06-785-008EXIST. EQUIPMENT & WIRING SCHEDULE Qt 8 SETS OF [4- 500MCM -4 "C.] PLUS (2) SPARE 4 "C. 4 -600 MCM -4 "C. d 2 [4- 600MCM & 1 #1 /0(G) - 3- 1/2 "C.] 4� LINE GUTTER: 12" x 12 "x 60" (MIN.), WITH (2) 600 MCM PER PHASE AND NEUTRAL RUN ACROSS ENTIRE LENGTH. PROVIDE POLARIS OR EQUAL PRE - FORMED TAP KIT W/ MIN. OF (1) #4- 500MCM SPARE TAP. �5 4- 350MCM & 1 #1 /0(N) - 3 "C. 400A.- 3PH -4W ELECTRIC METER �7 3P -400A. (L- FRAME) MAGNETIC -ONLY CIRCUIT BREAKER WITH SOLID NEUTRAL IN NEMA 1 /U.LS.E. ENCLOSURE. Q FIRE PUMP CONTROLLER (WYE- DELTA). REFER TO FP -OWGS. Q 4- 350MCM & 1 #3 (G) - 3 "C. 10 4 -500 MCM & 1 #3(G) -3 "C. 11 4 # 4/0 & 1 #3 (G)- 2- 1/2 "C. 4 # 6 & 1 #8(G) - 1-1/4-C. 4 If 1/0 & 1 #6 (G)- 2 "C. 14 ELEVATOR MACHINE FUSED DISCONNECT SWITCH 3P- 200A. -25OV. W/150A. RK5 FUSES. NEMA 1 ENCLOSURE. Q 3 #1/0 & 1 #6((;)- 2 "C. TO ELEVATOR MACHINE (25 HP). 1� PHOTOCELL. INTERMATIC # K4236M. 17 8P -30A. MECHANICALLY -HELD LIGHTING CONTACTOR IN NEMA 1 ENCLOSURE W /120V. COIL, 2 -WIRE CONTROL RELAY AND H -O -A SWITCH ON COVER. 3 # 14- 3/4 "C t9 1P- 20A.- 120/277V., 24 -HOUR ELECTRONIC TIME SWITCH WITH BATTERY CARRYOVER. INTERMATIC MODEL No. ET102C. 20 3P -225A FRAME -200A TRIP C.B.- 65,000 AIC WITH SOLID NEUTRAL IN NEMA 1 /U.L.S.E. ENCLOSURE. 21 PANELBOARD. REFER TO PANEL SCHEDULES. 2 SERVICE GROUND TO FOOTING REBARS, TO 5/8 "0 x 10' -0" COPPERCLAD DRIVEN GROUND ROD & TO COLD WATER PIPE. LINE GUTTER: 10" x 10 "x 48" (MIN.), WITH (1) 600 MCM PER PHASE AND NEUTRAL RUN ACROSS ENTIRE LENGTH. PROVIDE POLARIS OR EQUAL PRE - FORMED TAP KIT W/ MIN. OF (1) #4- 500MCM SPARE TAP. TYPE: SIEMENS MAIN BUS: 225 AMP SERVICE: 120208V, 30,4W PANEL 73' NEUTRAL: FULL MOUNTING: SURFACE MAINS: M.L.O. POLES: 42 A.I.C. 10K SERIES DEM. kVA NO DEM WA TRIP! POLE CONDUIT WIRE REMARKS CKr �' CKT �' REMARK WIRE CONDO TRIP/ POLE NO DEM kVA , DEM. kVA 144 1.0 20 -1 1/2 12 RECEPTACLES 1 12 OFFICE LIGHTING 10 1/2 20 -1 1.6 NO. DESIGNATION 0.8 20 -1 1/2 12 RECEPTACLES 3 4 OFFICE LIGHTING 10 1/2 20 -1 1.2 2 SETS OF 41600 & #110(G);:S lj2 "C 130 0.8 20 -1 1 12 SPARE 5 6 OFFICE LIGHTING 10 1/2 20 -1 1.2 220 611 1.2 20 -1 1/2 12 RECEPTACLES 7 8 RECEPTACLES 12 1/2 20 -1 1.0 800 800 1.0 20 -1 1/2 12 RECEPTACLES 9 10 RECEPTACLES 12 1/2 20 -1 1.0 TOTAL CONNECTED LOAD Ln_i2557 1.0 20 -1 1/2 12 RECEPTACLES 11 12 RECEPTACLES 12 1/2 20 -1 1.0 SPACE 43.4 CONNECTED LOAD = 69.1 KVA SEE SECTION 1 FOR