAFT
WALL WITH 3 -51W STUDS AT 16' O.C. MAXIMUM UP TO 4' ABOVE CEILING IN ORDER TO
PROVIDE FOR RECESSED ITEMS IN THE WALL WITHOUT INTERFERING WITH THE
INTEGRITY OF THE RATED WALL. FURR OUT SHOULD BE OF ADEQUATE DEPTH AS
REQUIRED FPOR DEPTH OF RECESSED ITEMS.
6. ITEMS WITH A SURFACE AREA OF 16 SQUARE INCHES SHALL NOT BE RECESSED IN A
RATED WALL.
7. ALL WALLS SURROUNDING TOILETS, EXAM ROOMS, MECHANICAL ROOMS, OFFICES, OR
ADDITIONAL SPACES REQUIRING SOUND ATTENUATION SHALL HAVE WALL EXTENDED TO
THE UNDERSIDE OF THE FLOOR/ROOF DECK ABOVE. THESE WALLS SHALL HAVE 3 -112"
FIBERGLASS BATT SOUND ATTENUATION BLANKETS.
8. ITEMS DENOTED ON THE DRAWINGS WITH A DASH -DOT LINE ARE BEING FURNISHED BY
THE OWNER. THE CONTRACTOR SHALL COORDINATE WITH THE OWNER ON DELIVERY
AND INSTALLATION.
9. REFER TO VIEW WINDOW SCHEDULE FOR SIZE AND TYPE OF INTERIOR WINDOWS WHICH
ARE DENOTED WITH A NUMBER IN A HEXAGON.
10. ALL WALL MOUNTED SINKS AND LAVATORIES SHALL BE MOUNTED TO ALLOW FOR 1'-3'
MINIMUM BETWEEN THE CENTERLINE OF THE SINK AND FACE OF ADJACENT WALL, FIXED
EQUIPMENT, CASEWORK, ETC. THERE IS AN ADDITIONAL REQUIREMENT IS TO PROVIDE A
MINIMUM OF 4" BETWEEN SIDE OF SINK AND FACE OF ADJACENT WALL, FIXED
EQUIPMENT, CASEWORK, ETC.
11. HANDICAP ACCESSIBLE WATER CLOSETS SHALL BE MOUNTED SO THAT THERE IS
EXACTLY 1'-6" BETWEEN FACE OF THE CLOSEST ADJACENT SIDE WALL OR TOILET
PARTITION AND THE CENTERLINE OF THE WATER CLOSET. THE FLUSH VALVE FOR ALL
WATER CLOSETS SHALL BE MOUNTED ON THE 'OPEN-MOST' SIDE OF THE WATER CLOSET
AT 44' MAXIMUM A.F.F. TO THE TOP.
13. REFER TO DRAWING SHEET A -2 FOR ALL DIMENSIONED ELEVATIONS OF TYPICAL HANDICAP
ACCESSIBLE TOILETS.
14. REFER TO DRAWING SHEET A -2 FOR INTERIOR FINISHES, ACCENT WALLS, AND LOCATIONS OF
CORNER GUARDS, WALL BUMPERS GUARDS, HANRAILS, CHAIR RAILS, AND CROWN MOULDING.
15. REFER TO INDEX SHEET FOR ADDITIONAL; NOTES WHICH ALSO APPLY TO THE FLOOR PLAN(S).
16. PROVIDE ONE LAYER OF 518" TYPE X WATER RESISTANT GYPSUM BOARD AT WALLS BEHIND ALL
LAVATORIES AND FOR ALL WALLS IN ROOMS CONTAINING SHOWERS. WALLS BEHIND
SHOWERS AND TUBS SHALL RECEIVE 518" FIBERGLASS REINFORCED TILE BACKER BOARD.
17. ALL STUD WALLS INDICATED TO RECEIVE WALL MOUNTED SINKS AND LAVATAORIES SHALL
HAVE 6' MINIMUM STUD WALLS AS TO ACCOMMODATE PLUMBING CARRIERS.
18. ALL RECESSED FIRE EXTINGUISHER CABINETS SHALL BE FURRED OUT A MINIMUM OF W.
19. CASEWORK DIMENSIONS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION AND
INSTAALLATION OF CASEWORK. REFER TO CASEWORK NOTES FOR ADDITIONAL INFORMATION.
