06-785-011BASIC TEST FOR SMOKE DETECTOR WITH AIR HANDLING UNIT OFF AND POWER APPLIED TO THE AIR DUCT DETECTOR /SENSOR, INTRODUCE SMOKE INTO THE DETECTOR /SENSOR, OR ACTIVATE THE BUILT -IN TEST FEATURE AS DESCRIBED IN THE 4098 DETECTORS, SENSORS AND BASES APPLICATION MANUAL 574 -709. OBSERVE ALARM LED OPERATIONS. RESTORE NORMAL OPERATION TO DETECTOR BY MOMENTARILY REMOVING AC POWER, OR BY REMOVING AND REPLACING THE DETECTOR HEAD AFTER SMOKE HAS BEEN CLEARED FROM ITS CHAMBER. t SPLIT SYSTEM AIR HANDLING UNIT SCHEDULE UNIT SCHEDULE FAN SCHEDULE AIR HANDLING UNIT AIR HANDLING UNIT AIR COOLED CONDENSING UNIT AIR COOLED CONDENSING UNIT SYSTEM DATA ^ MARK LOCATION TRANE AIRFLOW(CFM) ESP FAN DX COIL HEATER ELECTRICAL WT MARK MODEL WT ELECTRICAL COMPRESSOR FAN UNIT COOLING CAPACITY EER REMARKS EER REMARKS DEL B CEILING GRILLE MODEL AS SHOWN AS SHOWN TYPE 1 (SURFACE) ( ) SEE PLAN TITUS TDC -AA TOTAL OA HP FLA KW STAGE V /O /HZ MCA MOCP QTY. TONS RLA HP FLA MCA MOCP TMBH SMBH EAT DB /WB TYPE SERVED NO. MCA /F PJ . LBS TONS NO. LBS VOLTS -PH -HZ (SEER) MOCP AHU -103 SW OFFICE TWE060P13 1,800 300 0.50 0.50 3.1 3/12 7.2 1 208/1/60 47 50 173 CU -103 2TTAO060A300 217 208/3/60 1 5.0 19.7 0.25 1.9 27 45 58.8 42.9 77.3'/65.0' 10.75 SEE NOTES AHU -104 SW OFFICE TWE090A 2.600 140 0.50 1.50 6.2 3/12 8.7 1 208/1/60 60 70 317 CU -104 2TTAO072A300 261 208/3/60 1 6.0 19.8 0.16 1.4 26 45 65.6 57.4 75.8'/61.8' 10.55 SEE NOTES AHU -105 SE OFFICE TWE060P13 1,550 240 0.50 0.50 3.1 3/12 7.2 1 208/1/60 47 50 173 CU -105 2TTA006OA300 217 208/3/60 1 5.0 19.7 0.25 1.9 27 45 57.6 41.1 77.5'/64.8' 10.75 SEE NOTES LUNCH ROOM GREENHECK SP -A290 120 -1 -60 130 0.400 DIRECT 2.0 21 LBS. WATTS GENERAL NOTES FOR ALL UNITS 1. TRANE IS THE BASIS OF DESIGN AND THE STANDARD FOR COMPARISON. 16. ALL AIR HANDLING UNITS AND CONDENSING UNITS INDICATED IN THE BUILDING 2. OUTSIDE AIR DESIGN CONDITIONS: 91'FDB - 79'FOB. GENERAL NOTES FOR ALL UNITS 3. MECHANICAL CONTRACTOR SHALL PROVIDE, AND ELECTRICAL CONTRACTOR SHALL WIRE AND INSTALL WEATHERPROOF DISCONNECT FOR CONDENSING UNIT 1. TRANE IS THE BASIS OF DESIGN AND THE STANDARD FOR COMPARISON. 16. ALL AIR HANDLING UNITS AND CONDENSING UNITS INDICATED IN THE BUILDING MECHANICAL CONTRACTOR SHALL PROVIDE, AND ELECTRICAL CONTRACTOR SHALL WIRE AND INSTALL DISCONNECT FOR AHU. 2. OUTSIDE AIR DESIGN CONDITIONS: 91'FDB - 79'FDB. OF 87 %EFF. SHALL HAVE THE FOLLOWING. a) NON BLEED THERMOSTATIC EXPANSION VALVE, MANUFACTURER SHALL PROVIDE COMPLETE WITH ELECTRIC HEAT AND SINGLE POINT ELECTRICAL CONNECTION. 