TOTAL CONNECTED LOAD ❑1 NON CON CURRENT LOAD; LOCATED A MAIN ROOF 1.0 20 -1 1/2 12 RECEPTACLES 13 14 RECEPTACLES 12 1/2 20 -1 1,5 1.2 20 -1 1/2 12 RECEPTACLES 15 161 RECEPTACLES 12 1/2 20 -1 1,2 0.8 20 -1 1/2 12 RECEPTACLES 17 18 SPACE 12 1 2 20 -1 1.5 1.0 20 -1 1/2 12 RECEPTACLES 19 20 1 ACCU -103 8 3/4 50 -3 0.7 1 8.4 50 -2 3/4 8 AHU -103 F 21 22 PANE12G2' 6 1 60 -2 4.6 20 -1 SPARE 23 24 TANKLESS W.H. 8 3/4 50 -2 9 10.7 70 -2 1 1/4 4 AHU -104 251 1 26 EWH 10 1/2 30 -2 4.5 20 -1 SPARE 27 281 EF -3 & 8 12 1Z2 20 -1 0.5 9 50 -2 3/4 8 TANKLESS W.H. 29 30 SPARE 20 -1 1.0 SPACE 31 32 ACCU -104 6 1 60 -3 1.0 1.0 20 -1 SPARE 33 34 SPARE 1 20 -1 1.0 1.0 20 -1 SPARE 35 36 OFFICE LIGHTING 10 1/2 20 -1 1 1.3 SPACE 37 38 OFFICE LIGHTING 10 1/2 20 -1 1.3 SPACE 39 40 OFFICE LIGHTING 10 1/2 20 -1 1.2 SPACE 1411 42 OFFICE LIGHTING 10 1/2 20 -1 1.2 31.9 19.7 TOTAL CONNECTED LOAD = 52.0 KVA = 144 AMPS n' NON CON CURRENT LOAD; LOCATED ON ROOF W.P. ENCLOSURE MOUNTED 1! -KOHLER MODEL 30REOZJB finai/nAiC3 %A .. FlillIZZIMITAME' 1 ST FLOOR EXIST. WIREWAY #1 SUMMARY SERVICE: 120/208V, 30.4W TENANTS KVA AMP OVER CURRENT PROTECTION FUTURE PANEL'Tt' 36.8 102 200 AMP FUTURE PANEL'T2' 37.1 103 200 AMP PANEL'T3' 52.0 144 200 AMP PANEL 'T4' /'G' 134.5 375 400 AMP TOTAL CONNECTED LOAD 1 260.4 1 724 TYPE: SIEMENS MAIN BUS: 400 AMP SERVICE: 120/208V, 30,4W PANEL eG' NEUTRAL: FULL MOUNTING: SURFACE MAINS: 3P 300 A MCB POLES: 24 A.I.C. 1OK SERIES DEM. WA NO DEM WA TRIP/ POLE NDUff WIRE REMARKS C T NO 'KT NO• REMARKS WIRE CONDO TRIP/ POLE NO DEM WA DEM. WA 231 0.4 20 -1 1/2 12 SERVER t 12 1 REFRIGERATOR 10 1/2 20 -1 1.2 NO. DESIGNATION 0.8 20 -1 1/2 12 PRE OP AREA 3 4 MICROWAVE 10 1/2 20 -1 1.5 2 SETS OF 41600 & #110(G);:S lj2 "C 130 0.4 20 -1 1/2 12 OR ROOM WORK STATION. 5 6 COMPUTER OUTLETS 10 1/2 20 -1 0,6 220 611 0.7 20 -1 1/2 12 JOVERNIGHT STAY BED 7 8 COMPUTER OUTLETS 10 1/2 20 -1 0,6 800 800 1.8 20 -1 1 2 12 O.R. RM. LTG. 9 10 COMPUTER OUTLETS 10 1/2 20 -1 0,6 TOTAL CONNECTED LOAD Ln_i2557 1.8 20 -1 1/2 12 LIGHTING 11 12 COMPUTER OUTLETS 10 1/2 20 -1 0,6 SPACE 43.4 CONNECTED LOAD = 69.1 KVA SEE SECTION 1 FOR TOTAL CONNECTED LOAD ❑1 NON CON CURRENT LOAD; LOCATED A MAIN ROOF 1.8 20 -1 1/2 12 LIGHTING 13 14 SPACE 12 1 Z2 20 -1 1.5 1.8 20 -1 1/2 12 LIGHTING 15 16 SPACE 12 1/2 20 -1 1.5 1.0 20 -1 1/2 12 SPARE 17 18 SPACE 12 1 2 20 -1 1.5 1.0 20 -1 1/2 12 SPARE 19 20 SPACE 12 1 2 20 -1 0.7 6.8 