20. INTERIOR METAL STUDS SHALL BE 3-518" x 20 GAGE OR AS SHOWN BELOW UNLESS
DIMENSIONED, DETAILED OR NOTED OTHERWISE
21. WALL MOUNTED JANITOR SINK - 8' OUTSIDE FACE OF STUD TO OUTSIDE FACE OF STUD (2 -1/2'
STUDS EACH SIDE)
1. FLOOR MOUNTED SINGLE TOILET -6" STUDS
2. FLOOR MOUNTED BACK TO BACK TOILETS -10" OUTSIDE FACAE TO OUTSIDE FACE OF
STUD (2 -1/2' STUDS EACH SIDE)
3. WALL MOUNTED LAVATORIES - 6' STUDS
22. WALL MOUNTED LAVATORIES SHALL SUPPORT A MINIMUM 250 LB. VERTICAL LOAD.
3\Ma-rkx r cnwartmamn - wq,
0
I
FLOOR PLAN -- NEW CONSTRUCTION
SCALE: 1/4" = 1'--0"
NOTE:
PROVIDE FI -FOIL INSULATION R =4.3
- EXISTING
2 HOUR RATED
PARTITION
1. THE CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE CONTRACT DOCUMENTS
AND AT ONCE REPORT TO THE ARCHITECT ANY INCONSISTENCY OR OMISSION THAT MAY
OCCUR.
2. THE CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ITEMS REQUIRING FINISH SELECTIONS
THAT ARE NOT CLARIFIED IN THE CONTRACT DOCUMENTS.
3. SHEET VINYLS WITH A PATTERN REPEAT, SHALL BE INSTALLED WITH SEAMS PROPERLY
MATCHED. IF SHEET VINYL IS USED WITH PRECISE PATTERN INLAY, UTILIZE METAL TEMPLATE
TO CUT SHEET VINYL.
4. HEAT WELDED SHEET VINYLS SHALL HAVE WELDING ROD COLOR SELECTED BY OWNER OR
ARCHITECT.
5. ALL RUBBER BASE SHALL BE 4' HIGH. VINYL BASE CAN NOT BE SUBSTITUTED FOR RUBBER
BASE.
6. ALL CEILINGS AND UNDERSIDE SURFACE OF SOFFITS TO BE PAINTED TO MATCH'SHERWIN
WILLLAMS ", SW #1004, PURE WHITE UNLESS OTHERWISE NOTED.
7. ALL `WET WALLS' OF TOILET ROOMS SCHEDULED TO RECEIVE PAINTED FINISH SHALL HAVE
EPDXY PAINT FINISH.
8. WHERE FINISHES ARE TO MATCH EXISTING MATERIALS; FINISH SCHEDULE HAS BEEN NOTED
AS (MEX). THE CONTRACTOR SHALL FIELD VERIFY.
9. ALL FLOORING TRANSITIONS SHALL OCCUR AT THE CENTERLINE OF ALL DOORS UNLESS
OTHERWISE DESIGNATED.
10. CEILING ACCESS PANELS. HVAC DIFUSSERS /GRILLES SHALL BE WHITE UNLESS OTHERWISE
NOTED.
11. THRESHOLD AND FLOOR MATERIAL TRANSITIONS ARE AS FOLLOWS:
a. VINYL TILE / CARPET; "ROPPE" TRANSITION PIECE #159
b. SHEET VINYL/ CARPET: `ROPPE' TRANSISTION PIECE # 168
C. INTEGRAL BASE CAP STRIP: 'ROPPE" #28
d. OWNER OR ARCHITECT TO SELECT COLORS FROM 'ROPPE' COLOR CHAIN.
12. THE CONTRACTOR SHALL PAINT ALL PARTITIONS AND DRYWALL CEILINGS WITH 1 COAT LATEX
PRIMER AND 2 COATS LATEX FINISH (FLAT) IN COLOR SELECTED BY OWNER.
13. ALL PAINT GRADE DOORS AND FRAMES SHALL RECEIVE 1 COAT LATEX PRIMER AND 2 COATS
LATEX FINISH (SEMI - GLOSS) IN COLOR SELECTED BY OWNER,
i
176
119NITC-07URE, Le
=irm Cd& No.JAA2600115
1210 Windy Preserve
.ake Worth, Florida 33467
)hone: (561)649 -5025
=ax: (561) 649 -5025
-Mail: MDT ArchAlcomcast.ne�
/hark D. Taudien• AIA
2rincipai
CONSULTANTS
SEAL
r,
s � 1
1
r •c'
u`- ,
�
r
ARCH. OF RECORD
MARK D. TAUDIEN
AR 0011821
O
J J
u- Q
{.� i)
OF°
LL .�
(0
z �: z
zow
/
W z
♦ j 0
LL
'� U
0
W
♦♦W • w z
O VzJ Qz
J
O (f) cL
w w
O
r _.J
LL.
N0. REVISION DATE
0 gu�&. Vt� : 312S oB
SHEET
A -1
PROD. NO. 07 -11 -01
DATE: DEC. 10, 2007