3. MECHANICAL CONTRACTOR SHALL PROVIDE, AND ELECTRICAL CONTRACTOR SHALL WIRE AND INSTALL WEATHERPROOF DISCONNECT FOR CONDENSING UNIT CRANK CASE HEATER, SOLENOID VALVE, HARD START KIT & THE PIPING SHALL 6. 4. MECHANICAL CONTRACTOR SHALL PROVIDE, AND ELECTRICAL CONTRACTOR SHALL WIRE AND INSTALL DISCONNECT FOR AHU. BE INSTALLED USING LONG RADIUS ELBOWS. 5. MANUFACTURER SHALL PROVIDE COMPLETE WITH ELECTRIC HEAT AND SINGLE POINT ELECTRICAL CONNECTION. * AIR HANDLERS MUST HAVE A LIQUID LINE SOLENOID INSTALLED AT THE AIR HANDLERS. EQUIPMENT SYSTEM NOTES ( TRANE) 7. 6. MANUFACTURER SHALL PROVIDE COMPLETE WITH FILTER - DRIER, LIQUID LINE SOLENOID, SIGHT GLASS, COASTAL FILTER, CRANKCASE HEATER, ANTI -SHORT * PROVIDE ALL CONDENSER COMPRESSORS WITH CRANK CASE HEATERS. CONNECTION CYCLE PROTECTION, HIGH - PRESSURE SWITCH,LO- PRESSURE SWITCH, AND THERMOSTATIC EXPANSION VALVE. MANUFACTURER SHALL PROVIDE COMPLETE WITH FOUR INCH 45% A.D.S. EFFICIENCY FILTERS. * AIR HANDLERS MUST HAVE A LIQUID LINE SOLENOID INSTALLED AT THE AIR HANDLERS. 7. CONTRACTOR SHALL PROVIDE COMPLETE WITH 95% EFFICIENT VIBRATION ISOLATION. PROVIDE A/C UNITS WITH DIGITAL PROGRAMMABLE HEATING AND COOLING THERMOSTAT WITH ON -OFF SWITCH SUB -BASE. * PROVIDE ALL CONDENSER COMPRESSORS WITH CRANK CASE HEATERS. 10. 8. MANUFACTURER SHALL PROVIDE COMPLETE WITH FOUR INCH 45% A.D.S. EFFICIENCY FILTERS FOR AHU -103, 104, & 105. * PROVIDE EVAPORATOR COILS WITH NON BLEED TXV'S * ROOF MOUNTED CONDENSING UNITS TO BE POSITIONED WITH UNITS SERVING 8. INTERLOCK EF -5 & EF -7 WITH AHU -106. 9. PROVIDE A/C UNITS WITH DIGITAL PROGRAMMABLE HEATING AND COOLING THERMOSTAT WITH ON -OFF SWITCH SUB -BASE. * ADD 2 OZ. OF OIL FOR EACH 10 FEET OF LINE OVER 200 FEET. THE LOWEST LEVELS CLOSER TO THE LINE CHASE TO MINIMIZE REFRIGERANT LINE DISTANCE. 10. SIZE AND RUN REFRIGERANT PIPING AS PER MANUFACTURER'S, AND ASHRAES' PUBLISHED RECOMMENDATIONS FOR INSTALLED LENGTH OF RUN. MECHANICAL * PROVIDE EVAPORATOR COILS WITH NON BLEED TXV'S CONTRACTOR SHALL CLOSELY COORDINATE ALL REQUIRED APPURTENANCES REQUIRED FOR THE INSTALLED DISTANCE REQUIREMENTS WITH THE UNIT MANUFACTURER. * ADD 2 OZ. OF OIL FOR EACH 10 FEET OF LINE OVER 200 FEET. 11. PROVIDE PROPER VIBRATION ISOLATORS AS PER MANUFACTURERS RECOMMENDATIONS, PLANS AND SPECIFICATIONS. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES. * ALL LINE LENGTH, SIZES AND UNIT LOCATION MUST BE REVIEWED AND 12. INSULATE REFRIGERANT SUCTION LINE WITH 3/4" FIRE RETARDANT ARMAFLEX. THEN SUBMITTED TO THE LOCAL TRANE OFFICE FOR APPROVAL. APPROVED BY THE INSTALLING CONTRACTOR. ALL LINE LENGTH AND 14. 13. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES. SIZES MUST FOLLOW TRANE APPLICATION GUIDE PUBLICATION # 32- 3009 -03, CONTRACTOR SHALL COORDINATE WITH STRUCTURAL ENGINEER SIZE OF HANGER RODS AND CONCRETE INSERT FOR ALL EQUIPMENT. THEN SUBMITTED TO THE LOCAL TRANE OFFICE FOR APPROVAL. 14. PROVIDE BUILT -IN DISCONNECT WITH ALL AIR HANDLING UNITS. ' 15. CONTRACTOR SHALL COORDINATE WITH STRUCTURAL ENGINEER SIZE OF HANGER RODS AND CONCRETE INSERT FOR ALL EQUIPMENT. BASIC TEST FOR SMOKE DETECTOR WITH AIR HANDLING UNIT OFF AND POWER APPLIED TO THE AIR DUCT DETECTOR /SENSOR, INTRODUCE SMOKE INTO THE DETECTOR /SENSOR, OR ACTIVATE THE BUILT -IN TEST FEATURE AS DESCRIBED IN THE 4098 DETECTORS, SENSORS AND BASES APPLICATION MANUAL 574 -709. OBSERVE ALARM LED OPERATIONS. RESTORE NORMAL OPERATION TO DETECTOR BY MOMENTARILY REMOVING AC POWER, OR BY REMOVING AND REPLACING THE DETECTOR HEAD AFTER SMOKE HAS BEEN CLEARED FROM ITS CHAMBER. t SPLIT SYSTEM AIR HANDLING UNIT SCHEDULE FAN SCHEDULE O.A. VENTILATION (CFM PER PERSON) AIR HANDLING UNIT TOTAL AIR COOLED CONDENSING UNIT o SYSTEM DATA MARK MANUFACTURER LOCATION TRANE AIRFLOW(CFM) ESP FAN MODULE # 1 MODULE # 2 ELECTRICAL WT MARK MODEL A WT ELECTRICAL COMPRESSOR FAN UNIT COOLING CAPACITY EER REMARKS SEE NOTES B CEILING GRILLE MODEL AS SHOWN AS SHOWN TYPE 1 (SURFACE) ( ) SEE PLAN TITUS TDC -AA SEE NOTES C CEILING GRILLE AS SHOWN AS SHOWN AS SHOWN TYPE (LAY -IN) SEE PLAN TITUS TLF -AL SEE NOTES D CEILING GRILLE TOTAL OA HP I FLA TYPE VELOCITY TYPE PRIMARY V /0 /HZ MCA MOCP QTY. TONS RLA HP FLA MCA MOCP TMBH SMBH EAT T SERVED NO. LBS NO. LBS VOLTS -PH -HZ (SEER) AHU -106 STANDARD FOR COMPARISON. OPERATING AREA MCCB -06 2,050 400 1.50 3.00 11.0 HEPA 500 FPM FLAT THROWAWAY 208 -3 -60 13.8 25 1512 CU -106 2TTA0072A300 261 208/3/60 1 6.0 19.8 0.16 1.4 26 45 74.2 54.9 78.2'/65.4' 53.2'/53.0' 10.55 SEE NOTES DIRECT 1.6 10 LBS. 99.9% W80 S EF -7 SUBSTERILE /DIRTY ROOM GREENHECK SP -A510 120 -1 -60 200 0.375 DIRECT 2.3 31 LBS. WATTS EF -8 LUNCH ROOM GREENHECK SP -A290 120 -1 -60 130 0.400 DIRECT 2.0 21 LBS. WATTS GENERAL NOTES FOR ALL UNITS 1. TRANE IS THE BASIS OF DESIGN AND THE STANDARD FOR COMPARISON. 