60 -2 1 6 PANEL'G1' 21 22 PANE12G2' 6 1 60 -2 4.6 20 -1 SPARE 23 24 OFFICE LIGHTING 10 1/2 20 -1 1.4 18.3 20 -1 7.3 CONNECTED LOAD = 25.6 KVA PLUS 25% CONTINUEOUS LOAD = 1.3 KVA TOTAL CONNECTED LOAD = 26.9 KVA (75 AMP) D NON CON CURRENT LOAD; LOCATED 0 MAIN ROOF TYPE: GE LINE ISOLATION MAINS: 3P60AMCB SERVICE IN: 1202O8V, 10, 3W PANEL 'G1' SERVICE OUT: 120208V. 10, 3W POLES: 12 WITH BUILT IN ISOLATION TRANSFORMER (10 KVA) DEM. WA NO DEM WA TRIP! POLE CONDUIT WIRE REEKS CHT NO. CKr NO. REMARKS WIRE CONDO TRIP/ POLE NO DEM WA DEM. WA 231 0.4 20 -1 1/2 12 O.R. EQUIP 1 2 O.R. EQUIP 12 1/2 20 -1 0.4 NO. DESIGNATION 0.8 20 -1 1/2 12 O.R. EQUIP 3 4 O.R. EQUIP 12 1/2 20 -1 0.8 2 SETS OF 41600 & #110(G);:S lj2 "C 130 0.5 20 -1 1/2 12 O.R. EQUIP 5 6 O.R. EQUIP 12 1/2 20 -1 0.5 220 611 0.7 20 -1 1/2 12 1 O.R. EQUIP 7 8 1 O.R. EQUIP 12 1/2 20 -1 0.7 800 800 1.0 20 -1 5 SPACE ISPARE 9 1101 SPARE SPACE 1/2 20 -1 1.0 TOTAL CONNECTED LOAD Ln_i2557 ___j 39 140 0' SPACE tt 12 SPACE 0 INCLUDES TENANTS 1 & 2 ( 73.9 KVA ) 41 142 SPACE 43.4 CONNECTED LOAD = 69.1 KVA SEE SECTION 1 FOR TOTAL CONNECTED LOAD ❑1 NON CON CURRENT LOAD; LOCATED A MAIN ROOF 3.4 20 -1 3.4 12 TOTAL CONNECTED LOAD = 6.8 KVA 33 AMP) TYPE: SIEMENS MAIN BUS: 60 AMP SERVICE: 120208V, 30,4W PANEL 'G2' NEUTRAL: FULL MOUNTING: SURFACE MAINS: MLO POLES: 12 A.I.C. 1 OK SERIES DEM. WA NO DEM WA TRIP/ POLE CONDUIT WIRE REMARKS CKT ND. T NO. REMARKS WIRE CONDO TRIP/ POLE NO DEM WA DEM. WA 231 0.6 20 -1 1/2 12 RECOVERY ROOM EQUIP 1 2 FUTURE Q.R. EQUIP 12 1/2 20 -1 0.4 NO. DESIGNATION 0.4 20 -1 1/2 12 RECOVERY ROOM BED 3 4 FUTURE O.R. EQUIP 12 1/2 20 -1 0.4 2 SETS OF 41600 & #110(G);:S lj2 "C 130 0.4 1 20 -1 1/2 12 FUTURE O.R. EQUIP 5 6 SPARE 2 SETS OF 41600 & 11/0(G); ^3 1/2 "C 6 20 -1 1.0 220 611 0.4 20 -1 1/2 12 FUTURE O.R. EQUIP 7 8 SPACE 220 611 3 35 800 800 1.0 20 -1 5 SPACE SPARE 1 9 1 1 10 SPACE SPACE 1/2 30 -2 5.0 TOTAL CONNECTED LOAD Ln_i2557 ___j 39 140 0' SPACE 11111 12 SPACE 0 INCLUDES TENANTS 1 & 2 ( 73.9 KVA ) 41 142 SPACE 43.4 CONNECTED LOAD = 69.1 KVA SEE SECTION 1 FOR TOTAL CONNECTED LOAD ❑1 NON CON CURRENT LOAD; LOCATED A MAIN ROOF 2.8 20 -1 1.8 12 TOTAL CONNECTED LOAD = 4.6 KVA (22 AMP) TYPE: EXST.SIEMENS'SB2' DEM. IVA NO DEM WA TRIP! POLE EXISTING MAIN BUS: 3000A CU. WIRE SERVICE: 1201208V, 30,4W 22 8.4 50 -2 _A.].0 :0(ISTIN3 --- - A PAN E L H DA 8 MOUNTING: FLOOR NO DEM kVA DEM. kVA 231 n Malrj ;