16. ALL AIR HANDLING UNITS AND CONDENSING UNITS INDICATED IN THE BUILDING 2. OUTSIDE AIR DESIGN CONDITIONS: 91'FDB - 79'FOB. SHALL HAVE THE FOLLOWING. a) NON BLEED THERMOSTATIC EXPANSION VALVE, 3. MECHANICAL CONTRACTOR SHALL PROVIDE, AND ELECTRICAL CONTRACTOR SHALL WIRE AND INSTALL WEATHERPROOF DISCONNECT FOR CONDENSING UNIT CRANK CASE HEATER, SOLENOID VALVE, HARD START KIT & THE PIPING SHALL 4. MECHANICAL CONTRACTOR SHALL PROVIDE, AND ELECTRICAL CONTRACTOR SHALL WIRE AND INSTALL DISCONNECT FOR AHU. BE INSTALLED USING LONG RADIUS ELBOWS. OF 87 %EFF. 5. MANUFACTURER SHALL PROVIDE COMPLETE WITH ELECTRIC HEAT AND SINGLE POINT ELECTRICAL CONNECTION. EQUIPMENT SYSTEM NOTES (TRANE): 6. ALL FANS SHALL BE MIN. 6. MANUFACTURER SHALL PROVIDE COMPLETE WITH FILTER - DRIER, LIQUID LINE SOLENOID, SIGHT GLASS, COASTAL FILTER, CRANKCASE HEATER, ANTI -SHORT CYCLE PROTECTION, HIGH - PRESSURE SWITCH,LO- PRESSURE SWITCH, AND THERMOSTATIC EXPANSION VALVE. * AIR HANDLERS MUST HAVE A LIQUID LINE SOLENOID INSTALLED AT THE AIR HANDLERS. PROVIDE BACKDRAFT DAMPER. 7. CONTRACTOR SHALL PROVIDE COMPLETE WITH 95% EFFICIENT VIBRATION ISOLATION. * PROVIDE ALL CONDENSER COMPRESSORS WITH CRANK CASE HEATERS. CONNECTION 8. MANUFACTURER SHALL PROVIDE COMPLETE WITH FOUR INCH 45% A.D.S. EFFICIENCY FILTERS. * ROOF MOUNTED CONDENSING UNITS TO BE POSITIONED WITH UNITS SERVING 9. PROVIDE A/C UNITS WITH DIGITAL PROGRAMMABLE HEATING AND COOLING THERMOSTAT WITH ON -OFF SWITCH SUB -BASE. THE LOWEST LEVELS CLOSER TO THE LINE CHASE TO MINIMIZE REFRIGERANT LINE DISTANCE. 10. SIZE AND RUN REFRIGERANT PIPING AS PER MANUFACTURER'S, AND ASHRAES' PUBLISHED RECOMMENDATIONS FOR INSTALLED LENGTH OF RUN. MECHANICAL * PROVIDE EVAPORATOR COILS WITH NON BLEED TXV'S 8. INTERLOCK EF -5 & EF -7 WITH AHU -106. CONTRACTOR SHALL CLOSELY COORDINATE ALL REQUIRED APPURTENANCES REQUIRED FOR THE INSTALLED DISTANCE REQUIREMENTS WITH THE UNIT MANUFACTURER. * ADD 2 OZ. OF OIL FOR EACH 10 FEET OF LINE OVER 200 FEET. 11. PROVIDE PROPER VIBRATION ISOLATORS AS PER MANUFACTURERS RECOMMENDATIONS, PLANS AND SPECIFICATIONS. * ALL LINE LENGTH, SIZES AND UNIT LOCATION MUST BE REVIEWED AND 12. INSULATE REFRIGERANT SUCTION LINE WITH 3/4" FIRE RETARDANT ARMAFLEX. APPROVED BY THE INSTALLING CONTRACTOR. ALL LINE LENGTH AND 13. INSTALL CHEMICAL DRYER AND STRAINER IN REFRIGERANT LIQUID LINES. SIZES MUST FOLLOW TRANE APPLICATION GUIDE PUBLICATION # 32- 3009 -03, THEN SUBMITTED TO THE LOCAL TRANE OFFICE FOR APPROVAL. 14. PROVIDE BUILT -IN DISCONNECT WITH ALL AIR HANDLING UNITS. 15. CONTRACTOR SHALL COORDINATE WITH STRUCTURAL ENGINEER SIZE OF HANGER RODS AND CONCRETE INSERT FOR ALL EQUIPMENT. BASIC TEST FOR SMOKE DETECTOR WITH AIR HANDLING UNIT OFF AND POWER APPLIED TO THE AIR DUCT DETECTOR /SENSOR, INTRODUCE SMOKE INTO THE DETECTOR /SENSOR, OR ACTIVATE THE BUILT -IN TEST FEATURE AS DESCRIBED IN THE 4098 DETECTORS, SENSORS AND BASES APPLICATION MANUAL 574 -709. OBSERVE ALARM LED OPERATIONS. RESTORE NORMAL OPERATION TO DETECTOR BY MOMENTARILY REMOVING AC POWER, OR BY REMOVING AND REPLACING THE DETECTOR HEAD AFTER SMOKE HAS BEEN CLEARED FROM ITS CHAMBER. t AIR DISTRIBUTION SCHEDULE EXHAUST FAN SCHEDULE O.A. VENTILATION (CFM PER PERSON) OVERALL TOTAL AIR FLOW o FAN LOCATION SERVED MANUFACTURER MODEL MARK TYPE SIZE NECK SIZE (CFM) FRAME THROW MAKE MODEL REMARKS A DIFFUSER 24X24 AS SHOWN AS SHOWN TYPE 3 (LAY -IN) SEE PLAN TITUS TDC -AA SEE NOTES B CEILING GRILLE AS SHOWN AS SHOWN AS SHOWN TYPE 1 (SURFACE) ( ) SEE PLAN TITUS TDC -AA SEE NOTES C CEILING GRILLE AS SHOWN AS SHOWN AS SHOWN TYPE (LAY -IN) SEE PLAN TITUS TLF -AL SEE NOTES D CEILING GRILLE AS SHOWN AS SHOWN AS SHOWN TYPE 3 (LAY -IN) SEE PLAN TITUS 3FL SEE NOTES E CEILING GRILLE AS SHOWN AS SHOWN AS SHOWN TYPE 1 (SURFACE) ) SEE PLAN TITUS 3FL SEE NOTES WA°TS NOTES: DIFFUSER & GRILLE LEGENDS 1. TITUS IS THE BASIS OF DESIGN AND TRASH STANDARD FOR COMPARISON. DEVICE TYPE THROW PATTERN 2. REFER TO ARCHITECTURAL DRAWINGS FOR CEILING TYPE. 0.375 3. PROVIDE OFF WHITE FINISH UNLESS OTHERWISE NOTED NECK SIZE _8 "O Al 100 AIR VOLUME (CFM) (SUBJECT TO ARCH. APPROVAL). 4. SEE FLOOR PLANS FOR VARIATIONS OF THROW & DIRECTIONS. 6X6 -FACE SIZE 5. ALL AIR DISTRIBUTION DEVICES ARE ALUMINUM. OR OVERALL SIZE 6. PROVIDE IF REQUIRED TRANSITIONS FOR NECK SIZES. EF -6 BASIC TEST FOR SMOKE DETECTOR WITH AIR HANDLING UNIT OFF AND POWER APPLIED TO THE AIR DUCT DETECTOR /SENSOR, INTRODUCE SMOKE INTO THE DETECTOR /SENSOR, OR ACTIVATE THE BUILT -IN TEST FEATURE AS DESCRIBED IN THE 4098 DETECTORS, SENSORS AND BASES APPLICATION MANUAL 574 -709. OBSERVE ALARM LED OPERATIONS. RESTORE NORMAL OPERATION TO DETECTOR BY MOMENTARILY REMOVING AC POWER, OR BY REMOVING AND REPLACING THE DETECTOR HEAD AFTER SMOKE HAS BEEN CLEARED FROM ITS CHAMBER. t ASHRAE 62 CONFORMANCE UNIT � EXHAUST FAN SCHEDULE O.A. VENTILATION (CFM PER PERSON) VENTILATION ON TOTAL AREA SERVED o FAN LOCATION SERVED MANUFACTURER MODEL (CFM) VOLT CFM HP OR S.P DRIVE SONES WEIGHT SW OFFICE AHU -104 7 1.00 20 140 140 SW OFFICE WATTS 10 0.85 20 170 EF -3 SE OFFICE TOILET GREENHECK SP -8110 20 120 -1 -60 75 WAOTS 0.375 DIRECT 1.5 10 LBS. �LL. -4- _� , NOTE: *ASHRAE 62 -1989 ALLOWS "WHERE PEAK OCCUPANCIES OF LESS THAN THREE HOURS DURATION OCCUR, THE OUTDOOR AIR FLOW RATE MAY BE DETERMINED ON THE BASIS OF AVERAGE OCCUPANCY FOR BUILDING FOR THE DURATION OF OPERATION OF THE SYSTEM, PROVIDED THE AVERAGE OCCUPANCY USED IS NOT LESS THAN ONE - HALF THE MAXIMUM. •* PROVIDED 25 AIR CHANGES PER HOUR (ACH) FOR SUPPLY AIR AND 5 ACH FOR FRESH AIR. EF -4 TOILET GREENHECK SP -8110 120 -1 -60 75 0.375 DIRECT 1.5 10 LBS. WA°TS EF -5 TRASH GREENHECK SP -8110 120 -1 -60 T30 0.375 DIRECT 1.6 10 LBS. WATTS EF -6 MEDIAL GAS ROOM GREENHECK SP -8110 120 -1 -60 30 0.375 DIRECT 1.6 10 LBS. W80 S EF -7 SUBSTERILE /DIRTY ROOM GREENHECK SP -A510 120 -1 -60 200 0.375 DIRECT 2.3 31 LBS. WATTS EF -8 LUNCH ROOM GREENHECK SP -A290 120 -1 -60 130 0.400 DIRECT 2.0 21 LBS. WATTS NOTES: 1. INTERLOCK WITH LIGHTSWITCH (LION). 5. MOTOR SHALL COMPLY WITH FLORIDA ENERGY CODE AND SHALL BE A MIN. OF 87 %EFF. 2. UNIT - MOUNTED SPEED CONTROLLER. 6. ALL FANS SHALL BE MIN. UL -705 LISTED. 3. PROVIDE BACKDRAFT DAMPER. 7. MANUFACTURER SHALL PROVIDE SPEED CONTROLLER FACTORY WIRED FOR ONE POINT CONNECTION 4. PROVIDE FACTORY ISOLATORS FOR ALL EXHAUST FANS 8. INTERLOCK EF -5 & EF -7 WITH AHU -106. ASHRAE 62 CONFORMANCE UNIT � OCCUPANCY (# OF PEOPLE) INTERMITTENT OCCUP OCCUPANCY O.A. VENTILATION (CFM PER PERSON) VENTILATION ON TOTAL AREA SERVED o -0 C FACTOR ( *) 0 (CFM) (CFM) o AHU -103 24 0.63 20 296 300 SW OFFICE AHU -104 7 1.00 20 140 140 SW OFFICE AHU -105 10 0.85 20 170 240 SE OFFICE AHU -106 8 1.31 20 210 400 " OPERATING AREA V) ° on Wp �LL. -4- _� , NOTE: *ASHRAE 62 -1989 ALLOWS "WHERE PEAK OCCUPANCIES OF LESS THAN THREE HOURS DURATION OCCUR, THE OUTDOOR AIR FLOW RATE MAY BE DETERMINED ON THE BASIS OF AVERAGE OCCUPANCY FOR BUILDING FOR THE DURATION OF OPERATION OF THE SYSTEM, PROVIDED THE AVERAGE OCCUPANCY USED IS NOT LESS THAN ONE - HALF THE MAXIMUM. •* PROVIDED 25 AIR CHANGES PER HOUR (ACH) FOR SUPPLY AIR AND 5 ACH FOR FRESH AIR. REVISIONS No. OWNER REGIV. REV. (3- 13 -06) Q i 0 0 %4 o -0 C °L -+- 0 w W et- o LL O �o 20100 n.e. 21 avenue no. miami beach, fl 33179 N 4) U 2 i 0 0 %4 o -0 C °L -+- 0 w W et- o LL O �o Q Im C- m M v v= F- V m O :D O LL 1V Q v (n O J O LEI iE in a or 13039 c DRAWN M.R. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 SHEET M -3 lor 6 SHEETS Q < n0 i V) 0 %4 O -0 C LL_ 0 w W et- w LL DRAWN M.R. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 SHEET M -3 lor 6 SHEETS Q < n0 i V) 0 C CE O -0 C LL_ 0 cc w LL O Q W 44 v= F- V m Ld > :D O LL ■ (n O J O LEI iE in zo -a V) ° on Wp �LL. -4- _� , 2 W ( .l2 DRAWN M.R. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 SHEET M -3 lor 6 SHEETS